• Title/Summary/Keyword: EQ Master List

Search Result 1, Processing Time 0.015 seconds

Analysis of Loss of HVAC for Nuclear Power Plant (원전의 공기조화설비(HVAC) 상실사고 분석방법)

  • Song, Dong-Soo
    • Journal of Energy Engineering
    • /
    • v.23 no.1
    • /
    • pp.90-94
    • /
    • 2014
  • Environmental qualification (EQ) for safety-related equipment is required to ensure that those equipment will perform their required function even under the harsh environment conditions arising from design basis accident in the nuclear power plant. As a part of EQ program, the room temperature analysis in case of a loss of Heating, Ventilation, and Air Conditioning(HVAC) system was carried out to ensure the operability of the safety-related equipment of a nuclear power plant randomly chosen among the Korean nuclear power plants. In this paper, this analysis was performed in the conservative perspective using GOTHIC code. The room temperature analysis includes selecting the rooms in which the safety related equipment are located but not supported by safety related HVAC and determining the temperature of the selected rooms. Target rooms for the analysis consist of W229/W237 (Aux. feedwater pump room), W232 (Aux. feedwater tank room) and W230 (Equipment passageway). The results showed the temperature range from $43^{\circ}C$ to $83^{\circ}C$, in 72 hours after a loss of HVAC. Those values are far below of generic EQ temperature($171^{\circ}C$). Therefore, it is satisfied with EQ requirement of temperature limits on safety related equipment.