• 제목/요약/키워드: Arrester Diagnostics

검색결과 5건 처리시간 0.019초

피뢰기 진단장치의 설계 및 제작 (Design and Fabrication of a Lightning Arrester Analyzer)

  • 길경석;한주섭;서황동
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제53권11호
    • /
    • pp.572-576
    • /
    • 2004
  • Various devices for diagnosing arrester soundness are suggested, and most of them simply measure magnitude of leakage current. However, such kind of devices do not provide detailed information needed for the diagnosis. In this study, we designed and fabricated a new arrester analyzer by means of measuring the magnitude, the phase vs. wave height and the harmonics of total leakage currents. The analyzer is composed of a current detector, an optical linker, and a main device operated by a microprocessor. The main device is connected with leakage current detector optically not to be influenced by electromagnetic interference. The analyzer developed measures only total leakage currents, but analyzes most parameters needed for the arrester diagnostics.

누설전류측정에 의한 피뢰기 열화진단에 있어 전원고조파의 영향 (Influence of Harmonics in Power System Voltage on Arrester Deterioration Diagnostics by Leakage Current Measurement)

  • 길경석;한주섭;주문노
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제52권1호
    • /
    • pp.42-46
    • /
    • 2003
  • Arresters are deteriorated by overvoltages or impulse currents, and the resistive leakage current of arresters increases as the deterioration of the arrester progresses, showing an increase in the 3$^{rd}$ harmonic component of the leakage current. In this reason, arrester diagnostic techniques based on the 3$^{rd}$ harmonic leakage current as a reference parameter of deterioration are widely used. The technique, however, includes an error due to the harmonics of power system voltage. Therefore, the influence of the harmonics on arrester diagnostics should be considered. In this paper, we designed a PSpice ZnO arrester model to simulate the influence of the voltage harmonics described above. A pure sinusoidal voltage and its the 3r harmonic voltage were applied to the model, and the leakage current components were analyzed. From the simulation results, it is confirmed that the peak value of resistive leakage current depends not only on the phase of the 3$^{rd}$ harmonic voltage but also on the magnitude of it. Consequently, the errors caused 1)y the harmonic voltage could be minimized by correcting the magnitude of leakage current upon analyzing the harmonics.cs.

피뢰기 열화진단에 있어 전원 고조파의 영향과 보정에 관한 연구 (A Study on the Influence of Harmonics in Power System Voltage on Arrester Diagnostics and its Compensation)

  • 김일권;송재용;한주섭;길경석;류길수;조한구
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제54권11호
    • /
    • pp.493-497
    • /
    • 2005
  • This paper dealt with the influence of harmonic voltages on arrester diagnostics and its compensation method by using a designed Pspice arrester model. A pure sinusoidal voltage and its 3$^{rd}$ harmonic voltage were applied to the model, and the leakage current components were analyzed. The simulation results have shown that the peak value of resistive leakage current depends not only on the phase of the 3$^{rd}$ harmonic voltage but also on the magnitude of it. In this paper, an approximated 5$^{th}$ order polynomial formula by the Least-Square-Technique was derived, and correction factors which compensate the error caused by the 3$^{rd}$ harmonic voltage were calculated.

피뢰기 열화진단을 위한 저항분 누설전류의 측정장치 (Measurement Device of Resistive Leakage Current for Arrester Deterioration Diagnosis)

  • 길경석;한주섭;김정배
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제52권10호
    • /
    • pp.469-475
    • /
    • 2003
  • Resistive leakage current flowing ZnO blocks increases with its ages, which is an important indicator of arrester deterioration. However, a complicated circuitry is essential to measure the resistive leakage current included in the total leakage current, and the difficult handling of the measurement makes few applications to the fields. In this paper, we propose a resistive leakage current measurement device which is composed of a current detection circuit and an analysis program operated on a microprocessor. The device samples the input leakage current waveform digitally, and discriminate the zero-cross and the peak point of the waveform to analyze the current amplitude vs. phase. The capacitive leakage current is then eliminated from the total leakage current by using an algorithm to extract the resistive leakage current only. Also, the device can be operated automatically and manually to analyze the resistive leakage current even when the leakage current waveform is distorted due to various types of arrester deterioration. To estimate the performance of the device, we carried out a test on ZnO blocks and lightning arresters. From the results, it is confirmed that the device could analyze most parameters needed for the arrester diagnostics such as total leakage current. resistive leakage current, and the $3^rd$ harmonic leakage current.

철도용 피뢰기 진단기술 및 장치 (Diagnostic Technique and Device for Railway Arresters)

  • 길경석;한주섭;장동욱
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2004년도 춘계학술대회 논문집
    • /
    • pp.1422-1424
    • /
    • 2004
  • Various deterioration diagnostic techniques and devices are suggested, and most of which measure leakage current components as an indicator of arrester ageing. However, the techniques based on the magnitude of leakage current measure simply RMS or peak value of leakage current components and do not provide detailed information needed in the diagnosis. In this study, we found that the phase vs. wave height of total leakage current is changed or a new wave height is produced with arrester ageing. To complete the new technique, we designed an arrester diagnostic device which is composed of a current detection circuit, an optical transmission circuit, and an analysis program. After measurement of the total leakage current, magnitudes, phase vs. wave height, and harmonics of the leakage current components are analyzed by the microprocessor based device. From the experimental results, we confirmed that the device can measure most parameters needed for the arrester diagnostics and analyze an initial deterioration state.

  • PDF