• Title/Summary/Keyword: ESFR sprinkler

Search Result 1, Processing Time 0.02 seconds

[Retracted]Evaluation of Early Suppression-Fast Response (ESFR) Sprinklers in Facilities and Residences for Elderly People ([논문철회]노인관련시설에서 조기반응형 스프링클러헤드의 유용성)

  • Choi, Young-Sang;Gong, Ye-Rin;Kong, Ha-Sung
    • Fire Science and Engineering
    • /
    • v.29 no.4
    • /
    • pp.15-20
    • /
    • 2015
  • This study compared, through a fire simulation, temperature changes of the smoke layer and the air layer, and height fluctuations of the smoke layer, according to the sprinkler head installation and non-installation, and the sprinkler head types in elderly-care facilities. When a standard response sprinkler worked, the radiant heat exceeded the conditions for the occurrence of flashover. However the ESFR sprinkler prevented flashover. When the early response head worked, inhabitants were not damaged by radiant heat because the maximum value of the heat flux remained $2,293W/m^2$, which is less then the burn hazard criterion of $4,000W/m^2$. The highest temperature of the room when fire occurred exceeded the safety standard in all of the smoke layer and the air layer, but the highest temperature was kept below the safety standard after it fell down rapidly. Because the height of the smoke layer was maintained above 1.1 m when the early response sprinkler worked, the falling of the smoking layer was much more delayed than in the case where the standard response sprinkler was used.