• Title/Summary/Keyword: Coating material-sprayed circular column

Search Result 1, Processing Time 0.016 seconds

Study of the Standard Testing Specifications for a Non-loading Performance Evaluation of Coating Material-sprayed Circular Steel Structures (뿜칠 피복 원형 철골구조의 비재하 내화성능 평가용 시험체 제안을 위한 연구)

  • Ok, Chi-Yeol;Kim, Jae-Jun
    • Fire Science and Engineering
    • /
    • v.30 no.3
    • /
    • pp.7-15
    • /
    • 2016
  • The cross-sectional shape factor is used worldwide to evaluate the scientific performance of fire-resistant structures. In South Korea, however, a system for applying a cross-sectional shape factor has not been arranged and circular or rectangular steel pipes are commonly used for large-scale steel frame buildings. On the other hand, coating material-spray steel beams and pillars that have received the certification of a fire-resistant structure from recognized organizations are mostly limited to a H-beam. A H-beam is granted a wide range of certifications without size limitations from a non-loading performance test with test standards based on the relevant provisions. Other types of steel pipe are to be certified for fireresistance according to shape. In this study, a cross-sectional shape factor was used to propose standard testing specifications for the application of coating material-sprayed circular and rectangular steel pipes, eventually to set the scope of certification for reasonable fire-resistant structures.