Analysis of RSET According to Exit Installation Standards for the Exterior of a Food Manufacturing Plant Building (식품공장 건축물 바깥쪽으로의 출구 설치기준에 따른 RSET 분석)

  • Park, Ha-Soung;Lee, Jae-Wook;Kong, Ha-Sung
    • The Journal of the Convergence on Culture Technology
    • /
    • v.10 no.2
    • /
    • pp.201-208
    • /
    • 2024
  • In this study, we investigated whether the evacuation time according to the exit installation standards specified in the building code during a food factory fire is compatible with the evacuation time based on the performance-based design specified by the fire department, in order to determine if evacuation safety is ensured. We used the Pathfinder program to confirm the evacuation time, and experimented with three scenarios for exit installation standards towards the outside of the building: 60m, 80m, and 100m. The target building in the experiment corresponded to the building code's exit installation standard of 100m from each dwelling. The experimental results showed tt in the cases of 80m and 100m, ASET exceeded RSET, indicating tt evacuation safety was not ensured, while in the case of 60m, evacuation safety was maintained. Through this study, it was confirmed tt even when the exit installation standards towards the outside of the building are met, evacuation safety may not be guaranteed.

A Study on the Fire Life Safety Improvement in Deteriorated Buildings - Focus on the Jongro Goshiwon Fire Analysis (노후 건축물의 화재인명안전 개선방안에 관한 연구 - 종로 고시원 화재사고의 분석을 중심으로 -)

  • Choi, Doo Chan
    • Fire Science and Engineering
    • /
    • v.32 no.6
    • /
    • pp.63-68
    • /
    • 2018
  • In this study, to recognize the limitations and problems of fire safety in existing deteriorated buildings in Korea, and to analyze the fire case of Jongno Gooshiwon, the fire life safety assessment was performed and analyzed through fire egress simulation and analyzed the domestic and foreign related codes and regulations. In order to secure the fire safety of existing deteriorated buildings, it is necessary to adopt the systematic introduction and application of fire safety performance evaluation of buildings based on quantitative and objective indicated method for performance maintenance and management for fire life safety.