• 제목/요약/키워드: District Heating Pipe

검색결과 57건 처리시간 0.021초

지역난방용 Flexible Pipe 활용방안 연구 (A Study on the Application Method of Flexible Pipe for District Heating in Korea)

  • 이기섭;박남수
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.637-642
    • /
    • 2008
  • The concept of district heating involves centralised heat production where heat is distributed to consumer via a piping network. The objective of this work is to identify the Flexible Pipe from an economy, execution, maintenance point of view. Flexible Pipe has in some countries, especially in Europe, been used for many years in district heating. In spite of years of experience, there still exist doubts about the possibilities of using flexible pipes in district heating applications, mostly because of no experiences in domestic market. The advantage of flexible pipe systems is their flexibility. This holds not only for the inner pipe but also for the total pipe system including insulation and jacket. Even for the largest diameter the minimum radius of curvature is given to 1.5m. The most important difference between flexible pipe systems and preinsulated steel pipes is their simple and quick assembly. Such information could provide a basis for making reasonable hypotheses about consumer preferences, to foam a basis for making future marketing more effective.

  • PDF

3방 비례제어 조절밸브 개발 및 성능 연구 (Development of Three-Way Proportional Control Valve and Performance Study)

  • 이종화;정택수;조종두;김주용
    • 설비공학논문집
    • /
    • 제26권5호
    • /
    • pp.218-223
    • /
    • 2014
  • Korea District heating corp. recently give an attention to combine the district heating and supply pipes as a two pipe system that are in the present system separated with room heating and warm water supply pipe, and the two pipe system is commonly applied for heating service in European countries. In the new two pipe system, only one heat source is supplied to a house and partitioned into room heating and warm water supply by household substation. So the effective distribution of supplied heat source in accordance to user intention is very important. This paper presents the development and performance test of three-way proportional control valve for a combined heat source system in district heating. The proposed valve is controlled to partition heat source into two different directions : hot water distributor for space heating and household substation for warm water supply in response to the pressure drops of tap water caused by the user. The performance investigation is shown within 3% of error compared to the theoretical model of the three-way proportional valve and its controllability is verified.

지역난방 증기 터빈 내 조속기 밸브 Inlet pipe 파손 원인 분석 (Failure Analysis of an Inlet Pipe of a Governor Valve in a Steam Turbine of a District Heating System)

  • 채호병;김우철;김희산;김정구;이수열
    • Corrosion Science and Technology
    • /
    • 제21권1호
    • /
    • pp.62-67
    • /
    • 2022
  • The objective of this study was to perform failure analysis of an inlet pipe located in a governor valve of a steam turbine in a district heating system. During the operation, the temperature of the governor valve was increased to as high as ~500 ℃, which induced thermal expansion of the inlet pipe along both axial and radial directions. While the inlet pipe did not have contact with the valve seat, the side plane of the upside was constrained by the casing part, which led the inlet pipe to experience stress field in the form of fatigue and creep. The primary crack was initiated at about 30 mm below the top where the complex stress field was anticipated. These results suggest that the main failure mechanism is a combination of thermal fatigue and creep during the operation supported by the observation of apparent beach marks on the fracture surface and pores near the cracks, respectively.

난류발생기를 가지는 원형 파이프내에서의 마찰저감 및 열전달율에 관한 실험적 연구 (Experimental Study on the Drag Reduction & Heat Transfer Ratio in the Circular Pipe with Swirl Generater)

  • 김성수;조성환;윤석만
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.430-435
    • /
    • 2008
  • Total lengths of domestic pipe network for district heating system are above about 2,500Km. A lots of pumping power for heat transportation through long pipe are required by the flow friction of pipe surface. Until now there have been considered about various methods to reduce the flow friction for district heating system such as using surfactants and turbulence promoters by swirl flow and baffles etc. At this study, swirl flow generator was tested about the possibility to increase the heat transfer ratio at the heat exchanger in the case which the suppling water temperature increased from $50^{\circ}C$ until $120^{\circ}C$. Experimental results showed that the heat transfer ratio increased and also pressure increase ratio increased simultaneously in the case which swirl flow generator installed. The amount of the increasing ratio for heat transfer and pressure were reached until 4.33% and 11% at the case of $120^{\circ}C$ suppling temperature which domestic district heating system were using.

  • PDF

지역난방수 공급관 에어벤트 부식 파손 분석 (Corrosion Failure Analysis of Air Vents Installed at Heat Transport Pipe in District Heating System)

  • 이형준;채호병;조정민;김우철;정준철;김희산;김정구;이수열
    • Corrosion Science and Technology
    • /
    • 제19권4호
    • /
    • pp.189-195
    • /
    • 2020
  • Two air vents situated on a heat transport pipe in district heating system were exposed to the same environment for 10 years. However, one air vent was more corroded than the other. It also had a hole on the top of the front-end pipe. Comparative analysis was performed for these air vents to identify the cause of corrosion and establish countermeasures. Through experimental observation of the damaged part and analyses of powders sampled from air vents, it was found that corrosion was initiated at the top of the front-end pipe. It then spread to the bottom. Energy dispersive X-ray spectroscopy results showed that potassium and chlorine were measured from the corroded product in the damaged air vent derived from rainwater and insulation, respectively. The temperature of the damaged air vent was maintained at 75 ~ 120 ℃ by heating water. Rainwater-soaked insulation around the front-end pipe had been hydrolyzed. Therefore, the damaged air vent was exposed to an environment in which corrosion under insulation could be facilitated. In addition, ion chromatography and inductively coupled plasma measurements indicated that the matrix of the damaged front-end pipe contained a higher manganese content which might have promoted corrosion under insulation.

유한요소 시뮬레이션을 통한 지역난방열배관 특성 평가 및 강화이형관의 제안 (Design Validation and Improvement of District Heating Pipe Using FE Simulation)

  • 김주용;김호범;고현일;안영모;조종두
    • 대한기계학회논문집A
    • /
    • 제33권4호
    • /
    • pp.337-345
    • /
    • 2009
  • This paper investigates the reliability of district heating pipes at thermo-elastic fatigue loading. District heating pipes, subjected to $120^{\circ}C$ and $16kg_f/cm^2$ due to water distributing service through inside the pipes, should endure long term cyclic thermal-mechanical loadings. The heating pipes are the co-centric tubes of steel pipe, poly urethane(PUR) insulator, and high density poly ethylene(HDPE) case. On installation, foam pad is externally wrapped for accommodating stress reduction near the bend sections of pipes. However, there have been frequent reports on the failures of bend sections in the middle of long term service. This study scrutinizes the observed failures near the bend sections through applying the finite element methods. Specially in this study, heating pipes are studied on the influence of foam padding on failures and proposed new designs for reinforced bend without foam pad.

지역난방 구리난방환수관의 공식 원인 분석 (Investigation of Pitting Corrosion of Copper Heat-Return Pipe in District Heating)

  • 이근형;송민지;강태욱;김우철;김희산;이수열
    • Corrosion Science and Technology
    • /
    • 제23권4호
    • /
    • pp.315-323
    • /
    • 2024
  • This work examined pitting corrosion failure of a copper heat-return pipe used in a district heating system. The copper pipe was corroded with a 48% reduction in thickness due to localized corrosion on the inner surface exposed to heating water of 20 ~ 40 ℃. Fe and Si elements as corrosion products were found around pits. Cl element was also observed, which accelerated oxidation of copper inside pits. Cu2O deposits on the pit's bottom surface decreased the pH inside the pit. X-ray diffraction analysis revealed hematite, cuprite, malachite and brochantite as corrosion products. Chemical analysis demonstrated that Fe and Si elements did not exist in the copper, supply water, or heating water, indicating that Fe and Si species might have entered into the pipe from the exterior. These results indicated that pits were initiated due to ion concentration gradient near Fe and Si species. Moreover, the interior of pits had lower pH due to Cl- concentration and Cu2O reactions, which accelerated the pit's growth and led to formation of pinholes. Additionally, we confirmed that the type of pitting corrosion was a complex combination of types I and II based on the HCO3-/SO42- ratio, pH, temperature, and corrosion products.