A Study on the Electromagnetic Transients at Switching Capacitor Banks in a Electric Distribution Electric Power Distribution Substation (배전변전소에서 캐패시터 뱅크 투입시 일어나는 전자과도 현상에 관한 연구)

  • 김경철
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.16 no.1
    • /
    • pp.92-99
    • /
    • 2002
  • Transient in an electric distribution system are mainly generated by switching. This paper presents analysis of switching surge and means of limiting the voltage magnification transient for high voltage power systems by using the EDSA's EMTAP software package. One means of limiting the voltage magnification transient is to convert the end-user power factor contraction capacitor banks to harmonics filters. An inductance in series with the capacitor bank was used to decrease the transient voltage at the customer bus to acceptable levels. And also simulation results used the EDSA harmonics analysis program show the effect of harmonics reduction.

A Study on Introducing Security Certification for Control Systems (제어시스템 보안인증 도입 방안 연구)

  • Choi, Hoyeol;Kim, Daeyeong;Shin, Hyungjune;Hahn, Changhee;Hur, Junbeom
    • Journal of the Korea Institute of Information Security & Cryptology
    • /
    • v.26 no.3
    • /
    • pp.725-734
    • /
    • 2016
  • SCADA(Supervisory Control and Data Acquisition) system is widely used for remote monitoring and control throughout the domestic industry. Due to a recent breach of security on SCADA systems, such as Stuxnet, the need of correctly established secure certification of a control system is growing. Currently, EDSA-CRT (Embedded Device Security Assurance-Communication Robustness Test), which tests the ability to provide core services properly in a normal/abnormal network protocol, is only focused on the testing of IP-based protocols such as IP, ARP, TCP, etc. Thus, in this paper, we propose test requirements for DNP3 protocol based on EDSA-CRT. Our analysis show that the specific test cases provide plentiful evidences that DNP3 should follow based on its functional requirements. As a result, we propose 33 specific test case for DNP3 protocol.

A study of the Distribution system of Harmonic Analsys and reduction of EDSA (EDSA를 이용한 수용가 설비의 전력품질 분석)

  • Kim, Yong-Ha;Lee, Bum;Lee, Sung-Jun;Lee, Jae-Geol;Yeon, Jun-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2002.11a
    • /
    • pp.319-324
    • /
    • 2002
  • This paper describes analysis of power quality in distribute network system. EDSA is used for simulations to the teal model system. Harmonic load flow, harmonic frequency scan studies, distortion levels, and filter design method. Through this paper, minimized injected harmonic by computating the capacitor of optimal filter satisfied with IEEE Std-519 applying to distribute system are analysed through detailed simulation.

  • PDF

Trend and verification measures of certification evaluation in control system (제어시스템 인증평가 동향 및 검증방안)

  • Ueda, Osamu
    • Proceedings of the Korea Information Processing Society Conference
    • /
    • 2016.04a
    • /
    • pp.259-262
    • /
    • 2016
  • 최근 중요 인프라 업계에서 주로 다뤄지는 제어시스템을 표적으로 한 사이버 공격으로 Stuxnet에 이어 Havex RAT, BlackEnergy2 라고 하는 멀웨어(Malware)를 이용한 사건이 많이 증가하고 있다. 제어시스템의 새로운 공격 방법에 대한 대책으로 시스템 입구와 내부조직에 대한 대책을 강화하기 위한 필요성이 요구되어 왔지만 그러한 대책은 한정되어 있다. 본 논문에서는 보안대책에 필요한 인증 취득에 있어서 기준이 되는 국제 표준인 ISASecure(R)EDSA 인증제도에 착목했다. 인증평가는 요구요건이 중복되는 불필요한 인증평가 작업을 최소화 하는 것으로 인증 취득 시 발생되는 코스트를 절감할 수 있으며 기존의 정보 보안 관리체계(lSMS)의 인증을 취득하고 있는 기업이나 조직이면 제어시스템의 인증 기준으로 추가된 차분 요건만으로 취득이 가능 할 수 있을 것으로 상정된다. 이러한 제어시스템의 보안을 구현하기 위해 IACS(Industrial Automation and Control System)에서 표준화로 제정한 IEC62443 시리즈를 참조하여 세계각국에서 사용되는 제어시스템을 대상으로 인증(EDSA) 요구사항의 차분을 도출하는 수법을 제안하고자 한다.

Transient Grounding Impedance Characteristics of a Copper Rod-type Grounding Electrode used for Electric Distribution Systems Using EDSA Program (EDSA 프로그램을 이용한 배전계통에 사용되는 동봉 접지전극의 과도 접지임피던스 특성)

  • Kim, Kyung-Chul;Oh, Kyung-Hoon;Kim, Min-Sung;Choi, Jong-Kee;Kim, Dong-Myung
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.8
    • /
    • pp.26-32
    • /
    • 2009
  • Grounding insures a reference potential point for electric devices and also provides a law resistance path for fault or transient currents in the earth. The ground impedance as a function of frequency is necessary for determining its performance since fault or transient currents could contain a wide range of frequencies. A copper rod electrode is the most commonly used grounding electrode in electric distribution systems. In this paper, the grounding impedance of copper rods has been measured in frequency raging from 60[Hz] up to 100 [kHz] and an equivalent model of the grounding impedance is identified from the measured values. The grounding impedance under study when a typical lightning surge is injected into the grounding system was simulated numerically and graphically through the use of the EDSA software program.

Harmonics Analysis and Reduction of Incheon International Airport (인천국제공항 여객터미널의 고조파분석에 의한 저감대책 강구)

  • Kim, Young-Ha;Lee, Sung-Jun;Kim, Dong Kun;Oh, Suk-Hyun;Kim, Mi-Ye
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.1
    • /
    • pp.87-93
    • /
    • 2005
  • In this paper, we perform the harmonic filter design for Incheon international airport, especially passenger terminal based on the results of measurement and analysis. Also, we show the waveform of machines which produce harmonics as a harmonic source. For harmonic filter design, we propose the APF(Active Power Filter) and ZSF(Zero Sequence Filter) design. Also, we simulate the filter effects using EDSA package. The results show the effectiveness of the method.

A Study on the Analysis of Harmonics Reduction Effects Using Single-tuned Filters In a Power System Included Power Converters (전력변환장치를 포함한 전력시스템에서 동조 필터를 이용한 고조파 저감 효과의 분석에 관한 연구)

  • 최홍규;김경철;강태은;전기원
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.14 no.3
    • /
    • pp.81-87
    • /
    • 2000
  • The increasing use of non-linear loads such as power electronics draw highly distorted currents from the utility system. High harmonics currents and voltages will cause equipment damage and disturb the plant operation. The common solution to harmonics problem is to use harmonics filters. In this paper simulation results used the EDSA harmonics analysis program verifying the effects of the single-tuned filter for harmonic elimination are presented.

  • PDF

A Study on the Security-Constrained Economic Dispatch for Power System (전력계통의 안전도를 고려한 경제급전에 관한 연구)

  • 김경철;최홍규;원진희
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.16 no.3
    • /
    • pp.7-14
    • /
    • 2002
  • The economic dispatch is one of the major concerns in case of buying and selling generated powers between electric powers companies. This paper describes the power system security the optimal power flow, and the security-constrained economic dispatch and shows the EDSA\`s active optimal power flow software package is well suited through a simple case study.

A Study on the Reliability of Electric Power Distribution System (배전시스템의 신뢰도에 관한 연구)

  • 김경철;최홍규;원진희
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.16 no.3
    • /
    • pp.61-66
    • /
    • 2002
  • Electric power distribution networks are prime examples of systems where a very high degree of reliability is expected. Reliability is the probability of a device or system performing its function adequately for the period of time intended and intented operating conditions intented. This paper shows that a better meshed distribution configuration over the case study of radial configuration distribution system was selected by comparing the indices obtained from EDSA\`s reliability worth assessment of distribution systems program.