• 제목/요약/키워드: 5ESS-2000 통신장비실

검색결과 1건 처리시간 0.015초

5ESS-2000 통신장비실의 열환경특성과에너지성능 개선방안에 관한 연구 (A Study on the Characteristics of Thermal Environment and Improvement of Energy Performance in 5ESS-2000 Telecommunication Equipment Room)

  • 이승복;조춘식
    • KIEAE Journal
    • /
    • 제4권4호
    • /
    • pp.19-26
    • /
    • 2004
  • The purpose of this study was to evaluate the thermal environment of present state and energy consumption and to verify the improvement of energy performance applying free cooling in 5ESS-2000 telecommunication equipment room. Analysis program is used the DOE-2.1E and commercial CFD code, Star-CD. The results of the simulation show that free cooling could reduce 42.1% of cooling energy, increase 48.5% of heating energy because introduced outdoor air must heating and humidification. Therefore free cooling could reduce yearly 34,609.9 kWh of heating and cooling energy and this is reaching to 21.6% of total energy.