Prediction and Analysis of Electrical Environmental Characteristics under ±500kV HVDC Double Bipole Transmission Line (±500kV HVDC 2회선 송전선로의 전기환경특성 예측 및 평가)

  • Woo, Jeong Min;Ju, Mun-No;Shin, Koo Yong;Kwon, Gu Min;Choi, Woo Jung;Lee, Jae Hyun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.67 no.4
    • /
    • pp.554-560
    • /
    • 2018
  • Since Korea has a small land area, it is expected to construct the conductor return type with neutral wire in the case of ${\pm}500kV$ HVDC double bipole transmission line. Therefore, in order to apply ${\pm}500kV$ HVDC double bipole transmission line with neutral wire in Korea, it is necessary to develop technology for insulation and environmental designs. In this study, radio interference, audible noise, electric field and ion current density according to the polarity arrangement were compared and assessed in the ${\pm}500kV$ HVDC double bipole transmission line with the conductor return method. And the optimum configuration of HVDC double bipole transmission line was determined from the viewpoint of electrical environment.

Analysis of Electric field and Ion Characteristics on HVDC Overhead Transmission Line (초고압 직류가공 송전선로에서의 전계 및 이온류 특성분석)

  • Lim, Jae-Seop;Shin, Koo-Yong;Lee, Dong-Il;Ju, Mun-No;Yang, Kwang-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.9
    • /
    • pp.1638-1643
    • /
    • 2010
  • HVDC is better economic method than HVAC in case of long distance transmission and it is possible to interconnect transmission lines regardless of difference of power frequency. The electrical environment problems of HVDC overhead transmission line are electric field, charged voltage, ion current and so on. For biopolar HVDC lines, most of the ions are directed toward the opposite polarity conductor, but a significant fraction is also directed toward the ground. These problems are major factor to design configuration of HVDC overhead transmission line. Therefore, It is necessary to test an environmental characteristics of HVDC overhead transmission line. In this paper, to assess the ion characteristic of HVDC transmission line, continuous measurements have been done on the biopolar single circuit line with ACSR 480mm2-6 bundle conductors of Gochang HVDC Test line. And then the ion characteristics were analyzed.

The Study on the Efficient HVDC Capacity Considering Extremely Low Probability of 765kV Double Circuit Transmission Lines Trip

  • Moon, Bong-Soo;Ko, Boyung;Choi, Jin-San
    • Journal of Electrical Engineering and Technology
    • /
    • v.12 no.3
    • /
    • pp.1046-1052
    • /
    • 2017
  • The load on the power grid of South Korea is expected to grow continuously until the late 2020s, and it is necessary to increase the transfer capacity from the Eastern grid to the Seoul-Gyeonggi region by reinforcing the transmission network for the electric power system to remain stable. To this end, the grid reinforcement by two bipole LCC HVDC transmission systems have been considered on account of the public acceptability and high growth of the fault current level, even though an additional 765kV system construction is more economical. Since the probability of the existing 765kV double circuit transmission line trip is extremely low, a dynamic simulation study was carried out to estimate the efficient HVDC capacity able to stabilize the transient stability by utilizing the HVDC overload capability. This paper suggests the application plan to reduce the HVDC construction capacity with ensuring the transient stability during the 765kV line trip.

Assessment of the Electrical Environmental Characteristics to Decide Optimal Bundle Type for HVDC ${\pm}500kV$ Overhead Transmission Lines (HVDC ${\pm}500kV$ 가공 송전선로의 최적 도체방식 선정을 위한 전기환경특성 평가)

  • Ju, Mun-No;Kil, Gyung-Suk;Yang, Kwang-Ho;Lee, Sung-Doo;Hwang, Gi-Hyun
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.11
    • /
    • pp.520-526
    • /
    • 2006
  • Corona interferences, such as radio noise, audible noise and television noise, need to be taken into account in the design of HVDC transmission line conductor configuration. Therefore the line designer requires data from which to estimate the corona performance of any set of conductors. To get a sufficiently complete set of design data, it is necessary to examine the corona test of a large number of conductor geometries. This paper presents the results of corona cage test among three types of candidate conductors. It is quite clear from test results that the conductor geometries play an important role in establishing the magnitude of corona noise. Corona noise data from corona cage test are expressed as a statistical distribution of results obtained over long periods of time and various weather conditions. Therefore we can determine an environmentally-friendly conductor bundle for HVDC overhead transmission line. Based on this finding results, various simulations about HVDC line configurations, such as pole space and pole height, will be conducted. And then finally an optimal configuration for HVDC transmission line will be decided.

The Development of System for Measuring Ion Generated from HVDC Overhead Transmission Line (초고압 직류 가공 송전선로에서 발생되는 이온 계측시스템 개발)

  • Ju, Mun-No;Yang, Kwang-Ho;Lee, Dong-Il;Shin, Koo-Yong;Lim, Jae-Seop
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.11
    • /
    • pp.2035-2040
    • /
    • 2008
  • The electrical discharge of high voltage direct current(HVDC) overhead transmission line generate audible noise, radio noise, electric field, ion current and induced voltage on the ground. These items are major factors to design environmentally friendly configuration of DC transmission line. Therefore, HVDC transmission lines must be designed to keep all these corona effects within acceptable levels. Several techniques have been used to assess interference caused by ions on HVDC overhead transmission line. In this study, to assess the ion characteristic of DC line, the ion current density and induced voltage caused by ion flow were measured by plate electrodes manufactured from a metal flat board and charged bodies, respectively. The charged body has two types of cylinder and cylindrical plate. From the results of calibration experiments, the sensitivity of flat electrode and charged body can be obtained. At present, the developed system is used to investigate the ion generation characteristics of Kochang DC ${\pm}500kV$ test line.

Ion Effects of HVDC ±500 kV Double Bipole Overhead Transmission Line with Metallic Return Conductor Using Full-scale Test Line (실증시험선로를 이용한 도체귀로형 HVDC ±500 kV Double Bipole 가공송전선로의 이온류 특성 평가)

  • Shin, Kooyong;Kwon, Gumin;Ju, Munno;Woo, Jeong Min
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.5 no.4
    • /
    • pp.249-256
    • /
    • 2019
  • A full-scale test line was established to verify the electrical environmental interferences caused by the HVDC ±500 kV Double Bipole overhead transmission line with metallic return conductor, which is scheduled for construction in Korea and the fullscale test was conducted for one year. And through the human perception test of the DC electric-field under the HVDC Double Bipole line, the threshold value at which the human detects DC electric field was investigated to verify the validity of the design guide for the HVDC ±500 kV Double Bipole overhead transmission line. The polarity configuration of the HVDC ±500 kV Double Bipole test line was arranged diagonally with the same polarity in terms of the electrical environment disturbance and operation. The test line utilized the 6-bundle arrangement to prevent the corona discharge taking into account the domestic social acceptability. The test results show that the HVDC ±500 kV Double Bipole transmission line generated very little corona discharge from the conductors. Therefore, both DC electric field and ion current density met the domestic design guide for DC overhead transmission lines. Also, the human perception test of DC electric fields under the test line showed that 70% of participants did not recognize the DC electric field even when exposed to 23 kV/m.

Development of Corona Cage Measurement System for Simulation on Electrical Environmental Characteristics of HVDC Overhead Transmission Line (HVDC 가공 송전선로 전기환경특성 모의시험용 코로나 케이지 계측시스템 개발)

  • Kil, Gyung-Suk;Yang, Kwang-Ho;Lee, Sung-Doo;Ju, Mun-No
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.5
    • /
    • pp.245-249
    • /
    • 2006
  • Corona characteristics of conductors are dependent on the electric field conditions in the immediate vicinity of the conductors. In case of DC transmission line, particularly, the space charge plays an important role in the electric field distribution. Therefore, DC corona cage simulation is necessary for long-term test in the same conditions. This paper presents the results of designing and constructing hardwares such as DC power supply, measurement system and DAS to carry out the simulation. The corona cage longitudinally is divided into five equal length sections and three inner sections of those are isolated from the ground of outer cage. The measurement items are radio noise, corona current, television noise, audible noise and meteorological conditions. In the next step, various simulations about the type and configuration of two or three candidate conductors will be conducted. And then finally an environmentally-friendly conductor for HVDC overhead transmission line will be decided.

Linearity Optimization of DC CT and a Study on the Application of HVDC System (HVDC DC CT 선형성 최적화 및 시스템 적용에 대한 연구)

  • Choi, Yong-Kil;Lee, Eun-Jae;Choi, Ho-Seok;Lee, Wook-Hwa
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.6
    • /
    • pp.758-763
    • /
    • 2014
  • These days, the advantages of DC power system are consistently stand out in korea that was a small power loss and high stability. Needs of DC power transmission technology is focused In the midst of a smart grid and environment friendly generation technology boom that is needed for next generation technology. Researches and businesses for HVDC(High Voltage Direct Current) system has been began. But, Needs of HVDC equipment and system commissioning technology are not on the rise until now. In particular, South Korea's HVDC technology is after the foot runner of advanced country and company. In addition, There is no experience for equipment verification and commissioning technology. And Experts of HVDC are rare. Who has been fully understood hardware and system as a whole, and identified all the equipment's characteristic. Recently, Academia and industry are recognized a needs of HVDC technology. But it does not received a recognition of technical value. In this paper, introduce issues when we apply the IEEE's verification method for HVDC system, especially DC current measurement system, DC CT(Direct Current Transformer), among the HVDC equipments. And Proposes remedial methods on the issue in order to recognize the necessity that was HVDC equipments's verification and commissioning technology research should be focused on.

Study on the Air Insulation Design Guideline for ±500 kV Double Bipole Transmission Line with Metallic Return Conductor (도체귀로형 ±500 kV Double Bipole 송전선로 공기절연에 관한 연구)

  • Shin, Kooyong;Kwon, Gumin;Song, Seongwhan;Woo, Jungwook
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.5 no.3
    • /
    • pp.141-147
    • /
    • 2019
  • Recently, the biggest issue in the electricity industry is the increase in renewable energy, and various technologies are being developed to ensure the capacity of the power system. In addition, super-grids linking power systems are being pushed to utilize eco-friendly energy between countries and regions worldwide. The HVDC transmission technology is required to link the power network between regions with different characteristics of the power system such as frequency and voltage. Until now, Korea has applied HVDC transmission technology that connects mainland and Jeju Island with submarine cables. But, the HVDC transmission technology is still developing for long-distance high-capacity power transmission from power parks on the east coast to load-tight areas near the metropolitan area. Considering the high population density and mountainous domestic environment, it is pushing for commercialization of the design technology of the ${\pm}500kV$ Double Bipole with metallic return wire transmission line to transmit large-scale power of 8 GW using minimal right of ways. In this paper, the insulation characteristics were studied for the design of double-bipole transmission tower with metallic return wire, which is the first time in the world. And the air insulation characteristics resistant to the various overvoltage phenomena occurring on transmission lines were verified through a full-scale impulse voltage test.

Reliability Assessment in Hea-nam Cheju HVDC system using Well-being Method (Well-being기법을 이용한 해남-제주간 HVDC System신뢰도평가)

  • Son, Hyun-Il;Lee, Hyo-Sang;Shin, Dong-Joon;Kim, Jin-O
    • Proceedings of the KIEE Conference
    • /
    • 2004.11b
    • /
    • pp.227-229
    • /
    • 2004
  • In a new competitive market environment, it is very important to determines how much power can be transferred through the network. It's known as Available Transfer Capability(ATC). This paper presents a technique to evaluate Reliability Assesment and the Available Transfer Capability of Haenam-Cheju HVDC transmission system using Well-being Method which is based on the probabilistic method. The system Well-being is categorized in terms of the system Healthy and Marginal in addition to the conventional Risk index. Haenam-Cheju HVDC system has been studied for the optimal ATC based in well-being categories.

  • PDF