• Title/Summary/Keyword: Carbonization patten

Search Result 1, Processing Time 0.016 seconds

Carbonization Patten and Operation Characteristics of a 1Φ 2 W MCCB Damaged by PCITS (PCITS에 의해 소손된 1Φ 2 W MCCB의 탄화 패턴 및 작동 특성)

  • Lee, Jae-Hyuk;Choi, Chung-Seog
    • Fire Science and Engineering
    • /
    • v.28 no.5
    • /
    • pp.8-13
    • /
    • 2014
  • The purpose of this study is to analyze the damage pattern when overcurrent is applied to a thermal magnetic type molded case circuit breaker (MCCB) using a Primary Current Injection Test System (PCITS). When an overcurrent of 150 A was applied to the PCITS for 5 seconds with the trip bar of an MCCB being damaged, it was found that the surface of the temperature control device (bimetallic strip) positioned at the right was significantly carbonized. When an overcurrent of 300 A was applied to the PCITS for 5 s under the same conditions, the entire temperature control device was deteriorated, becoming flattened and in close contact with the MCCB. When an overcurrent of 450 A was applied to the PCITS for 5 s, the coil of the temperature control device was melted and disconnected. In addition, it was observed that the contacts, the enclosure and upper cover were deformed and there was a trace of carbonization on them. When approximately 3 s had elapsed after an overcurrent of 600 A was applied, white smoke occurred inside the MCCB and a flame was radiated out, after which the overcurrent supply stopped with "phutt" (whomp) sound. It was observed that when the same type of MCCB is damaged by a general flame, the surfaces of its handle, terminal, arc divider (extinguisher) and temperature control device were carbonized uniformly. In addition, it was found that the trip bar of the operating mechanism was melted down and the metal operation pin was moved while being tripped.