• Title/Summary/Keyword: EHP(Electric Heat Pump)

Search Result 22, Processing Time 0.023 seconds

Economic Analysis of Heating and Cooling System Corresponding to the Energy Cost of University Building (대학건물에서 에너지비용 변화에 따른 히트펌프 냉난방시스템에 대한 경제성 분석)

  • Kim, Dong-Wan
    • Journal of the Korean Institute of Educational Facilities
    • /
    • v.16 no.1
    • /
    • pp.43-50
    • /
    • 2009
  • This research is to analyze LCC of Heat Pump system in university building by reduction of electric power costs for education and incentive system for gas. Produced details item different expense of EHP and GHP equipment construction step and preservation administration step. Analysis result is as following. 1) Executed LCC analysis for target system after lowering whole curriculum reduction of electric power costs for education. Analysis result, energy cost-cutting effect of EHP appears greatly than GHP unlike existent study finding, EHP decided by economical system. 2) Sensitivity analysis executed by incentive 500,000 won per units and geometrical ration of gas expense by 1%. As a result, because lowering effect of electric charges appears greatly, EHP decided by more economical system than GHP. As research result of front is different from existent study finding, EHP by lowering of electric charges for alteration and education of governmental frequent volunteer system was decided by more economical system than GHP.

Analysis of Energy Consumption & Environmental Load of Electric Heat Pump and Gas Engine Driven Heat Pump (전기구동 히트펌프(EHP)와 가스엔진구동 히트펌프(GHP)의 에너지소비량 및 환경부하 분석)

  • Kim, Sang-Hun;Lim, Sang-Cae;Chung, Kwang-Seop;Kim, Young-Il
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.933-937
    • /
    • 2006
  • Energy is motive power that makes convenient society. But, our country's energy is depending on most import. Also, energy and environmental issue are important problem in community of nations. The purpose of this study is to analysis the energy consumption and environmental load of EHP and GHP in Medium and small-scaled office building. The annual energy consumption used to cooling and heating by EHP was 10 percent more than GHP. And annual energy cost of EHP was 33 percent more expensive than GHP. But, Compared to the annual $CO_2$ emission, EHP was 6 percent less than GHP. Therefore, equipment selection should be consider environmental load as well as energy consumption and cost.

  • PDF

A study for a Performance analysis of Hybrid heat pump Air conditioning system (복합열원형 히트펌프 냉난방 시스템의 성능분석에 관한 연구)

  • Lim, Hyun-Mook;Park, Hee-Moon;Cho, Soo;Sung, Uk-Joo;Park, Jin-Hoon;Park, Tae-Jin
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.1373-1378
    • /
    • 2009
  • This study is aiming comparison and analization between efficiency of hybride air conditioning system which uses low temperature water under dam and air and EHP(Electric Heat Pump). The experimental was carried out with air cooling tests for EHP system having 80HP and composition heat pump system. P-i diagram of both systems and COP was used to derive schemetic and calcuations. As results of the tests, hybride system has 1.4 time higher efficiency coefficient.

  • PDF

Analysis on Cascade Cycle Heat Pump Application as Night Storage Heater (심야전력을 이용한 Cascade Heat Pump Cycle의 운전결과 분석)

  • JUNG, H.;HWANG, S.W.;LEE, C.H.
    • Journal of the Korean Society of Mechanical Technology
    • /
    • v.13 no.1
    • /
    • pp.113-118
    • /
    • 2011
  • To analyze and verify the effect of replacing thermal storage heater by a cascade cycle heat pump using midnight electricity was installed and tested at a customer's house in Wonju, Korea. The electric night storage heater is consist of 30kW electric heater and 2,700 liters of thermal storage water tank to supply hot water for warming house floor. The power for electric heater was cut off and hot water was only generated by cascade cycle heat pump. Current thermal storage water tank was not eliminated and electric heater wiring was modified. Some operation logic of the heat pump was also modified for proper operation. The required capacity of the heat pump and hot water temperature for given warming condition were estimated. The estimated capacity of heat pump was about 19kW and estimated hot water temperature for proper heating was at least $75^{\circ}C$.

Economic Evaluation of Various Cooling Systems (냉방기기별 경제성 평가)

  • Kim, Young-Il;Cho, Keum-Nam
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.214-219
    • /
    • 2008
  • In this study, medium capacity EHP and GHP for air-conditioning a building with a floor area of $1,200\;m^2$ are compared economically. To consider all the factors of initial and operation costs effectively, an annual equal payment method is proposed. For the initial cost, equipment, construction, installation, electric facility, financial subsidy and tax cut are considered. Basic electricity, energy(electricity and gas), space charge, labor, insurance and repair are considered for the operation cost. Under the assumptions made in this study, overall cost of EHP is less than that of GHP. However, different outcome may result if different assumptions are made. This study is useful for performing an economic evaluation of various air-conditioning systems.

  • PDF

The Economic Comparison of EHP and GHP for Medium Capacity Air-conditioning (중용량 공조에서 EHP와 GHP의 경제성 비교)

  • Kim, Young-Il
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.20 no.3
    • /
    • pp.167-174
    • /
    • 2008
  • Cost related to building equipment accounts for about 85% of the life cycle cost of buildings. Therefore proper selection of air-conditioning system is important for reducing the overall cost of buildings. In this study, medium capacity EHP and GHP for air-conditioning a building with a floor area of 1,200 $m^2$ are compared economically. To consider all the factors of initial and operation costs effectively, an annual equal payment method is proposed. For the initial cost, cost of equipment, construction, installation, electric facility, financial subsidy and tax cut is considered. Cost of basic electricity, energy(electricity and gas), space charge, labor, insurance and repair is considered for the operation cost. Under the assumptions made in this study, overall cost of EHP is less than that of GHP, but this is not absolute and different outcome may result if different assumptions are made. This study is useful for those who are interested in choosing an air-conditioning system that costs less for mid-size buildings with simple calculations.

Analysis on Economic Feasibility of Electric Night Storage Heat Pump as a Substitution of a Heater (심야전기보일러 대체 Heat Pump의 경제성 분석)

  • JUNG, H.;JO, J.Y.;Lee, C.H.
    • Journal of the Korean Society of Mechanical Technology
    • /
    • v.13 no.3
    • /
    • pp.119-124
    • /
    • 2011
  • Electric night storage heater was introduced and disseminated for power grid balancing and efficient management of power generation facility. But fuel cost for heating has been increased rapidly while the cost of electricity increased slightly. This abnormal rate system caused peak load in winter at last. To solve this problem, application of an air source heat pump was suggested. In the study, the effect of replacing night heater by heat pump and the economics were analysed. In addition the expectation of prospect of heat pump penetration was simulated based on surveyed and investigated data. As a result, fund supporting as well as institutional backing was needed for effective propagation and return of investment.

The Energy Consumption Characteristics of Building Accordance with Air-Conditioning and Heating System (건축물 냉.난방 시스템에 따른 에너지 소비 특성 -서울 소재 A 대학교 건축물을 중심으로-)

  • Park, Kang-Hyun;Cha, Jung-Hoon;Kim, Su-Min
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2011.11a
    • /
    • pp.333-337
    • /
    • 2011
  • Central control air-conditioning systems are being replaced with individually controlled air-conditioning system in the university. The amount of growth of electricity consumption is due to the increasing demand of electric heat pump. In winter and summer, the energy consumption showed a tendency to increase. On the other hand, showed less energy in spring and autumn. Increase the amount of electricity than the degree of decline in gas consumption was higher. Can be considered as transitional phenomena. Because electric heat pump, gas driven heat pump and the absorption chiller-heater are used at the same time in some of the buildings.

  • PDF

Economic Analysis of Heat Pump System through Actual Operation (교육 시설에서의 히트 펌프 냉난방 시스템 실사용을 통한 경제성 분석)

  • Kim, Gil-Tae;Cheong, Seong-Ir;Joo, Ho-Young;Ahn, Young-Chull;Lee, Jae-Keun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.19 no.6
    • /
    • pp.470-475
    • /
    • 2007
  • The present study has been conducted economic analysis through actual operation of electric heat pump (EHP) and gas engine driven heat pump (GHP) which are installed at the same building in the university. Cost items, such as initial cost, annual energy cost and maintenance cost of each system are considered to analyze life cycle cost (LCC) and economical efficiencies are compared. The initial cost is considered on the basis of actual cost, and annual energy cost is converted into the cost after measuring electricity and gas consumption a day LCC applied present value method is used to assess economical profit of both of them. Variables used to LCC analysis are electricity cost escalation rate, natural gas cost escalation rate, interest rate, and service lives when each of them are 4%, 2%, 8%, and 20 years. The result shows that EHP (148,257,306 won) is more profitable than GHP (161,239,296 won) by 8.05% (12,981,990 won).

Analysis of Electric Substitution Effects by the Gas Consumption and Characteristics of Gas Cooling System (냉방기기 사용량과 특성을 고려한 가스냉방기기의 전력대체 효과 분석)

  • Park, Rae-Jun;Song, Kyung-Bin
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.5
    • /
    • pp.669-675
    • /
    • 2012
  • Recently, the amount of electrical heat pump(EHP), a electrical conditioning equipment, is sharply increasing due to the luxury and multi-story trend of building. Accordingly, the cooling load that occupying substantial part of summer electric consumption has increased dramatically, making difficulties in domestic supply of electricity in summer. There are some efforts to replace it with an alternative cooling equipment such as gas heat pump(GHP), a gas cooling equipment, in order to solve the problem of summer electricity supply through reducing the summer electricity peak. It is rare, however, to find studies on the actual effects of GHP on the reduction of summer electricity peak. This study, therefore, estimated the effects of the GHP on the summer electricity peak by the gas consumption and characteristics of gas cooling systems. In addition, electric substitution effects by gas cooling systems were analyzed through case studies in the summer of 2010.