• Title/Summary/Keyword: AC Interference

Search Result 89, Processing Time 0.034 seconds

The Effects of AC Corrosion on Underground Gas Pipeline Running Parallel with High Power Cables (전력케이블과 가스배관의 병행구간에 대한 교류부식 영향)

  • 배정효;김대경;김기준
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.49 no.10
    • /
    • pp.577-582
    • /
    • 2000
  • This paper analyze the interference problems, especially Ac corrosion when the gas pipeline is buried with power cable in the same submarine tunnel. This paper present the results of the study about interference mechanism(inductive coupling, conductive coupling, resistive coupling), AC corrosion, limitation of safety voltage, modeling of power cables, gas pipeline and grounding systems, analysis of induction voltage and optimal arrangement of power cables.

  • PDF

A Case Study on the AC Corrosion Effects for Bridges of Metallic Structure (철제구조 교량의 전식영향 연구)

  • Ha, Tae-Hyun;Lee, Hyun-Goo;Bae, Jeong-Hyo;Kim, Dae-Kyeong
    • Proceedings of the KIEE Conference
    • /
    • 2001.07a
    • /
    • pp.356-358
    • /
    • 2001
  • In general, when power lines, D/L and T/L are running parallel with bridge of metallic structure or crossing each other, AC corrosion is occur due to AC interference. This paper presents the results of AC interference mechanism, decision criteria of AC interference, and AC corrosion effects by analysis of AC induction voltage on pier and abut of bridge.

  • PDF

A Study on the Existing Induced Voltage Mitigation Method on Gas Pipelines using Steel Plate (보호철판을 이용한 가스배관 유도전압대책에 관한 연구)

  • Ha, Tae-Hyun;Lee, Hyun-Goo;Bae, Jeong-Hyo;Kim, Dae-Kyeong;Lee, Sung-Jin
    • Proceedings of the KIEE Conference
    • /
    • 2001.11b
    • /
    • pp.354-356
    • /
    • 2001
  • The demand of the power and gas energy have been rapidly increasing with the industralization, therefore, the area where buried pipelines run parallel with the adjacent power lines and cross them increases in Seoul as well as other cities. These situation cause AC interference from the power lines. However, there aren't any standards to preserve the pipelines from AC interference in Korea. We just use other country's criteria directly. Other developed countries have used the various AC interference mitigation methods such as lumped grounding. cancellation wires and gradient control wires etc.. This paper introduces the steel plate method which is using for AC interference mitigation method in Korea and investigates the effects of mitigation methods through case study by computer simulation.

  • PDF

Performance Evaluation of Interference Alignment Technique in Wireless LAN Environment (무선랜 환경에서 간섭정렬 기술의 성능 평가)

  • Yoon, Seokhyun;Shin, Won-Yong
    • The Journal of Korean Institute of Communications and Information Sciences
    • /
    • v.41 no.11
    • /
    • pp.1639-1644
    • /
    • 2016
  • In this paper, we consider the performance improvement that can be obtained with interference alignment (IA) technique applied to 802.11ac based multi-BSS WiFi service. To this end, we developed a system simulator consisting of a link-level PHY simulator, based on 802.11ac specification, and multi-BSS proportional-fair scheduler. Specifically, assuming perfect channel side information and synchronization of signals from multiple APs, we used a SLNR based interference alignment algorithm proposed in [13] and compared its performance with that of multiuser beamforming based time-sharing system. The performance was evaluated in terms of average throughput per BSS and 5% worst user throughput. The results show that 70 to 100% throughput gain can be obtained in this ideal scenario.

The Study on the AC Interference of High Power Cable on Underground Gas Pipeline (전력케이블과 가스배관의 병행구간에 대한 교류부식 영향 검토 연구)

  • Bae, J.H.;Kim, D.K.;Ha, T.H.;Lee, H.G.;Kwak, B.M.;Lim, C.J.
    • Proceedings of the KIEE Conference
    • /
    • 2000.07a
    • /
    • pp.470-473
    • /
    • 2000
  • Because of the continuous growth of energy consumption, and also the tendency to site power lines and pipelines along the same routes, the close proximity of high voltage structures and metallic pipelines has become more and more frequent. Moreover, normal steady state and fault currents become higher as electric networks increase in size and power. Therefore, there has been and still is a growing concern (safety of people marking contact with pipeline, risk of damage to the pipeline coating, the metal and equipment connected to pipeline. especially cathodic protection system) about possible hazards resulting from the influence of high voltage power system on metallic structures(gas pipeline, oil pipeline and water pipeline etc.). Therefore, we analyze the interference problems when the gas pipeline is buried with power cable in the same submarine tunnel. This paper present the results of the study about interference mechanism, AC corrosion, limitation of safety voltage and analysis of indiction voltage.

  • PDF

EMI Characteristics and filter design of AC Drives for Home Appliances (가전기기용 교류 전동기 구동 시스템의 EMI 특성 및 필터 설계)

  • 정세교;신휘범
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.9 no.1
    • /
    • pp.81-87
    • /
    • 2004
  • This paper describes a design method of electromagnetic interference (EMI) filter for pulse-width modulation (PWM) inverter-fed AC drives used for home appliances such as washing machine and air conditioner. The generating and coupling mechanisms of the conducted EMI for AC drives are first investigated. The design procedure of the EMI filter based on the EMI separation principle is then presented. Experiments we carried out for the PWM inverter-fed induction motor drive system and it is shown that the results satisfy the EN55014 EMI regulation.

Performance of Direct-Conversion Receiver with AC-Coupling in DC-Offset interference environment (DC-Offset 간섭환경에서 AC-Coupling을 갖는 직접변환 수신기의 성능)

  • 성봉훈;송윤정;김영완;김내수;서종수
    • Proceedings of the Korean Society of Broadcast Engineers Conference
    • /
    • 2002.11a
    • /
    • pp.9-14
    • /
    • 2002
  • Direct-conversion receiver(DCR) architecture has superior advantages in size, cost, and power over superheterodyne receiver architectures. However, the use of direct-conversion receiver architecture has been limited due to the direct-current offset noise. The ac coupling, which is used to overcome the direct-current offset noise, causes an inter-symbol interference(ISI), whose effects can be effectively mitigated using an equalizer. In this paper, the performance of a direct-conversion receiver with ac coupling in the presence of direct-current offset is analyzed via computer simulation. The simulation result shows that by using decision feedback equalizer with LMS(Least Mean Square) algorithm, signal-to-noise ratio loss of the direct-conversion receiver compared to the idea receiver can be reduced to less than 1㏈ for corner frequencies as large as 10% of the symbol rate.

  • PDF

A Study on The Effects of AC Corrosion on Underground Gas Pipeline Running Parallel with High Power Cables (Case II) (편력케이블과 가스배관의 병행구간에 대한 교류부식 영향 검토 연구(II))

  • Bae, Jeong-Hyo;Ha, Tae-Hyeon;Lee, Hyeon-Gu;Kim, Dae-Gyeong
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.51 no.2
    • /
    • pp.74-79
    • /
    • 2002
  • We have been analyzed the interference problems already in steady state, especially AC corrosion when the gas pipeline is burred with power cable in the same submarine tunnel. In the next stage, we analyze the induced voltage in a fault condition of 154[kV] underground T/L. This paper presents the results of them which are limitation of safety voltage. meodeling of power cables, gas pipeline and grounding systems, analysis of induced voltage in a fault condition, and protection of Power line system.

Improved Switching Frequency in Delta Modulated Inverter for UPS Applications

  • Sodaban, C.;Tipsuwanporn, V.;Thepsatorn, P.;Piyarat, W.;Witheephanich, K.
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 2004.08a
    • /
    • pp.986-989
    • /
    • 2004
  • The concept and results of a simple constant switching frequency delta modulation scheme suitable for DC-AC power conversion in uninterruptable power supply (UPS) applications are presented. Unlike the traditional delta modulation scheme, the scheme has a well defined harmonic spectrum, resulting in a simple filter design and reduced radio interference.

  • PDF

EMC/LVD Compatibility Evaluation of ITER AC/DC Converter Subrack by EN 61000 and IEC 61010 (ITER AC/DC Converter 서브랙의 EN 61000 및 IEC 61010에 의한 EMC/LVD 시험평가)

  • Shin, Hyun-Kook;Oh, Jong-Seok;Song, In-Ho;Suh, Jae-Hak;Choi, Jung-Wan
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.26 no.3
    • /
    • pp.222-226
    • /
    • 2021
  • To comply with CE marking requirements, the electromagnetic compatibility (EMC) and low-voltage directive (LVD) tests are conducted on the sub-racks of International Thermonuclear Experimental Reactor (ITER) AC/DC converters and bypass switches. The EMC tests consist of a series of tests, including the electromagnetic interference test, the electromagnetic field immunity test, and the rapid transient burst immunity test. In the LVD test, the electric shock protection test, the xcessive temperature limit and heat resistance of equipment tests, and the fire spread prevention test are performed. This work presents and reviews the European Directive for EMC/LVD and introduces the methods of EMC and LVD tests for the sub-racks of AC/DC converters and bypass switches. It also evaluates the test method and results to meet the European Directive requirements for CE marking. The sub-racks of ITER AC/DC converters and bypass switches successfully pass the EMC and LVD tests.