• 제목/요약/키워드: Back/forward sweep method

검색결과 5건 처리시간 0.019초

대칭성분을 이용한 3상 배전계통 조류계산 기법 (A New Distribution System Power Flow Method Using Symmetrical Components)

  • 최정환;정성일;박제영;김광호;김재언;박종근
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제51권1호
    • /
    • pp.15-22
    • /
    • 2002
  • This paper proposes a new power flow method for distribution system analysis by modifying the conventional back/forward sweep method using symmetrical components. Since the proposed method backward and forward sweeps with the variables expressed by symmetrical components, this method reduces computation time for matrix calculations; therefore, it is able to reduce the computational burden for real-time distribution network analysis. The proposed method was also developed to effectively analyze the unbalanced distribution system installing AVR(Auto Voltage Regulator), shunt capacitors. The proposed algorithm was compared with the conventional Back/forward Sweep method by applying both methods to three phase unbalanced distribution system of IEEE 123-bus model, and the test results showed that the proposed method would outperformed the conventional method in real-time distribution system analysis.

이중 후퇴각을 갖는 복합재 날개의 플러터 특성 (Flutter Characteristics of Double-Swept Composite Wings)

  • 구교남
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2000년도 춘계학술대회논문집
    • /
    • pp.1228-1233
    • /
    • 2000
  • A new planform of a wing having two sweep angles is proposed to enhance the aeroelastic stability of a swept-forward wing. The double-swept wing has two sweep angles with inboard wing swept-back and outboard wing swept-forward. Aeroelastic analysis is performed with the finite element method to model wing structure and the doublet point method to predict aerodynamic loads. The sweep angle of the inboard wing is varied in this analysis while the outboard wing is swept forward to a pre-selected amount. The results show that the aeroelastic stability can be drastically enhanced by adjusting the sweep angle of the inboard wing. The effect of the fiber orientation in the double-swept composite wing is studied and the proper ply angle is identified to maximize critical speed.

  • PDF

Symmetrical Components를 이용한 배전계통 3상 조류 계산 알고리즘 개발 (Development of 3 phase Power Flow calculation algorithm in distribution Power Systems using Symmetrical Component)

  • 최정환;장성일;김광호;박종근;김재언
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 A
    • /
    • pp.147-149
    • /
    • 2000
  • This paper describes a power flow method for distribution systems, applying the method of symmetrical component to back/forward sweep method. The proposed algorithm is effective for unbalanced radial distribution system, with process of distributed resource(PQ & PV node), AVR(Auto Voltage Regulator), shunt capacitor. This proposed method compared conventional back/forward sweep method with the using three phase unbalanced distribution systems with 34 nodes.

  • PDF

대칭성분을 이용한 배전계통 조류 계산 알고리즘 개발 (Development of Power Flow calculation algorithm in distribution Power Systems using Symmetrical Components)

  • 최정환;정종찬;김광호;박종근;김재언
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 A
    • /
    • pp.401-403
    • /
    • 2001
  • This paper describes a power flow method for distribution systems, applying the method of symmetrical component to back/forward sweep method. The proposed algorithm is effective for unbalanced radial distribution system, with process of AVR(Auto Voltage Regulator), shunt capacitor. The proposed method was compared with the conventional Back/forward sweep method by using three phase unbalanced distribution systems of 123 nodes.

  • PDF

Optimal Allocation Method of Hybrid Active Power Filters in Active Distribution Networks Based on Differential Evolution Algorithm

  • Chen, Yougen;Chen, Weiwei;Yang, Renli;Li, Zhiyong
    • Journal of Power Electronics
    • /
    • 제19권5호
    • /
    • pp.1289-1302
    • /
    • 2019
  • In this paper, an optimal allocation method of a hybrid active power filter in an active distribution network is designed based on the differential evolution algorithm to resolve the harmonic generation problem when a distributed generation system is connected to the grid. A distributed generation system model in the calculation of power flow is established. An improved back/forward sweep algorithm and a decoupling algorithm are proposed for fundamental power flow and harmonic power flow. On this basis, a multi-objective optimization allocation model of the location and capacity of a hybrid filter in an active distribution network is built, and an optimal allocation scheme of the hybrid active power filter based on the differential evolution algorithm is proposed. To verify the effect of the harmonic suppression of the designed scheme, simulation analysis in an IEEE-33 nodes model and an experimental analysis on a test platform of a microgrid are adopted.