• 제목/요약/키워드: AEGL

검색결과 12건 처리시간 0.016초

Evacuation Safety Evaluation of High School according to Hydrogen Fluoride Leakage

  • Boohyun Baek;Sanghun Han;Hasung Kong
    • International Journal of Internet, Broadcasting and Communication
    • /
    • 제16권2호
    • /
    • pp.255-266
    • /
    • 2024
  • The purpose is to evaluate evacuation safety by simulating the toxic effects of hydrogen fluoride leaks in areas surrounding national industrial complexes and to suggest alternatives for areas that do not satisfy evacuation safety. For human casualties caused by hydrogen fluoride leakage accidents, Available Safe Egress Time (ASET) is calculated by the toxic effects quantified with the Areal Locations of Hazardous Atmospheres (ALOHA), an off-site consequence assessment program. The Required Safe Egress Time (RSET) is calculated through Pathfinder, an evacuation simulation program. Evacuation safety is assessed by comparing ASET and RSET. The ALOHA program was used to evaluate the time to reach AEGL-2 concentration in 12 scenarios. The Pathfinder program was used to assess the total evacuation time of the high school among specific fire-fighting objects. Of the 12 accident scenarios, ASET was larger than RSET in the worst-case scenarios 1 and 9. For the remaining 10 accident scenarios, the ASET is smaller than the RSET, so we found that evacuation safety is not guaranteed, and countermeasures are required. Since evacuation safety is not satisfactory, we proposed to set up an evacuation area equipped with positive pressure equipment and air respirators inside specific fire-fighting objects such as the high school.

산화프로필렌의 누출영향평가에 따른 안전거리 산정 (The Selter Selection Plan due to Formaldehyde Leakage)

  • 오승주;한상훈;공하성
    • 대한안전경영과학회지
    • /
    • 제26권2호
    • /
    • pp.11-22
    • /
    • 2024
  • This study aims to present safety distances by the damage impact assessment of the leakage of propylene oxide. As a result of the experiment, the pressure 1psi range was 52m to 169m, the radiant heat 18kW/m2 range was 63m to 163m, the AEGL-2 range was analyzed as 224m to 414m, and the fire ball diameter was analyzed to be 45m to 121m. Additionally, the extent of damages was proportional to the amount of propylene oxide stored or handled. The safe distance for a 10% lethality due to overpressure and radiant heat was calculated to be 134m, and the safe distance for a 0% lethality was 169m. Toxicity was measured at 134m with a lethality 0%. Therefore, the safety distance due to leakage of propylene oxide is calculated to be between 134m and 169m.