• Title/Summary/Keyword: Baffle Spacing

Search Result 7, Processing Time 0.023 seconds

Effect of baffle parameters on heat transfer in shell-and-tube heat exchangers (원통다관형 열교환기에서 배플인자가 열전달에 미치는 영향)

  • Lee, Sang-Cheon;Jo, Yeong-U;Nam, Sang-Cheol
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.21 no.1
    • /
    • pp.185-194
    • /
    • 1997
  • An experimental study has been performed on the effect of baffle parameters on shell -side heat transfer in a conventional shell-and-tube heat exchanger. The baffle spacing distance and the number of baffle were varied to investigate the behavior of unequal baffle spacing correction factor which is appeared in the Bell Delaware method for prediction of the shell-side heat transfer coefficient. It was obvious that heat duties obtained from the experiment significantly deviated from those calculated by the conventional Bell-Delaware method. A new correlation of the unequal baffle spacing correction factor was developed. It was shown that the new correlation improves the accuracy of the Bell-Delaware method considerably. This result may induce the use of the Bell-Delaware method in developing a computer software for design of shell-and-tube heat exchangers.

An Experimental Study of Shell and Tube Heat Exchanger Performance with Baffle Spacing (배플수에 따른 원통다관형 열교환기 성능에 관한 실험 적 연구)

  • Lee, Yuk-Hyeong;Kim, Sun-Yeong;Park, Myeong-Gwan
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.25 no.12
    • /
    • pp.1748-1755
    • /
    • 2001
  • The shell and tube heat exchangers were introduced to apply to a big capacity condenser and a high pressure feed water heater for power plant in the beginning of 1990s. Design and manufacturing technology fur shell and tube heat exchangers have been developed until now. But it is very difficult to calculate the expected performance characteristics of the shell and tube heat exchanger, because there are many design parameters to be considered according to internal structure and the shell side heat transfer mechanism complicately related to the design parameters. Design parameters to be considered in the design stage of shell and tube heat exchanger are shell and tube side fluids, flow rate, inlet and outlet temperature, physical properties, type of heat exchanger, outer diameter, thickness, length of tube, tube arrangement, tube pitch, permissive pressure loss on both sides, type of baffle plate, baffle cutting ratio. The propose of study is an analysis TEMA(Tubular Exchanger Manufacturers Association) E shell and tube heat exchanger performance with changing a number of baffles(3, 5, 7, 9, 11) and tubes(16, 20) and determined optimal baffle spacing.

A study of number of baffle on shell and tube heat exchanger (원통다관형 열교환기의 가로막 개수에 관한 연구)

  • 김순영;이육형;박명관
    • Proceedings of the Korean Society of Precision Engineering Conference
    • /
    • 2000.05a
    • /
    • pp.635-638
    • /
    • 2000
  • The propose of study analyze a TEMA(Tubular Exchanger Manufacturers Association) E shell and tube heat exchanger performance with 3, 5, 7, 9, 11 baffles and 16, 20 tubes. In this investigate measured a variation of the heat exchanger cooling capacity change within each number of baffle and tube number and determined optimal number of baffle. designs for industry applications are optimized using the analysis of test results.

  • PDF

Flow and Heat Transfer Characteristics in Ice Making Heat Exchanger Applied to Ice-Storage System (빙축열 시스템의 제빙용 열교환기내에서 유동 및 열전달 특성)

  • Back, Young-Ryoul;Lee, Jae-Heon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.6 no.2
    • /
    • pp.110-119
    • /
    • 1994
  • Three dimensional characteristics of fluid flow and heat transfer have been studied numerically around the latent heat storage vessel which was applied to the practical ice-storage system. The result obtained indicates that the value of frictional coefficient decreases with decrease of baffle width. For the baffle spacing. $S/H_D=9.375$, baffle height. $H/H_D=0.5$ and various pressure drop, average Nusselt numbers in heat transfer surface are much dependent on the width of side baffle and middle baffle. that is. Nu_m decreases with decrease of the width of middle baffle when the width of side baffle is 4.375, where as the optimum condition of side baffle for $Nu_m$ exists in the range of 3.5< $B_1/H_D$ <4.375 at the width of middle baffle, $B_2/H_D=6.875$.

  • PDF

A Numerical Study on the Heat Transfer Performance of Single-Tube Annular Baffle System (단관 환형배플 시스템의 전열성능에 대한 수치해석)

  • Hong, Jeong-Ah;Jun, Yong-Du;Lee, Kum-Bae
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.24 no.8
    • /
    • pp.621-626
    • /
    • 2012
  • A new baffle configuration, an annular baffles, are considered in the present study as an alternative to reduce the excessive pressure drop associated with the conventional segmental ones in typical operating conditions. The heat transfer and pressure drops are numerically simulated for a single tube shell-and-tube model and compared against the conventional-baffle cases. Baffle blockage ratio and number of baffles are considered as the major variables for the present study specifying a fixed baffle spacing. It is found that the heat transfer increases 1.4~2.2 times without significant pressure loss compared to the bare tube cases and the goodness factor increases 1.35 times compared to the conventional-baffle model.

Dynamic Suppression Effects of Liquid Container to the Baffle Number and Hole Diameter (배플개수 및 내경변화에 따른 액체 저장탱크의 동억제 효과)

  • 조진래;김민정;이상영;허진욱
    • Journal of the Computational Structural Engineering Institute of Korea
    • /
    • v.15 no.1
    • /
    • pp.147-154
    • /
    • 2002
  • The dynamic load caused by sloshing of internal fluid severely affects the structural and control stabilities of cylindrical liquid containers accelerating vertically. If the sloshing frequency of fluid is near the frequency of control system or the tank structure, large dynamic force and moment act on launching vehicles. For the suppression of such dynamic effects, generally flexible ring-type baffles are employed. In this paper, we perform the numerical analysis to evaluate the dynamic suppression effects of baffle. The parametric analysis is performed with respect to the baffle inner-hole diameter and two different baffle spacing types : equal spacing with respect to the tank and one with respect to the fluid height. The ALE (arbitrary Lagrangin-Eulerian) numerical method is adopted for the accurate and effective simulation of the hydrodynamic interaction between fluid and elastic structure.

Thermo-hydraulic Effect of Tubular Heat Exchanger Fitted with Perforated Baffle Plate with Rectangular Shutter-type Deflector

  • Md Atiqur Rahman
    • Korean Chemical Engineering Research
    • /
    • v.62 no.2
    • /
    • pp.191-199
    • /
    • 2024
  • A study was conducted on a tubular heat exchanger to improve its heat transfer rate by using a novel baffle plate design with discontinuous swirling patterns. The design consisted of perforated baffle plates with rectangular air deflectors positioned at varying angles. The tubes in the heat exchanger were arranged in a consistent alignment with the airflow direction and exposed to a uniform heat flux on their surfaces. Each baffle plate included sixteen deflectors inclined at the same angle and arranged in a clockwise pattern. This arrangement induced a swirling motion of the air inside a circular duct where the heated tubes were located, leading to increased turbulence and improved heat transfer on the tube surfaces. The spacing between the baffle plates was adjusted at different pitch ratios, and the Reynolds number was controlled within a range of 16,000 to 29,000. The effects of pitch ratios and inclination angles on the heat exchanger's performance were analyzed. The results indicated that using a baffle plate with rectangular deflectors inclined at 30° and a pitch ratio of 1.2 resulted in an average increase of 1.29 in the thermal enhancement factor.