• Title/Summary/Keyword: Aisle partition system

Search Result 2, Processing Time 0.015 seconds

Evaluation of Cooling Energy Saving through Applying Aisle Partition System on a Data Center Server Room (파티션 시스템 적용을 통한 기존 데이터센터 서버실의 냉방 에너지 절감 성능평가)

  • Park, Jong-Soo
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.17 no.7
    • /
    • pp.726-733
    • /
    • 2016
  • In this study, a computer simulation of the three types of air distribution systems, open type system, aisle partition system and aisle containment system, to evaluate the applicability of the aisle partition system on a data center server room. The variables of the simulation were the height and location of the partition fixed on the top server rack. The energy efficiency of the air distribution systems were confirmed to be excellent in the order of the aisle containment system, aisle partition system, and open type system. In the cold aisle partition system, the height of the partition that can be effective in saving cooling energy by obstructing sufficient air recirculation was found to be more than 0.9m. In the hot aisle partition system, the height of the partition was found to be more than 0.8m.

Evaluation of Aisle Partition System's Thermal Performance in Large Data Centers for Superior Cooling Efficiency (데이터센터의 공조효율 향상을 위한 공조파티션시스템 성능평가에 관한 연구)

  • Cho, Jin-Kyun;Jeong, Cha-Su;Kim, Byung-Seon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.22 no.4
    • /
    • pp.205-212
    • /
    • 2010
  • In a typical data center, large numbers of IT sever racks are arranged multiple rows. IT environments, in which extensive electronic hardware is air-cooled, cooling system inefficiencies result when heated exhaust air from equipment prematurely mixes with chilled coolant air before it is used for cooling. Mixing of chilled air before its use with heated exhaust air results in significant cooling inefficiencies in many systems. Over temperatures may not only harm expensive electronic equipment but also interrupt critical and revenue generating services. Cool shield is a cost effective aisle partition system to contain the air in cold aisles and hot aisles of an IT server room. This paper focuses on the use of performance metrics for analyzing aisle partition system in data centers.