Absolute Evaluation Method to Obtain Ratio Error and Phase Displacement of Current Transformers (전류변성기의 비오차와 위상오차의 절대 평가 기술)

  • Kim, Yoon-Hyoung;Jung, Jae-Kap;Han, Sang-Gil;Koo, Kyung-Wan;Han, Sang-Ok
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.57 no.2
    • /
    • pp.153-159
    • /
    • 2008
  • We have developed an absolute evaluation method to obtain the ratio error and phase displacement of a current transformer (CT) without any precise standard CT by measuring four parameters in a CT equivalent circuit. The excitation admittance in the CT equivalent circuit can be obtained by employing standard resistors with negligible reactive component. The secondary leakage impedance in the CT equivalent circuit can be measured using a universal impedance bridge. The method was applied to CTs under test with the wide current ratios in the range of 5 A / 5 A - 5,000 A / 5 A and 5 A / 1 A - 5,000 A / 1 A. The ratio error and phase displacement of the CT under test obtained in this study are consistent with those measured at the national institute in Canada using the same CT under test within an expanded uncertainty (k = 2) in the overall current ratios.

Extension of Absolute Evaluation Technique for Ratio Error and Phase Displacement of Core Type Current Transformers: Ip =$5\;kA{\sim}40\;kA$ (철심형 전류변성기의 비오차 및 위상오차 절대 평가 기술의 확장 : 1차 전류 = $5\;kA{\sim}40\;kA$)

  • Kim, Yoon-Hyoung;Han, Sang-Gil;Jung, Jae-Kap;Han, Sang-Ok
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.57 no.4
    • /
    • pp.431-436
    • /
    • 2008
  • We have extended an absolute evaluation method to obtain the ratio error and phase displacement of a current transformer (CT) up to primary current of 40,000 A by measuring four parameters of equivalent circuit in CT. The method was applied to CTs under test with the current ratios in the range of 5,000 A / 5 A - 40,000 A / 5 A. The ratio error and phase displacement of the CTs under test obtained in this study are consistent with those measured at the national institutes in Canada and Germany using the same CTs under test within an expanded uncertainty (k = 2) in the overall current ratios.

Development of 132 kV Standard Potential Transformer and Stability Test (132 kV 초정밀 전압변성기(PT) 개발 및 안정도 평가)

  • Kwon, Sung-Won;Lee, Sang-Hwa;Jung, Jae-Kap;Kim, Mun-Seog;Kim, Jae-Young;Lee, Sung-Ha
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.1387_1388
    • /
    • 2009
  • High accurate and stable 132 kV potential transformers (PTs) including 66 kV & 22 kV PT with stability of less than 0.0033 % for 13 month and with ratio error within $\pm$ 0.024 % at full rated voltage have been developed. The PTs are useful as the reference PT of the PT comparator system in the voltage range of 11 kV to 132 kV PT.