• Title/Summary/Keyword: Current interrupter

Search Result 87, Processing Time 0.017 seconds

Dynamic Characteristic of Permanent Magnetic Actuator (영구자석형 액추에이터의 동작 특성)

  • Seo, J.H.;Kim, H.K.;Joo, S.W.;Hahn, S.C.
    • Proceedings of the KIEE Conference
    • /
    • 2004.04a
    • /
    • pp.24-26
    • /
    • 2004
  • For past decade, medium voltage circuit breakers have used the spring-driven mechanical system for interrupting of electric power. However, these mechanisms have many disadvantages of high power consumption, mechanical control components and electrical switching ones for the coil current. Recently, the vacuum interrupter operated by permanent magnet actuator gives outlook on improved characteristic, higher reliability and cost price reduction as well as the feature of simple structure and few components. This paper deals with the dynamic characteristics of permanent magnet actuator used in the medium voltage distribution systems. Coupled finite element method is used to analysis the dynamic characteristics of permanent magnetic actuator and we compared with those of conventional ones.

  • PDF

Spatial and Temporal Behavior of Arc with Magnetic Field (자계가 인가된 아크의 공간적, 시간적 거동)

  • Choi, Won-Joon;Kang, Jin;Choi, Seung-Kil;Ko, Hwang-Cheol
    • Proceedings of the KIEE Conference
    • /
    • 1998.07e
    • /
    • pp.1809-1811
    • /
    • 1998
  • Axial magnetic field restrains arc diffusion that appear at cutting off fault current in vacuum interrupter(VI). In this study, spatial and temporal behavior simulation of arc is carried out for various axial magnetic field. Also the results of this simulation show that axial magnetic field controls and helps to extinguish arcs. This study can be applied to design and analysis of VI. Dymo theory that is not considered in this study will be considered latter.

  • PDF

Effect of arcing time on the interruption Performance of EHV class GCB (아크시간이 초고압 가스차단기의 차단성능에 미치는 영향)

  • Park, K.Y.;Shin, Y.J.;Song, K.D.;Chong, J.K.;Song, W.P.;Kwon, K.Y.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07a
    • /
    • pp.161-163
    • /
    • 1998
  • The interruption performance of EHV class gas circuit breakers critically depends on the flow conditions inside interrupter and the external circuit conditions. In case of puffer type gas circuit breakers the flow conditons are significantly influenced by arcing time. In this paper the calculated results of RRRV and pressure rise at current zero with varying arcing time are presented and the effect of arcing time on the thermal interruption performance of EHV class gas circuit breakers is analyzed.

  • PDF

Analysis of Dynamic characteristic and design of permanent magnetic actuator (영구자석형 차단기의 특성해석 및 설계)

  • Seo J. H.;Kim H. K.;Joo S. W.;Hahn S. C.
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.1040-1042
    • /
    • 2004
  • For past decade, medium voltage circuit breakers have used the spring-driven mechanical system for interrupting of electric power. However, these mechanisms have many disadvantages of high power consumption, mechanical control components and electrical switching ones for the coil current. Recently, the vacuum interrupter operated by permanent magnet actuator gives outlook on improved characteristic, higher reliability and cost price reduction as well as the feature of simple structure and few components. This paper deals with the dynamic characteristics of permanent magnet actuator used in the medium voltage distribution systems. Coupled finite element method is used to analysis the dynamic characteristics of permanent magnetic actuator and we compared with those of conventional ones

  • PDF

Fabrication and Tests of the 24 kV class Hybrid Superconducting Fault Current Limiter

  • Lee, B.W.;Sim, J.;Park, K.B.;Oh, I.S.;Yim, S.W.;Kim, H.R.;Hyun, O.B.
    • Progress in Superconductivity and Cryogenics
    • /
    • v.9 no.4
    • /
    • pp.32-36
    • /
    • 2007
  • We fabricated and tested a novel hybrid superconducting fault current limiter (SFCL) of three-phase $24kV_{rms}/630A_{rms}$ rating. In order to apply conventional resistive SFCLs into electric power systems, the urgent issues to be settled are as follows, such as initial installation price of SFCL, operation and maintenance cost due to ac loss of superconductor and the life of cryostat, and high voltage and high current problems. The ac loss and high cost of superconductor and cryostat system are main bottlenecks for real application. Furthermore in order to increase voltage and current ratings of SFCL, a lot of superconductor components should be connected in series and parallel which resulted in extreme high cost. In addition, the method to quench all components at the same instant needs very sophisticated skill and careful operation. Due to these problems, the practical applications of SFCL were pending. Therefore, in order to make practical SFCL, the price of SFCL should be lowered and should meet the demand of utilities. We designed novel hybrid SFCL which combines superconductor and conventional electric equipment including vacuum interrupter, power fuse and current limiting reactor. The main purpose of hybrid SFCL is to drastically reduce total usage of superconductor by adopting current commutation method by use of superconductor and high fast switch. Consequently, it was possible to get the satisfactory test results using this method, and further works for field tests are in the process.

An Analysis of Cold Gas Flow-Field for UHV Class Interrupters (초고압 가스차단부의 냉가스 유동해석)

  • Song, Gi-Dong;Park, Gyeong-Yeop;Song, Won-Pyo
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.49 no.6
    • /
    • pp.387-394
    • /
    • 2000
  • This paper presents a method of cold gas flow-field analysis within puffer type GCB(Gas Circuit Breaker). Using this method, the entire interruption process including opening operation of GCB can be simulated successfully. In particular, the distortion problem of the grid due to the movement of moving parts can be dealt with by the fixed grid technique. The gas parameters such as temperature, pressure, density, velocity through the entire interruption process can be calculated and visualized. It was confirmed that the time variation of pressure which was calculated from the application of the method to a model GCB agreed with the experimental one. Therefore it is possible to evaluate the small current interruption capability analytically and to design the interrupter which has excellent interruption capability using the proposed method. It is expected that the proposed method can reduce the time and cost for development of GCB very much. It also will be possible to develop the hot-gas flow-field analysis program by combining the cold-gas flow field program with the arc model and to evaluate the large current interruption capability.

  • PDF

Interrupting Characteristics of 25.8kV Gas Circuit Breaker Using Thermal-Expansion Principle (열팽창분사원리를 이용한 25,8kV급 가스차단기의 차단특성)

  • Chang, K.C.;Shin, Y.J.;Park, K.P.;Jeong, J.K.;Kim, J.K.;Kim, G.S.
    • Proceedings of the KIEE Conference
    • /
    • 1994.07b
    • /
    • pp.1603-1605
    • /
    • 1994
  • Recently, Gas Circuit Breakers are rapidly replacing Vacuum Circuit Breakers in the medium voltage switchgear. This is due to the improved performance of - GCB in interrupting capability, price, weight, size etc., while the countermeasure to suppress the switching surges of VCB has not been satisfactory. Intensive research works on the GCB have been conducted in the world widely since 1980. Nowadays it is well known that the thermal expansion type GCB can provide- better performance than puffer type in the distribution power system. KERI has conducted researches in the GCB rated at 25.8kV 25kA with Jinkwang Co. using the thermal expantion principle since 1993. In this paper, the calculated results of electric and magnetic fields for the model GCB are presented and analyzed. The effect of permanent magnet used to improve the interruption capabilty at the low current level is also investigated. The design parameters for the interrupter inspected through the short-circuit tests conducted at high power laboratory of KERI.

  • PDF