  • Lightning arresters are deteriorated by repetition of protective operation against overvoltages or impulse currents in environments of its use. If a deteriorated arrester is left in power lines, it can lead to an accident such as a line to ground fault even in a normal system. Therefore, it is necessary to eliminate the deteriorated arrester in advance by checking the soundness of arresters on a regular basis, and to ensure the reliability of power systems by preventing accidents. Various deterioration diagnostic techniques and devices are suggested, and most of which measure leakage current components as an indicator of arrester ageing. However, the techniques based on the magnitude of leakage current measure simply RMS or peak value of leakage current components and do not provide detailed information needed in the diagnosis. In this study, we found that the wave height distributions of the total leakage currents are remarkably changed or a new wave height are produced with the progress of arrester deterioration. To propose a new technique for the diagnosis, we designed a leakage current detection unit and an analysis program which can measure leakage current magnitudes and analyze wave height distributions. From the experimental results, we confirmed that the proposed technique by analyzing the wave height distribution can simply diagnose the mode of defects such as a partial damage and an existence of punctures in arresters as well as deterioration of arresters.

폴리머 피뢰기의 구조에 따른 온도와 누설전류 특성 (Temperature and Leakage Current Characteristics of Polymeric Surge Arrester with Housing)

  • 조한구;유대훈;이운용;김하나
    • 한국전기전자재료학회논문지
    • /
    • 제20권3호
    • /
    • pp.273-280
    • /
    • 2007
  • In this paper, the ZnO surge arrester performance of power distribution class has been studied under different manufacturing conditions such as housing materials(polymeric, porcelain), interface sealants and one-body molding type. In the recent years, the polymeric ZnO surge arresters have been developed and put into operations based on their excellent characteristics. For polymeric surge arresters, the inner gas volume is extremely small, especially in solid insulation polymeric arresters there are not any gas volume inside arresters in the structure due to polymeric materials are filled into the internal gas volume. The sealing integrity is related to safe operation of surge arrester, the prime failure reason of porcelain housed arresters is moisture ingress. In this paper, the sealing integrity of polymeric surge arresters is investigated with moisture multi-aging test and ingress test. The evaluation techniques are used to inspect the sealing integrity of polymeric arresters, including leakage current, surface temperature, reference voltage and dissipation factor.

가속열화시험을 이용한 배전용 폴리머피뢰기의 장기신뢰성 평가기법 개발 (Development of Longtime Reliability Assessment Method of Polymer Housed Distribution Surge Arresters using Accelerated Aging Test)

  • 김주용;송일근;문재덕
    • 조명전기설비학회논문지
    • /
    • 제20권10호
    • /
    • pp.141-150
    • /
    • 2006
  • 본 논문에서는 폴리머피뢰기의 현장 열화인자를 인가할 수 있는 가속열화 시험장치를 제작하고 국내 환경조건을 모의할 수 있는 시험주기를 개발하여 폴리머피뢰기 완제품에 대한 장기신뢰성 평가법을 제안하였다. 그리고 가속열화시험 및 현장설치에 의한 전기적, 화학적 특성변화를 분석하여 폴리머피뢰기의 열화정도를 평가함으로써 본 연구에서 제안한 평가기법의 실효성을 검증하고 국산 폴리머피뢰기의 유지보수에 필요한 특성 데이터를 제시하였다.

배전선 1상의 피뢰기 및 가공지선 생략 방안 연구 (A Study on The Scheme for Omission of lightning Arresters on One-Phase and Overhead Ground Wires in the Power Distribution Lines)

  • 정현수;정창호;김진오;송일근;장완성
    • 조명전기설비학회논문지
    • /
    • 제15권2호
    • /
    • pp.13-20
    • /
    • 2001
  • 본 논문은 배전선에 설치하는 내뢰설비인 가공지선과 피뢰기의 특성과 생략 방안에 대하여 언급하였다. 특히, 피뢰기의 중간 상을 생략하는 방안에 대하여 EMTP 시뮬레이션을 실시하여 생략시 나타날 수 있는 문제점과 생략 방안에 대해 기술하였으며, 가공지선은 지정된 경우에는 생략이 가능하고 피뢰기는 중간 상을 생략시 건전상의 피뢰기 용량을 재검토해야 할 것으로 생각된다.

  • PDF

배전용 피뢰기의 접지도선 설치기법 (The Installation Technique of Grounding Electrode Conductors for Metal Oxide Distribution Surge Arresters)

  • 이복희;유인선;이태룡;안창환;윤중순;윤형희;김재승;김종채
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 C
    • /
    • pp.1718-1720
    • /
    • 2001
  • The route of surge arrester connection is very important because bends and kinds of leads increase the impedance to lightning surges and tend to nullify the effectiveness of a grounding electrode conductor. There is a need to know how effective installation of lightning surge arresters is made in order to control voltage and to absorb energy at high lightning currents. The effectiveness of a grounding conductor and bonding for 18[kV] metal oxide distribution line arresters was experimentally investigated with lightning and oscillating impulse voltages.

  • PDF

배전용 피뢰기의 가속열화시험 (Accelerating aging test of distribution lightning arresters)

  • 김주용;송일근;김찬영;이병성;문재덕
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 하계학술대회 논문집
    • /
    • pp.596-598
    • /
    • 2000
  • This paper presents a new accelerating aging test facility for distribution lightning arresters. Aging parameters of lightning arrester are moisture ingress, electrical stress and surge absorption and so on. In this system, we applied 13.2kV to 6 samples and controled temperature and humidity of chamber and measured leakage currents of the all samples. Also we developed accelerating aging cycle which consists of -35$^{\circ}C$∼90$^{\circ}C$ temperature and 40%∼90% humidity. Through the aging test we found out the leakage current of aged sample increases rapidly according to the temperature rising. Hereafter we can determine the replacement guide of leakage current for field operating arresters and condition assessment of aged samples through this aging test.

  • PDF

경년에 따른 배전용 피뢰기의 열화특성 (Characteristics analysis of field aged distribution surge arresters)

  • 조성수;김주용;김찬영;송일근;박중신
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2323-2325
    • /
    • 1999
  • This paper presents characteristics of the aged and new 18kV surge arresters. In order to investigate aging characteristics, we measured total leakage current and resistive leakage current using specially made leakage current measurement system and also investigated $tan{\delta}$ of the arresters and microstructure of the elements. Through the investigation we found that all of the arresters does not aged for 2 years field operation.

  • PDF

22.9kV 지중계통의 뇌과전압 해석 및 뇌서지 보호방안에 관한 연구 (A Study on the Lightning Overvoltage Analysis and Lightning Surge Protection Methods in 22.9kV Underground Distribution Systems)

  • 김상국;정채균;이종범;박왈서
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제53권8호
    • /
    • pp.454-460
    • /
    • 2004
  • The effects of surge arresters for protection of transmission systems against direct lightning strokes have already been reviewed using Electromagnetic Transients Program(EMTP). Distribution lines are spanned in much larger area than transmission lines, and therefore, are more susceptible to lightning strokes. We have modelled the 22.9kV underground distribution cable systems that have arresters and grounding wires. And this paper analyzes the overvoltages on underground distribution cable systems when direct lightning strokes strike on the overhead grounding wire using EMTP. Then we investigated that (1) the effects of lightning stroke according to underground distribution cable length (2) voltages at the riser pole and at the cable terminal according to installation of arrester. This study will provide insulation coordination methods for reasonable systems design in 22.9kV underground distribution cable systems.

수배전계통의 여러 가지 고장조건에서 피뢰기에 흐르는 누설전류 (Leakage Currents Flowing through Lightning Surge Arresters under Various Fault Conditions in Receiving and Distribution Power Systems)

  • 이복희;길형준;강성만;최휘성
    • 조명전기설비학회논문지
    • /
    • 제18권5호
    • /
    • pp.132-139
    • /
    • 2004
  • 수배전계통의 고장에는 1선 지락, 선간 단락, 2선 지락 등의 고장이 있다. 가공 배전 계통에서 일어나는 대부분의 고장은 1선 지락이며, 피뢰기는 이러한 고장에 의한 빈번한 과전압에 의해 스트레스를 받는다. 본 논문에서는 수배전계통에서 일어날 수 있는 고장을 모의하여 여러 가지 고장에 의해 피뢰기에 흐르는 누설전류의 특성에 대하여 조사하였다. 결과적으로, $\pm$10[%] 범위의 전압변동률에 의해서 피뢰기에 흐르는 누설전류는 거의 변화가 없었다. 성능이 우수한 접지 시스템 하에서는 전압변동률은 피뢰기의 긴 시간동안의 동작에 별 영향을 줄 수가 없었다. 하지만, 1선 지락 고장에서 피뢰기에 흐르는 누설전류의 최대값은 비효과적인 접지 시스템의 운전 전압에서의 누설전류와 비교하였을 때 140배 이상이 되었다. 그러나 선간 단락과 2선 지락 고장의 경우에는 피뢰기의 누설전류에 거의 영향을 미치지 못했다.

발변전용 피뢰기의 구조 및 ZnO 바리스터 소자의 전기적 특성 (Structure of Station Class Lightning Arresters and Electrical Characteristics of ZnO Varistor Blocks)

  • 조한구;한세원;이운용;윤한수;최인혁
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 하계학술대회 논문집 Vol.5 No.2
    • /
    • pp.1158-1161
    • /
    • 2004
  • This paper presents structural characteristics of station class lightning arresters and electrical characteristics of manufactured ZnO varistor blocks which are usable in those arresters. Three types of station class lightning arresters were investigated and those are a ceramic arrester, a FRP tube type polymer arrester, and a FRP rod type polymer arrester. Each arrester has merits and demerits with structural characteristics. In general, polymer arresters were made of silicon rubber for housing materials, FRP tube or rod for mechanical strength, ZnO blocks for electrical characteristics, and metal parts for electrical contact and the silicon rubber, the housing materials, was directly injected to the arrester module which was assembly composed of electrodes, ZnO blocks and FRP tube or rod, and to prevent the nonlinear electric fields distribution on upper parts of arresters, the grade ring was adopted to the upper electrodes. The reference voltage, nonlinear coefficient, residual voltage, and voltage ratio of manufactured ZnO varistors are 4.90kV, 50, 9.54kV, 1.94, respectively. Compared to designed electrical characteristics, the reference voltage was low for 600v and the voltage ratio was slightly high. However, the characteristics of discharge withstand was so excellent that the mechanical destruction does not occur at the impulse current of $8/20{\mu}s$ 10kA for 100 times.

  • PDF