Evaluation of Thermal Utilization of Dousing System in PHWR Nuclear Power Plant

  • Nam, S.D.;Ryu, J.I.
    • Journal of ILASS-Korea
    • /
    • v.4 no.3
    • /
    • pp.42-52
    • /
    • 1999
  • An effectiveness of thermal utilization of a dousing system in the 600 MW PHWR Nuclear Power Plant has been evaluated. The behavior and conditions of water droplet sprayed in a postulated accident conditions in containment configuration has been calculated. In this calculation, two pressure conditions with the consideration of obstruction area and containment wall effect has been established : one being the minimum containment pressure of 7 kPa(g) encountered for dousing shut off and the other being the containment design pressure 124 kPa(g). The results revealed that the effectiveness of the thermal utilization ranges from 93% to 97%. In the analysis on two cases without/with side wall effect in the containment building, the thermal utilization decreases with obstruction area from 89% to 85%, which satisfies the design criteria set for the containment pressure against the accident condition.