• 제목/요약/키워드: Exhausted heat from subway

검색결과 3건 처리시간 0.017초

미활용 에너지원으로서의 지하철 배열이용에 관한 연구 (Research on using the exhausted heat from subway tunnel as unused energy)

  • 김종렬;금종수;최광환;윤정인;박준택;김동규;김보철;정용현
    • 설비공학논문집
    • /
    • 제10권6호
    • /
    • pp.695-701
    • /
    • 1998
  • Researches on unused energy are being continued because of the limited fossil fuel and the destruction of environment. Therefore this study was peformed as follows. The collectable amount of exhausted heat for an air-conditioning was calculated by the subway thermal environment prediction program. And the electric power needed by conventional heat source equipments was compared with one by unused heat source equipments when the exhausted heat was used by heat pump in heating and hot water supplying. The results are summarized as follows; 1) Forced ventilation should be conducted to keep optimal temperature in subway tunnel in summer as well as in winter. According to the simulation, temperature in tunnel was higher than that on the ground in summer when the forced ventilation was conducted only in winter. 2) Ventilating time should be calculated out to the optimal condition for not only saving power of ventilation fan but reusing exhausted heat. By the simulation, it is certain that the exhausted heat should be eliminated in air-conditioning time. 3) The use of exhausted heat source heat pump could save 8% of electric power per hour in comparison with existing heat pump. It was based on a present heat generation and traffic for ventilating time of general air-conditioning, but could be different by ventilating time. 4) As the traffic increases up to 1.5 or 2 times, electric power consumption of the conventional heat pump increases to 11% or 13.5% per mean hour in comparison with that of the exhausted heat source heat pump, though all-day ventilation.

  • PDF

지하철배열 이용 시스템의 경제성 평가 (Feasibility study on waste heat utilization system in subway)

  • 이철구;김종대;임태순;방승기;함흥돈
    • 한국지열·수열에너지학회논문집
    • /
    • 제7권1호
    • /
    • pp.59-64
    • /
    • 2011
  • Feasibility study on energy saving system by utilizing exhausted heat from subway, which is one of the unused energy, was carried out. General heat source system using absorption chiller-heater was used for comparing to the energy saving system, and payback period method using initial cost and running cost of two systems, was used to perform economic estimation. Payback period was about ten years, and this period might be shortened if nation's economic support enact.

공기열원 히트펌프의 에너지원으로서 지하철 배열 이용에 관한 연구 (A study on the utilization of exhausted heat from subway for energy source of heat pump)

  • 김종렬;정기철
    • 한국가스학회지
    • /
    • 제4권4호
    • /
    • pp.13-19
    • /
    • 2000
  • 지구환경 보존 및 화석연료의 고갈에 대한 대책으로 미활용 에너지원에 대한 연구들이 진행되고 있다. 본 연구는 이러한 관점에서 지하철에서 배기되는 공기를 공기열원 히트펌프의 열원으로 이용할 수 있는가를 알아보기 위해 서울 지하철 5호선 Y역을 대상역으로 선정하여 터널내의 공기온도, 배열량을 시뮬레이션하였다. 이 배열량을 난방용 열원으로 히트펌프에 이용했을 경우 전력소비량과 대기를 직접 이용하는 히트펌프의 전력소비량을 계산하여 에너지 절약량을 검토하였으며, 여름철 냉방 유무 및 환기시간에 따른 터널내 온열환경을 파악하였다.

  • PDF