• Title/Summary/Keyword: Absorption chiller

Search Result 148, Processing Time 0.032 seconds

Optimal Control Algorithm for the Dual Source Chiller Air Conditioning System (복합 열원 공조시스템의 최적 제어 알고리즘)

  • Han, Do-Young;Kim, Jin
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.9
    • /
    • pp.881-888
    • /
    • 2004
  • Control algorithms for a dual source chiller air conditioning system were developed. These are control algorithms for the supply air temperature control, the supply header chilled water temperature control, the chiller chilled water temperature control, and the cooling tower water temperature control. These algorithms were analyzed by using a dynamic simulation program. Simulation results showed the energy savings and the satisfactory controls of an absorption and centrifugal chiller air conditioning system. Therefore, control algorithms developed for this study may effectively be used for the improved controls of the dual source chiller air conditioning system.

Dynamic Models and Simulation of the Absorption Air Conditioning System (흡수식 공조 시스템의 동적 모델과 시뮬레이션)

  • 한도영;이승기
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.11
    • /
    • pp.994-1003
    • /
    • 2000
  • Control algorithms for the absorption air conditioning system may be developed by suing dynamic models of the system. The simplified effective dynamic models, which can predict the dynamic behaviors of the system, may help the development of effective control algorithms for the system. In this study, a dynamic simulation program for the absorption air conditioning system was developed. Dynamic models for an absorption chiller, a cooling tower, an air handling unit, a boiler, a three way valve, a controller, and a duct were developed and programed. Control algorithms for the absorption chiller, the cooling tower, and the air handling unit were selected, and analyzed to show the effectiveness of dynamic models. From the simulation results, it may be concluded that this simulation program may be effectively used for the development of optimal control algorithms of the absorption air conditioning system.

  • PDF

Performance Characteristics on the Mixed Flow Type Absorption Chiller-Heater (혼합흐름 사이클용 흡수식 냉온수기의 성능특성)

  • Yoon, J.I.;Shin, G.B.;Park, S.H.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.8 no.3
    • /
    • pp.351-360
    • /
    • 1996
  • This study focuses on the development and evaluation of the high efficiency absorption chiller-heater, which can be applied to a direct gas fired, double effect system with 40RT (508,000kJ) cooling capacity. The performance of the absorption chiller-heater is investigated through cycle simulation and experiment to obtain the system characteristics with the inlet tenperature of cooling, chilled water, and gas input flow rate. The efficiency of the different cycles has been studied and the simulation and experiment results show that higher coefficient of performance could be obtained for mixed flow cycle. The five percent difference was obtained from the comparison between experimental and cycle simulation results. As a result of this study, the optimum designs were determined based on the operating conditions and the coefficient of performance.

  • PDF

Heat and mass transfer of helical absorber on household absorption chiller/heater (가정용 흡수식 냉난방기의 나선형 흡수기 열물질전달)

  • 권오경;윤정인
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.5
    • /
    • pp.570-578
    • /
    • 1999
  • An experimental study has been performed on heat and mass transfer in a falling film absorber with a strong lithium bromide solution in small-sized household absorption chiller/heater. Components were concentrically arranged in a cylindrical form. from the center, low temperature generator, absorber and evaporator. This arrangement of helical-typed heat exchangers allows to make the machine much more compact than conventional one. Experimental measurements were conducted with a helical absorber and the obtained data were compared with data in the literatures. The comparison revealed that the helical absorber tube provides a similar performance to existing tube bundle absorber in heat and mass transfer. As a result, the heat and mass transfer characteristics of helical type absorber showed the possibility of the reduction in size and weight of small] capacity absorption chiller/heater.

  • PDF

A experimental study of water vapor absorption characteristics using four components solution for gas fired absorption chiller (가스냉난방기용 4성분계 흡수용액의 수증기 흡수특성에 관한 실험적 연구)

  • Lee Yong-Won;Oh Young-Sam;Park Dal-Ryung;Baek Young-Soon
    • Journal of the Korean Institute of Gas
    • /
    • v.2 no.4
    • /
    • pp.47-52
    • /
    • 1998
  • Water vapor absorption performance of four components solution ($LiBr+LiNO_3+LiC1+H_2O$) which could be substituted for commonly used $LiBr/H_2O$ solution in water cooled abosorption chiller is tested using a vertical tube absorber. Inlet solution concentration, inlet solution temperature, solution flow rate and inlet temperature of cooling water is varied as experimental parameters. The results of the experiment of water vapor absorption performance show that four components solution should have $2\%$ higher concentration for equal absorption capacity of $LiBr/H_2O$. But considering that four components solution have higher solubility than LiBr solution about $3\%$ high oncentration, four components solution ($LiBr+LiNO_3+LiC1+H_2O$) have more absorption capacity than LiBr solution in actual absorption chiller and can be applied to a small or air cooled absorption chiller.

  • PDF

Optimization of Heat Transfer Area Distribution for a Hot Water Driven Absorption Chiller (중온수 흡수식 냉동기의 열전달 면적 최적화)

  • 정시영;조광운;이상수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.5
    • /
    • pp.431-438
    • /
    • 2000
  • The major irreversibilities in absorption chillers are associated with the transfer of heat into and out from the machine and irreversible process inside the machine. By modeling only external irreversibilities(endo-reversible), a model was formulated to predict the ideal performance of a single-effect absorption chiller. Its actual performance including both external and internal irreversibilities was calculated with a in-house simulation program. The optimization of heat transfer area distribution was performed for both endo-reversible cycle and actual cycle. The equation of endo-reversible modeling was found to give about 2times higher cooling capacity than the simulation program. At optimal distribution, it was found that heat transfer area of the evaporator was about 30% of total area, that of the generator was 20%, and the rest 50% was for the absorber and condenser. The system COP for endo-reversible cycle was slightly higher than that for actual cycle. In the case of LiBr-water single-effect absorption chiller, the maximum cooling capacity was obtained near the condition that LMTD is same at all heat exchangers.

  • PDF

The Influences of LiBr Solution Recirculation in Absorber on the Absorption Chiller Performance (흡수기 용액 재순환이 흡수식 냉동기 성능에 미치는 영향)

  • Jeong, Jong-Su;Jin, Seong-Min;Park, Chan-U;Choe, Seung-Hak;Jeong, Bong-Cheol
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.26 no.5
    • /
    • pp.733-741
    • /
    • 2002
  • If a part of the poor solution from the absorber outlet is recirculated to the absorber inlet, the solution temperature at the solution spray pump can be reduced, and the solution flow rate in the absorber is increased. We have performed the experiments on the influences of the absorption chiller performance according to the ratio of the recirculation, defined as the ratio of the recirculation flow rate to the total solution flow rate at the absorber outlet. As increasing the ratio of the recirculation, the absorption capacity of the solution can be deteriorated. On the other hand, due to the increasing flow rate, the heat transfer rate can be enhanced. As a result, the performance of the absorber and the cooling capacity of the absorption chiller have nothing to do with the recirculation ratio, and the lifetime of the spray pump will be maintained.

Dynamic Analysis of an Ammonia-Water Absorption Chiller (암모니아-물 흡수식 냉각기의 동적 해석)

  • Kim Byong Joo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.10
    • /
    • pp.990-998
    • /
    • 2004
  • Dynamic behavior of an ammonia-water absorption system was investigated numerically. Thermal-hydraulic model for a single-effect 3 RT chiller was developed by applying transient conservation equations of total mass, $NH_3$ mass, energy and momentum to each component. Transient variations of system properties and transport variables were analysed during start-up operation. Numerical analyses were performed to quantify the effects of bulk concentration and charging ratio on the system performance in terms of cooling capacity, coefficient of performance, and time constant of system. For an absorption chiller considered in the present study, optimum charging ratio and bulk concentration were to found to exist, which resulted in the maximum cooling capacity and COP. The time constant increased as the charging ratio increased, but decreased with the increase of bulk concentration.

The Influences of the Refrigerant Adulteration by an Absorbent on the Cooling Capacity and COP of the Absorption Chiller (흡수식 냉동기에서 흡수액이 증발기로 혼입시 냉각용량과 성능계수에 미치는 영향)

  • Park, Chan-Woo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.9
    • /
    • pp.753-760
    • /
    • 2006
  • The purpose of the present work is to investigate the influence of the refrigerant adulteration by LiBr solution on the cooling capacity and COP for three different types of abso게tion chillers: a single-effect type, a series-flow double-effect type and a parallel-flow with double-effect type. A simulation program has been prepared for the cyclic analysis of absorption chillers. With some assumptions, the calculations have been performed by solving the mass balance equation, energy balance equation and the state equation simultaneously. The range of the LiBr concentration of refrigerant was 0% to 20% in the present study. For the single-effect absorption chiller, the maximum decrease in the cooling capacity was 10% at the 20% of LiBr concentration. For the double-effect chiller, the capacity was decreased by 11.1% for the parallel-flow type and the series-flow type. Also, the COP was reduced by 3.0% in single-effect, 2.8% in series-flow type (SR=0.4) and 2.3% in parallel-flow type.