• 제목/요약/키워드: Compressor System

검색결과 1,076건 처리시간 0.03초

컴프레서 구동용 전동기 축계의 구조 안전성 평가 (STRUCTURAL SAFTY EVALUATION OF COMPRESSOR DRIVING MOTOR SHAFT SYSTEM)

  • 정건화;곽주호;김병주;이종문
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2007년도 춘계학술대회A
    • /
    • pp.1031-1036
    • /
    • 2007
  • Torsional vibration analysis is necessary at design stage to ensure the reliability of a system particularly when the driven machine is a reciprocating compressor. This paper contains the results of torsional vibration analysis and fatigue strength evaluation for 540 kW compressor driving motor. Torsional vibration analysis showed that the $2^{nd}$ torsional mode of the entire shaft system has the possibility of resonance with the $14^{th}$ order excitation of compressor and twin line frequency of motor at operating speed. Therefore, the analyses were required to ensure the structural reliability of the motor. The fatigue strength was evaluated for the shaft and inner fans using the results of forced vibration analysis. It is concluded that the motor has sufficient fatigue strength under normal operating condition.

  • PDF

멀티형 냉방시스템의 압축기 제어 (Compressor Control of a Multi-type AIr Conditioning System)

  • 한도영;권형진
    • 설비공학논문집
    • /
    • 제13권8호
    • /
    • pp.780-786
    • /
    • 2001
  • For the compressor speed control of a multi-type air conditioning system, a fuzzy control algorithm was developed. The sum of zone temperature errors and its derivative were used as input variables, and the compressor speed was selected as the output variable. To test the effectiveness of the control algorithm, one outdoor environmental chamber and four indoor environmental chambers were used. In the chambers the zone temperature step change test and the indoor unit change over test were performed. Test results showed that, for the control of compressor speed, the fuzzy control algorithm was more effective than the conventional proportional control algorithm for the energy conservation.

  • PDF

Subcooling Bypass Technology를 적용한 압축기 토출 냉매 온도 감소에 관한 연구 (A Study on the Decrease of Compressor Discharge Temperature Using Subcooling Bypass Technology)

  • 곽경민;배철호
    • 설비공학논문집
    • /
    • 제21권6호
    • /
    • pp.326-332
    • /
    • 2009
  • The purpose of the study is to decrease the refrigerant temperature at the outlet of the compressor under high thermal load conditions for air cooled vapor compression refrigeration system. The subcooling bypass line called subcooling bypass technology(SBT) is installed to the window type A/C system to investigate the performance test. The standard air calorimeter test method is applied to measure the refrigerant temperature at the outlet of the compressor, cooling capacity, power consumption, and system EER. The refrigerant temperature at the outlet of the compressor decreases as the bypass rate increases. When the bypass rate is 8.2%, the refrigerant temperature at the outlet of the compressor decreases $2.8^{\circ}C$ while the cooling capacity and EER are the same as the conventional A/C unit.

CO2 압축기의 운전조건과 오일토출의 상관분석에 관한 실험적 연구 (An Experimental Study on Correlation between Oil Discharge and Various Operating Conditions of a CO2 Compressor)

  • 이익수;강병하
    • 설비공학논문집
    • /
    • 제23권1호
    • /
    • pp.73-79
    • /
    • 2011
  • A portion of oil for lubrication of compressor flows together with refrigerant in the refrigeration system. If the oil discharge from a compressor is increased in the refrigeration system, not only pressure drop is increased in other components, such as evaporator and gas cooler, but also heat transfer coefficient in the heat exchangers is decreased. Oil discharge rate from a compressor may strongly depend on operating conditions of a compressor. In this study, one stage single rotary compressor is employed for measuring oil circulation ratio(OCR). Carbon dioxide and PAG oil are used as refrigerant and lubricant. Using a U-tube densimeter, mixture density is measured. Oil circulation ratio(OCR) can be estimated by measured mixture density. The results obtained indicate that the oil circulation ratio(OCR) is increased as the suction temperature or compressor operating frequency is increased. Oil circulation ratio(OCR) correlation of the compressor is also suggested.

일체형 로타리 압축기-베인 팽창기 (A Combined Rotary Compressor-vane Expander)

  • 김현진;노영재;김용희
    • 한국유체기계학회 논문집
    • /
    • 제18권3호
    • /
    • pp.12-19
    • /
    • 2015
  • As a means of improving cycle performance of a R410A air-conditioning system, a combined structure of compressor and expander was introduced. A vane rotary type expander was designed to share a common shaft with twin type rolling piston rotary compressor in a housing. Numerical simulation on the performance of the combined compressor and expander was carried out. At ARI condition, the volumetric and total efficiencies of the designed vane expander were 69.37% and 30.23%, respectively. With the application of this expander, the compressor input was reduced by 3.91%, and the cooling capacity was increased by 3.98%. As a result, COP of the air-conditioning system was improved by 8.2%. As the pressure difference between the condenser and the evaporator becomes large, COP improvement increases unless the mass flow rate in the expander exceeds that in the compressor.

전력변환장치를 이용한 상용차용 무시동 에어컨 압축기 시스템 (Commercial Vehicle Anti-Start Air Conditioner Compressor System Using a Power Conversion Unit)

  • 한근우;김성곤;이충훈;최명현;정영국;임영철
    • 조명전기설비학회논문지
    • /
    • 제29권6호
    • /
    • pp.96-108
    • /
    • 2015
  • his study deals with a power conversion unit of an anti-start air conditioner compressor system for the commercial vehicle. In case of converter, to reduce the switching losses and current stresses of the device, applies LLC resonant topology. Transformer leakage inductance in the full-bridge converter is used for making the resonance with the capacitor of the voltage-doubler. Through this method we can increase power and decrease volume of system. Both circuit analysis and design guideline are described. So in this paper, power conversion unit is designed. 2.5kW anti-start air conditioner compressor system was implemented, and system operation and stability was verified through experiment.

디지털 스크롤 압축기를 이용한 시스템 에어컨의 냉난방특성 (Cooling and Heating Characteristics of System A/C using the Digital Scroll Compressor)

  • 전용호;김대훈;권영철;이윤수;문제명;홍주태
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2003년도 춘계학술대회
    • /
    • pp.1536-1541
    • /
    • 2003
  • In order to investigate the cooling and heating characteristics of a variable-capacity system A/C using a digital scroll compressor, the cooling and heating capacities and EER are measured by the psychrometric calorimeter. The capacity of the system is controlled by the digital scroll compressor, which is operated by controling PWM valve and the loading vs. unloading time. When the system A/C is operated under the cooling and heating standard conditions, EER is nearly uniform but cooling capacity and heating capacity increase at minimum, rated and maximum modes. When the auxiliary heater is on, at the cold region, the system A/C produces the excellent heating capacity.

  • PDF

공기압축기 소비에너지 평가에 관한 연구 (A Study on the Evaluation of Energy Consumption of the Air Compressor)

  • 장지성
    • 드라이브 ㆍ 컨트롤
    • /
    • 제17권2호
    • /
    • pp.38-44
    • /
    • 2020
  • Various efforts have been initiated to reduce the energy consumption of the compressor as it is one of the approaches to saving a large portion of the fixed cost of the production site. Various results of reducing the energy consumption of the compressor have been reported, but to reduce the energy consumption of the compressors fundamentally, regular management of the compressor should ensure optimum operation. This requires periodic on-site visits by experts, but is often overlooked as a cost issue, resulting in the use of the compressor in low-efficiency conditions. Thus, it is necessary to develop a low-cost evaluation technology for compressor condition monitoring and efficiency analysis to ensure that the compressor is always driven at the optimum efficiency without imposing undue burden on the compressor user. In this study, a sensor was installed at the inlet, outlet, and power supply of the compressor, and a method for evaluating the energy consumption of the compressor using the minimum sensor was derived. The experimental results are presented to show the validity of the proposed method. It was confirmed that the energy consumption of the compressor can be easily as well as efficiently evaluated by using the method developed in this study.

FTA 기법을 이용한 Compresson고장 진단

  • 배용환
    • 한국정밀공학회:학술대회논문집
    • /
    • 한국정밀공학회 1993년도 춘계학술대회 논문집
    • /
    • pp.305-309
    • /
    • 1993
  • The application of fault tree technique to the analysis of compressor failure is considered. The techniques involve the decomposition of the system into a logic diagram or fault tree in whichcertain basic or primary events lead to a specified top event which signifiss the total failure of the system. The fault trees are used to obtain miniumal cut sets from whichthe modes of system failure and, hence the reliability for the top event can be calculated. The method of constructing fault trees and the subsequent estimation of reliability of the system is illustrated through a compressor failure. FTA is roved to be efficient to investigate the compressor fault train.

왕복동식 압축기의 스너버내 맥동압 분포 (Pulsatile Pressure Distribution on the Snubber of Reciprocating Compressor)

  • 이경환;;정한식;정효민
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2007년도 동계학술발표대회 논문집
    • /
    • pp.606-611
    • /
    • 2007
  • Pulsation is an inherent phenomenon in reciprocating compressors. It interacts with piping to cause vibrations and performance problems. Indiscriminately connecting to a compressor can be dangerous and cost money in the form of broken equipment and piping, poor performance, inaccurate metering, unwanted vibration, and sometimes noise. Piping connected to a compressor can materially affect the performance and response. To minimize these detrimental effects, reciprocating compressor system should be equipped by pulsation suppression system. This study discusses pressure pulsation phenomena occurred in a reciprocating compressor system. An experiment applied air compressor unit, as pulsating pressure generator, has been done. The compressor was connected sequentially to a snubber model and pressure tank. Sensor probes were placed on the inlet and outlet pipes of snubber. Compressor was driven by a motor controlled by a frequency regulator. The experiment was conducted by adjusting the regulator at 40Hz. General information about an internal gas flow can be achieved by numerical analysis approach. Information of the velocity, pressure and turbulence kinetic energy distribution are presented in this paper. Based on this result, the design improvement might be done.

  • PDF