• 제목/요약/키워드: Arrester

검색결과 303건 처리시간 0.028초

배전용 ZnO 피뢰기 소자의 열적/전기적 파라미터 분석에 관한 연구 (A study on analysis of thermal and electrical parameters of the ZnO arrester block)

  • 이복희;이수봉;이승주;전병욱;김동성
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2007년도 춘계학술대회 논문집
    • /
    • pp.353-356
    • /
    • 2007
  • This paper presents the thermal and electrical characteristics of ZnO arrester blocks under the AC voltages. The leakage currents of ZnO arrester blocks were measured as a function of time. The temperature distributions of ZnO arrester blocks were observed by the forward looking infrared camera The degradation and thermal runaway of ZnO arrester blocks were closely related with the temperature limit of ZnO arrester blocks which decided heat generation and dissipation As a result, the degradation and thermal runaway of ZnO arrester blocks depend on the temperature and leakage current of ZnO arrester blocks.

  • PDF

ZnO 피뢰기 소자의 열적.전기적 특성 분석 (Analysis of Thermal and Electrical Characteristics of ZnO Arrester Blocks)

  • 이수봉;이복희
    • 조명전기설비학회논문지
    • /
    • 제21권10호
    • /
    • pp.82-88
    • /
    • 2007
  • 이 논문에는 교류전압에서 ZnO 피뢰기 소자의 열적 전기적 특성을 기술하였다. ZnO 피뢰기 소자의 누설전류는 시간의 변화에 따라 측정하였다. ZnO 피뢰기 소자의 온도분포를 열화상카메라에 의해 관측하였다. ZnO 피뢰기 소자의 열화 및 열폭주 현상은 열발생과 열방산을 결정짓는 ZnO 피뢰기 소자의 온도한계와 밀접한 관계가 있다. ZnO 피뢰기 소자의 저항은 ZnO 피뢰기 소자의 온도와 누설전류에 의해 민감하게 변화한다. 결론적으로 ZnO 피뢰기 소자의 열화 및 열폭주 현상은 ZnO 피뢰기 소자의 온도와 소자를 통해 흐르는 누설전류에 상당히 의존적인 것으로 나타났다.

대용량 컨버터의 Arrester 설계 (Arrester Design of High power Converter)

  • 김찬기;이원교;신진철;류흥우
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2004년도 전력전자학술대회 논문집(1)
    • /
    • pp.461-464
    • /
    • 2004
  • 본 논문은 대용량 컨버터에 이용되는 Arrester에 대한 설계기법을 보여주고 있다. 본 논문에는 Arrester의 설계방법과 일반적인 AC계통에서 사용하는 Arrester와 다른 열방산 특성을 다루었다.

  • PDF

18kV 배전용 피뢰기의 구조에 따른 온도특성 (Temperature Characteristics with Structure of 18kV Lightning Arresters for Distribution System)

  • 조한구;윤한수;이운용;김석수;최인혁
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 하계학술대회 논문집 Vol.5 No.2
    • /
    • pp.1125-1128
    • /
    • 2004
  • This paper presents the temperature characteristics with structure of 18 kV lightning arresters for distribution. Three types of polymer arresters were fabricated and ceramic type arrester was also ready to investigate. Below $100^{\circ}C$, three types of polymer arresters exhibited almost the same leakage current value, but above $100^{\circ}C$, polymer arrester that arrester module was injected into polymer housing with grease exhibited the highest leakage current and the arrester with the lowest leakage current was the arrester that silicon rubber was directly injected to arrester module. The rising of leakage current of polymer arrester with grease was because of existing grease between FRP winding and silicon housing, and reducing the insulation characteristics of the grease. All polymer arresters exhibited the same temperature characteristics but ceramic typr arrester was slower than polymer arrester in heat emission despite lowest leakage current. It was thought that the air layer between ZnO varistor blocks and ceramic housing prevented the heat emission. However, in spite of the difference of the structure, the variation of the surface temperature of all arresters exhibited the same result.

  • PDF

폴리머 피뢰기의 고장전류에 대한 방압 설계기술에 관한 연구 (Study on the relief design for the fault current of polymer arrester)

  • 김인성;박효열;조한구
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 D
    • /
    • pp.1717-1719
    • /
    • 1999
  • The chief advantage of polymer arrester. from design of pressure relief, anti-contamination, electrical failure was reduced by outdoor polymer housing. In the first for development of pressure relief design for polymer arrester, fault current and surge were studied through experiments of electrical. Designed the FRP inner tube and unit modules for pressure relief housing. Tested the performance of unit modules for pressure relief of polymer arrester, and the result was successful. The pressure relief of polymer arrester depend on design pattern of diamond shape and ellipse. Study on the pressure relief of FRP inner tube for outdoor polymer arrester. Designed and manufactured FRP inner tube of polymer arrester. Tested the fault current of polymer arrester per 10 kA, 10 cycle.

  • PDF

외부환경 변화에 따른 배전용 피뢰기의 전기적 특성 (Electrical properties of 18kV ZnO surge arrester according to the variation of surrounding conditions)

  • 이복희;이승주;이수봉;김동성;신희경
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2008년도 춘계학술대회 논문집
    • /
    • pp.289-292
    • /
    • 2008
  • This paper describes the electrical characteristics of the ZnO surge arrester according to the variation of surrounding conditions. To investigate the characteristics of degraded ZnO surge arrester, 8/20 [${\mu$s], 2.5 [kA] impulse currents were applied to the ZnO surge arrester to be test. To present the effect of the surrounding con야tions, the leakage currents of ZnO surge arrester were measured to the surrounding temperature and wet conditions. As a result, the increase of ambient temperature causes the increase of resistive leakage current of ZnO surge arrester. Also, in the wet test, the outside leakage current through the ZnO surge arrester housing is much larger than the intrinsic leakage current.

  • PDF

폴리머 피뢰기의 모듈 설계 및 성능에 관한 연구 (A Study on Module Design and Performance of Polymer Arrester)

  • 조한구;천종욱;강영길
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2003년도 춘계학술대회 논문집 유기절연재료 방전 플라즈마연구회
    • /
    • pp.108-111
    • /
    • 2003
  • The main objective of this paper is to module design and pressure relief test a new type of polymer gapless surge arrester for power distribution line. Metal oxide surge arrester for most electric power system applications, power distribution line and electric train are now being used extensively to protect overvoltage due to lightning. Surge arresters with porcelain housing must not have explosive breakage of the housing to minimize damage to other equipment when subjected to internal high short circuit current. When breakdown of gapless elements in a surge arrester occurs due to flashover, fault short current flows through the arrester and internal pressure of the arrester rises. The pressure rise can usually be limited by fitting a pressure relief diaphragm and transferring the arc from the inside to the outside of the housing. However, there is possibility of porcelain fragmentation caused by the thermal shock, pressure rise, etc. Non-fragmenting of the housing is the most desired way to prevent damage to other equipment. The pressure change which is occurred by flashover become discharge energy. This discharge energy raises to damage arrester housing and arrester housing is dispersed as small fragment. Therefore, the pressure relief design is requested to obstruct housing dispersion.

  • PDF

Gas tube형 Arrester의 Passive IMD 연구 (The Research for Passive IMD of Gas Tube Arrester)

  • 한진욱;김태홍;유종준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 학술회의 논문집 정보 및 제어부문 A
    • /
    • pp.63-66
    • /
    • 2003
  • Resident mobile communication system technology has been developed. But, surged high voltages in antenna generally have damaged mobile communication. To solve this problem, we use arrester in Rx-Tx line system. That is, the arrester is to protect devices in system against considerable over-voltages or lighting strike. Currently, system protection using of arrester has been arrived in content level but these days, the fact of PIMD(Passive Intermodulation Distortion) which is RF passive components' nonlinear characteristic has appeared. This paper describes PIMD' causes occurred in arrester-estimated from Gas tube capsule, plating, temperature, humidity by experiment.

  • PDF

산화아연 피뢰기 소자의 열적 특성 향상을 위한 연구 (A study on the improvement of the thermal properties of ZnO arrester blocks)

  • 김동성;이수봉;이승주;김동규;양순만;이복희
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2009년도 추계학술대회 논문집
    • /
    • pp.335-338
    • /
    • 2009
  • In this study, in order to investigate the thermal and electrical properties of ZnO arrester block against 60[Hz] AC voltage, the changes in leakage current were measured. The temperature distribution appearing on the ZnO arrester blocks was observed using a forward looking infrared camera. In particular, the correlation between the thermal and electrical properties of a ZnO arrester block was analyzed experimentally. From this analysis, the thermal phenomena resulting from the heat generation and dissipation of the ZnO arrester block were interpreted. The degradation and thermal runaway phenomena of ZnO arrester block are closely related to the temperature limit of the ZnO arrester block. The installation of an additional metal electrode has resulted in the decrease of the leakage current due to the heat dissipation.

  • PDF

Gas Tube형 Arrester의 Passive IMD 연구 (The Research for Passive IMD of Gas Tube Arrester)

  • 한진욱;고홍남;곽진교;신동주
    • 대한전기학회논문지:시스템및제어부문D
    • /
    • 제53권11호
    • /
    • pp.776-779
    • /
    • 2004
  • Resident mobile communication system technology has been developed. But, surged high voltages in antenna generally have damaged mobile communication. To solve this problem, we use an arrester in Rx-Tx line system. That is, the arrester is introduced to protect devices in system against considerable over-voltages or lighting strike. Currently, system protection using an arrester has arrived in a content level but these days, the PIMD(Passive Intermodulation Distortion) with RF passive components' nonlinear characteristic has appeared. This paper describes PIMD' causes occurred in arrester-estimated from Gas tube capsule. plating, temperature, and humidity by experiment.