• Title/Summary/Keyword: Diagonal ventilation circuit

Search Result 1, Processing Time 0.014 seconds

A Study on the Airflow Distribution in the Diagonal Ventilation Circuit for the Design of a High Level Radioactive Waste Repository (고준위 방사성 폐기물 처분장 설계를 위한 Diagonal 환기 회로 내 공기량 분배에 관한 연구)

  • Hwang, In-Phil;Choi, Heui-Joo;Roh, Jang-Hoon;Kim, Jin
    • Tunnel and Underground Space
    • /
    • v.22 no.3
    • /
    • pp.173-180
    • /
    • 2012
  • In this study, diagonal ventilation circuits that are advantageous in air flow direction control were studied. Based on the results of the study, it could be seen that air volumes in diagonal ventilation circuits could also be calculated using numerical formulas or programs if the air volumes and air flow directions to be infused into diagonal branches are determined in advance as with other serial/parallel circuits. To apply the results, design plans for high level radioactive waste repositories applied with diagonal ventilation circuits and parallel ventilation circuits. To compared the each design plans and obtain expected operation results, ventilation network simulations were conducted through the Ventsim program which is a ventilation networking program. Based on the results, in the case of diagonal repositories that was expected to cause great increases in resistance, fan pressure was 1570 pa, total flux was 84 $m^3/s$, fan efficiency was 76.4%, fan power consumption was 181.2 kW and annual fan operating costs were 178,710,838 and thus maximum around 8% differences were shown in pressure and flux values and a difference of around 1.5% was shown in terms of operating costs.