• 제목/요약/키워드: Ethane(R170)

검색결과 6건 처리시간 0.018초

Utilization Of Ethane As Working Fluid At Two-Stage Cascade Vapour Compression System

  • Kim, Yeong-Geun;Shin, You-Sik;Jeong, Hyo-Min;Chung, Han-Shik;Lubi, Rahadiyan
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.414-420
    • /
    • 2005
  • For supporting future demands of lower temperature. environmental friendly low- temperature refrigerants must be studied and developed to replace halocarbon. Ethane. which is one of hydrocarbon compound. is an environmental friendly refrigerant because it has zero ODP and GWP ${\sim}$ 20[per 100yr]. On this study, two-stage cascade refrigeration system was utilized to investigate performance of ethane on the low-stage. By employing R22 at higher stages. energetic performance as well as operating condition of R22/R170 system is compared to R22/R23. At low stage evaporation pressure ranges from 1.10 to 2.74 bar, R22/R170 shows higher COP over R22/R23. Furthermore, at the same range evaporation temperature R22/R170 can reach lower temperature.

  • PDF

캐스캐이드 냉동시스템에서 냉매로서의 프로판-에탄 냉매의 성능 분석 (The Characteristic of Propane(R290)-Ethane(R170) as Refrigerant in the Cascade Refrigeration System)

  • 김필환;이병호;정효민;정한식;김철수
    • 동력기계공학회지
    • /
    • 제11권4호
    • /
    • pp.50-55
    • /
    • 2007
  • Nowadays, demands on super low temperature condition for industrial and commercial uses are thriving. Considering of its wide application in the present and the future, study of the super-low temperature refrigeration system should be actively carried out. This study is aimed to investigate refrigeration capacity and coefficient of performance(COP) of the cascade refrigeration system, as well as to get the system which can reach evaporator temperature of $-70^{\circ}C$. For this purpose, R290 and R170 are charged in high stage and low stage respectively. Finally the characteristics of system using R290 and R170 will be proposed. Additionally, In this experiment, the flow rate of air flowing through the LS evaporator and the compressor inlet pressure were varied to investigate the refrigeration capacity and coefficient of performance characteristics.

  • PDF

액-가스 열교환기를 이용한 R170(에탄)용 냉동시스템의 성능 특성 (Performance Characteristics of Refrigerant R170(Ethane) Refrigeration System Using Liquid-gas Heat Exchanger)

  • 구학근
    • 동력기계공학회지
    • /
    • 제20권5호
    • /
    • pp.78-85
    • /
    • 2016
  • This paper considers the influence of internal heat exchangers to the efficiency of a refrigerating system using R170. These liquid-gas heat exchangers(internal or suction-line heat exchangers) can, in some cases, yield improved system performance while in other cases they degrade system performance. A steady state mathematical model is used to analysis the performance characteristics of refrigeration system with internal heat exchanger. The influence of operating conditions, such as the mass flowrate of R170, inner diameter tube and length of internal heat exchanger, to optimal dimensions of the heat exchanger is also analyzed in the paper. The main results were summarized as follows : the mass flowrate of R170, inner diameter tube and length of internal heat exchanger, and effectiveness have an effect on the cooling capacity, compressor work and RCI(Relative Capacity Index) of this system. Exception for the effect of inner diameter, the RCI of R170 with respect to refrigerant mass flowrate, the length and effectiveness of internal heat exchanger is about 2.1~3.3% higher than that of R13 at the same experimental conditions. With a thorough grasp of these effect, it is necessary to design the R170 compression refrigeration cycle using internal heat exchanger.

에탄을 사용한 2원 냉동 시스템의 성능 평가 (Study of Ethane Performance at Two-Stage Cascade Vapor Compression System)

  • 루비 라하디얀;김연근;정한식;정효민
    • 동력기계공학회지
    • /
    • 제10권2호
    • /
    • pp.75-82
    • /
    • 2006
  • 세계적인 환경 보호 정책에 따라 할로겐화탄소 냉매를 대체할 환경 친화적인 초저온 냉매의 개발과 연구가 활발히 진행되고 있다. 일반적으로 캐스캐이드 2원 냉동 시스템에서 아직까지 할로겐화탄소 냉매가 널리 사용되고 있다. 탄화수소 화합물의 한 종류인 에탄은 낮은 지구 온난화 지수와 낮은 오존층 파괴지수를 가진 친 환경적인 자연 냉매이다. 본 연구는 지구 온난화 지수가 높은 R-23 냉매와 비교하여 캐스캐이드 2원 냉동 시스템에서 에탄의 성능 시험을 목적으로 수행 하였다. 1원측에는 R-22를 사용하였으며, 증발 온도에 따른 성능은 R-23 보다 에탄(R-170)이 더 높게 나타났다.

  • PDF

액화질소 초저온과 이원냉동 초저온 냉열의 비교 실험적 연구 (A Study on the Cold Energy for Liquefied Nitrogen Gas and Cascade Refrigeration System)

  • 김철수;장현순;정효민;정한식
    • 동력기계공학회지
    • /
    • 제11권1호
    • /
    • pp.56-62
    • /
    • 2007
  • This paper represents the cold energy for liquefied nitrogen gas and cascade refrigerator. In this study, the vaporizer of liquefied nitrogen gas has the fin coil tube type with the dimension of inside diameter of 10mm and outside diameter of 12mm. Also, the total length of vaporizer is 20,000mm. The main experimental parameters are the mean velocity in duct and the supplied flow-rates of liquefied nitrogen gas. For the cascade refrigeration system, the refrigerants are ethane(R 170) in the high pressure stage and R 22 in the low pressure stage.

  • PDF