• 제목/요약/키워드: Arrester Soundness

검색결과 8건 처리시간 0.025초

철도용 피뢰기의 열화진전에 관한 연구 (A Study on the Deterioration Progress of Railway Arresters)

  • 길경석;한주섭;한문섭
    • 한국철도학회논문집
    • /
    • 제7권4호
    • /
    • pp.307-311
    • /
    • 2004
  • Arresters are the best protective device on electrical power systems against transient overvoltages generated by lightning and/or switching operation. Nonetheless, arresters are deteriorated by absorption of moisture in the environments of its use, repetition in the protective operation to overvoltages, and some defects at manufacturing. It is therefore important to estimate the electrical characteristic changes of ZnO blocks. In this paper, an accelerated ageing test by a standard lightning impulse current was carried out to extract parameters needed for arrester diagnosis, and leakage current components were measured. Total energy applied to the ZnO blocks at each time is about 1,050[J] in 8/20[${\mu}\textrm{s}$] impulse current. From the experimental results, we proposed electrical parameters and leakage current level to diagnose arrester soundness.

피뢰기 진단장치의 설계 및 제작 (Design and Fabrication of a Lightning Arrester Analyzer)

  • 길경석;한주섭;서황동
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제53권11호
    • /
    • pp.572-576
    • /
    • 2004
  • Various devices for diagnosing arrester soundness are suggested, and most of them simply measure magnitude of leakage current. However, such kind of devices do not provide detailed information needed for the diagnosis. In this study, we designed and fabricated a new arrester analyzer by means of measuring the magnitude, the phase vs. wave height and the harmonics of total leakage currents. The analyzer is composed of a current detector, an optical linker, and a main device operated by a microprocessor. The main device is connected with leakage current detector optically not to be influenced by electromagnetic interference. The analyzer developed measures only total leakage currents, but analyzes most parameters needed for the arrester diagnostics.

급전선로에 설치되어 있는 피뢰기의 누설전류 측정과 관리방안 (Leakage Current Measurement and Management of Arresters Installed in Feeder Lines)

  • 한주섭;서황동;길경석;한문섭;장동욱
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2005년도 춘계학술대회 논문집
    • /
    • pp.819-824
    • /
    • 2005
  • This paper describes the measurement result of leakage current flowing arresters connected in feeder lines to propose an optimal management method. Twenty seven arresters set in seven areas were analyzed on a regular basis for 4 months. The results showed that the RMS and the peak value of the total leakage currents for soundness arresters were a range of $200uA{\sim}00uA$. respectively. During the period of measurement, the magnitude of the leakage current didn't show conspicious changes and there were impossible places to analyze arrester's status due to including high THD rate in a feeder line, From the study, leakage current measurement has to be performed at a condition without running an electric train in the line, and the allowable RMS value of soundness arrester is bellow 600uA.

  • PDF

Measurement Method of the Resistive Leakage Current for Lightning Arrester Diagnosis

  • Kil, Gyung-Suk;Han, Ju-Seop;Song, Jae-Yong;Seo, Hwang-Dong
    • Transactions on Electrical and Electronic Materials
    • /
    • 제6권2호
    • /
    • pp.63-66
    • /
    • 2005
  • Several ways for monitoring the soundness of ZnO lightning arresters have been suggested, and all of which are based on the measurement of leakage current since it is well known that the resistive leakage current is a main indicator of arrester deterioration. In this paper, we proposed an algorithm to measure the resistive leakage current, which is quite different from the conventional method that eliminates capacitive current from the total leakage current. The proposed algorithm is based on that the magnitudes of the resistive leakage current are equal at the same applied voltage levels. To confirm the reliability of the algorithm, we fabricated a leakage current detector and designed an analysis program. Experimental results showed that the method does not need a complex circuitry and is useful to analyze the resistive leakage current.

철도용 피뢰기의 열화진전에 관한 연구 (A Study on the Deterioration Progress of Railway Arresters)

  • 길경석;한주섭;한문섭
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2004년도 춘계학술대회 논문집
    • /
    • pp.1393-1395
    • /
    • 2004
  • Arresters are the best protective device on electrical power systems against transient overvoltages generated by lightning and/or switching operation. Nonetheless, arresters will be deteriorated due to absorption of moisture in the environments of its use, repetition in the protective operation to overvoltages, and some defects at manufacturing. It is therefore important to estimate the electrical characteristic changes of ZnO blocks. In this paper, an accelerated deterioration test by a standard lightning impulse current was carried out to extract parameters needed for diagnosing arrester deterioration, and leakage current components were measured. Total energy applied to the ZnO blocks at each time is 1,050[J] in 8/20[${\mu}s$] impulse current. From the experimental results, we proposed electrical parameters and leakage current level to diagnose arrester soundness.

  • PDF

ZRO 피뢰기 소자의 뇌충격전류에 의한 전기적 특성 변화 비교 (Comparison on electrical characteristic changes of ZnO Arrester Blocks by Lightning Impulse Current)

  • 한주섭;박영호;길경석;김찬영
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 추계학술대회 논문집 학회본부 C
    • /
    • pp.1108-1110
    • /
    • 1999
  • This paper describes the comparison results on electrical characteristic changes of ZnO blocks by lightning impulse current. The five types of ZnO blocks used in lightning arrester for distribution lines have been estimated repeatedly till about 400 times by a standard lightning impulse current of 3kA, $8/20{\mu}s$, and changes of the performance characteristics of them to operation times were examined and compared quantitatively every fifty times discharge. It is expected that the result will be useful to diagnose the soundness of ZnO blocks or lightning arresters, and to develope deterioration diagnosis device for them.

  • PDF

피뢰기 진단을 위한 저항분 누설전류의 새로운 측정기법 (New Measurement Technique of the Resistive Leakage Current for Arrester Diagnosis)

  • 길경석;한주섭;송재용;박대원;서황동
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 춘계학술대회 논문집 방전 플라즈마 유기절연재료 초전도 자성체연구회
    • /
    • pp.73-75
    • /
    • 2004
  • Resistive leakage current following arresters is an important indicator of ageing, but total leakage current and its harmonic analysis are widely used in diagnosing arrester soundness because of difficulties in measuring resistive leakage current. In this paper, we proposed a new method for measuring resistive leakage current, which is quite different from the conventional methods such as a self-cancel method and a synchronous rectification method. The proposed method is based on that the magnitudes of resistive leakage currents are equal at the same voltage level. To confirm the possibility of the proposed method. we fabricated a leakage current measurement device and designed an analysis program that can analyze resistive leakage current. Comparing with other methods. this technique does not need a complex circuitry and is very simple to complete.

  • PDF

누설전류의 파고분포 분석에 의한 새로운 피뢰기 진단기술 및 장치 (New Diagnostic Technique and Device for Lightning Arresters by Analyzing the Wave Height Distribution of Leakage Currents)

  • 길경석;한주섭;송재영;조한구;한문섭
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제52권12호
    • /
    • pp.562-567
    • /
    • 2003
  • Lightning arresters are deteriorated by repetition of protective operation against overvoltages or impulse currents in environments of its use. If a deteriorated arrester is left in power lines, it can lead to an accident such as a line to ground fault even in a normal system. Therefore, it is necessary to eliminate the deteriorated arrester in advance by checking the soundness of arresters on a regular basis, and to ensure the reliability of power systems by preventing accidents. Various deterioration diagnostic techniques and devices are suggested, and most of which measure leakage current components as an indicator of arrester ageing. However, the techniques based on the magnitude of leakage current measure simply RMS or peak value of leakage current components and do not provide detailed information needed in the diagnosis. In this study, we found that the wave height distributions of the total leakage currents are remarkably changed or a new wave height are produced with the progress of arrester deterioration. To propose a new technique for the diagnosis, we designed a leakage current detection unit and an analysis program which can measure leakage current magnitudes and analyze wave height distributions. From the experimental results, we confirmed that the proposed technique by analyzing the wave height distribution can simply diagnose the mode of defects such as a partial damage and an existence of punctures in arresters as well as deterioration of arresters.