Ground Fault Current Variation of 22.9kV Multi Neutral Grounded Distribution System with CD Type Superconducting Cable (22.9kV 중성점 다중접지계통에 CD형 초전도케이블을 적용한 경우의 지락전류변화)

  • Lee, Jong-Bae;Hwang, Si-Dole;Sohn, Song-Ho;Lee, Geun-Joon
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.6
    • /
    • pp.993-999
    • /
    • 2007
  • This paper discusses the effects of CD type superconducting cable operation in 22.9kV multi neutral grounded distribution system during L-G fault and counterplans to power system protection. In case of using the 3-phase CD-type superconducting cable, the inductance of superconducting cable system would be decreased due to the current of shield part of superconducting cable, which is opposite direction and nearly equal value with respect to main superconductor. However, when the shield circuit system is operated in shorted state, shield current decreases faulted ground current and give effects to power system protection scheme. This study examines the phenomena of single line to ground fault case in above mentioned system using the EMTDC program and discusses the right operation method of superconducting shield.

Ground fault current variation of 22.9kV CD type superconducting cable system (22.9kV 중성점 다중접지계통에 CD형 초전도케이블을 적용한 경우의 지락전류변화)

  • Lee, Geun-Joon;Lee, Sang-Han;Son, Song-Ho;Hwang, Si-Dol
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.46-47
    • /
    • 2006
  • 본 논문은 CD형 초전도 케이블을 22.9kV 다중접지 배전계통에 적용한 경우 불평형 지락 고장이 초전도 케이블에 미치는 영향을 검토하고 이로 인한 중성선 전류의 변화 및 계통보호를 위한 대책을 논한다. 3상 CD형 초전도 케이블을 사용하는 경우 귀로선은 전향선과 전류가 반대이면서 거의 동일한 전류가 흐르므로 회로의 인덕턴스를 크게 줄일 수 있지만 이를 위해 회로를 단락하여 운전하는 경우 지락고장시 영상회로가 별도로 존재하지 않으면 지락전류를 저감시키는 결과를 초래하게 되어 계통보호에 영향을 주게 된다. 본 논문은 EMTDC 프로그램을 활용하여 이 현상을 XLPE 케이블 계통과 비교, 모의하는 한편, 정상적인 보호계전기 동작이 가능토록 하는 대책에 대해 논한다.