• 제목/요약/키워드: Autocascade system

검색결과 4건 처리시간 0.019초

A Study on Autocascade Refrigeration System Using Carbon Dioxide and R134a Mixture

  • Park, Soo-Nam;Kim, Min-Soo
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제9권1호
    • /
    • pp.39-49
    • /
    • 2001
  • Investigation of the performance of an autocascade refrigeration system using the refrigerant mixtures of R744 (carbon dioxide) and R134a (1,1,1,2-tetrafluoroethane) has been carried out by simulation and experiment. Cycle simulation using a constant UA model in heat exchangers has been performed for R744/134a mixtures of the compositions ranging from 10/90 to 30/70 by weight. Variations of mass flow rate of refrigerant, compressor work, refrigeration capacity and COP with respect to mass fraction of R744/134a mixture were presented. Performance test has been executed in the autocascade refrigeration system by varying secondary fluid temperatures at evaporator and condenser inlets. Experimental results match quite well with those obtained from the simulation.

  • PDF

이산화탄소와 R134a의 혼합냉매를 이용한 오토캐스케이드 냉동시스템의 성능 (Performance of autocascade refrigeration system using carbon dioxide and R134a)

  • 박수남;김민수
    • 설비공학논문집
    • /
    • 제11권6호
    • /
    • pp.880-890
    • /
    • 1999
  • The purpose of this study is to investigate the performance of an autocascade refrigeration system using the refrigerant miktures of R744 (carbon dioxide) and R134a (1,1,1,2-tetrafluoroethane) as working fluids by simulation and experiment. Cycle simulation using a constant UA model in heat exchangers has been performed for R744/134a mixtures of the compositions in the range of from 10/90 to 30/70 by weight percentage. Variations of mass flow rate of refrigerant, compressor work, refrigeration capacity and COP with respect to mass fraction of R744/134a mixture were presented. Performance test has been executed in an autocascade refrigeration system by varying secondary fluid temperatures at evaporator and condenser inlets. Experimental results show similar trend with those from the simulation.

  • PDF

오토캐스케이드 방식을 적용한 극저온 칠러 시스템의 실험적 연구 (An Experimental Study of Cryochiller System Using Autocascade)

  • 차동안;권오경;윤재호;김대열
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2007년도 춘계학술대회B
    • /
    • pp.1980-1985
    • /
    • 2007
  • The purpose of this study is to investigate the performance of an autocascade refrigeration system using the refrigerant mixtures of R-134a(64${\sim}$72wt%), R-23(20${\sim}$25wt%) and R-14(8${\sim}$12wt%) as working fluids by experiment. The experimental apparatus consisted of a autocascade system with a compressor, condenser, evaporator, gas-liquid separator and cascade condenser, etc. Two main causes to this failure were considered as follows. First, the pressure ratio in the compressor was extremely increased at the beginning of the experiment. Second, the outlet temperature in compressor was higher than its limited temperature. For a stable operation of the compressor, a portion of the mixed refrigerant was by-passed at the inlet of the heat exchanger and transferred directly to the suction of the compressor in the modified system. The experimental parameters were changed weight of R-134a(1800g, 2800g), R-23(700, 800, 900g) and R-14(300, 400, 500g). The results showed that the best performance in case of R-134a of 2800g, R-23 of 900g and R-14 of 500g.

  • PDF

이산화탄소를 냉매로 사용하는 오토캐스케이드 냉동기의 성능에 관한 해석 및 실험 (Analysis and Experiment on The Performance of an Autocascade Refrigeration System Using Carbon Dioxide As a Refrigerant)

  • 김성구;김민수
    • 설비공학논문집
    • /
    • 제13권5호
    • /
    • pp.411-421
    • /
    • 2001
  • The purpose of this study is to investigate the performance of an autocascade refrigeration system by simulation and experiment using refrigerant mixtures of R744/134a and R744/290 as working fluid. Variations of mass flow rate of refrigerant, compressor work refrigeration capacity and COP with respect to mass fraction of R744/134a and R744/290 mixture were presented under different operating conditions. Performance test has been executed by ASRAE standard. Experimental results show as the composition of R744 in the refrigerant mixture increases, heating and coling capacity are enhanced, but COP trends to decrease. Experimental results are compared with those from the simulation.

  • PDF