• Title/Summary/Keyword: 3-Phase transformer

Search Result 310, Processing Time 0.024 seconds

3-Phase Transformer Isolated Multi-level Inverter Using Common Arm (공통암을 이용한 3상 변압기 절연 멀티레벨 인버터)

  • Song, Sung-Geun;Park, Sung-Jun;Kim, Dong-Ok;Lim, Young-Cheol;Kim, Kwang-Heon
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.12 no.2
    • /
    • pp.149-156
    • /
    • 2007
  • The number of transformer and the size of transformer in inverter using 3-phase transformer could be reduced compare with a multi-level inverter using single phase transformer. but still the 3-phase transformer inverter needs many switches. In this study, we proposed the isolated multi-level inverter using 3-phase transformers and common arm, in this paper. Also, using phase angle control method with switching frequency equal to output fundamental frequency, harmonics component of output voltage and switching loss can be reduced. Finally, We tested multi-level inverter to clarify electric circuit md reasonableness through Matlab simulation and experiment by using prototype inverter.

Single Phase NPC Module - Development of 75KVA Single Phase Smart Transformer with 3 Serial Cascade Configuration (단상 NPC Module- 3직렬 Cascade 구성 방식의 75KVA급 단상 지능형 변압기 개발)

  • Park, Ju-Young;Niyitegeka, Gedeon;Cho, Kyeong-Sig;Kim, Myung-Yong;Park, Ga-Woo
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.22 no.2
    • /
    • pp.118-125
    • /
    • 2017
  • In this paper, we propose a smart transformer for a smart transformer miniature model, which can replace a 60 [Hz] single-phase transformer installed in an electric vehicle. The proposed smart transformer is lighter than a conventional transformer, can control instantaneous voltage, and can be expected to improve power quality through harmonic compensation. The proposed intelligent transformer consists of an incoming part, an AC/DC converter, and a dual active bridge. Only the incoming part and the AC/DC converter are described in this paper. The proposed intelligent transformer has 75 kVA 3.3 kV input and 750 V DC output, which are verified by simulation and experiment.

Zero Sequence Impedance of Yg-Yg Three Phase Core Type Transformer (Yg-Yg 3상 내철형 변압기의 영상분 임피던스 분석)

  • Jo, Hyunsik;Cho, Sungwoo;Shin, Changhoon;Cha, Hanju
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.6
    • /
    • pp.940-945
    • /
    • 2016
  • In this paper, zero sequence equivalent circuit of Yg-Yg three phase core-type transformer is analyzed. Many problems by iron core structure of the three phase transformer due to asymmetric three phase lines, which includes line disconnection, ground fault, COS OFF, and unbalanced load are reported in the distribution system. To verify a feasibility of zero sequence impedance of Yg-Yg type three phase transformer, fault current generation in the three phase core and shell-type Yg-Yg transformer is compared by PSCAD/EMTDC when single line ground fault is occurred. As a result, shell-type transformer does not affect the flow of fault current, but core-type transformer generate an adverse effect by the zero sequence impedance. The adverse effect is explained by the zero sequence equivalent circuit of core-type transformer and Yg-Yg type three phase core-type transformer supplies a zero sequence fault current to the distribution system.

Conceptual Design of a Single Phase 33 MVA HTS Transformer with a Tertiary Winding (3차 권선을 고려한 단상 33MVA 고온초전도 변압기의 개념설계)

  • Lee, S.W.;Kim, W.S.;Hahn, S.Y.;Hwang, Y.I.;Choi, K.D.
    • Progress in Superconductivity
    • /
    • v.7 no.2
    • /
    • pp.162-166
    • /
    • 2006
  • We have proposed a 3 phase, 100 MVA, 154 kV class HTS transformer substituting for a 60 MVA conventional transformer. The power transformer of 154 kV class has a tertiary winding besides primary and secondary windings. So the HTS transformer should have the 3rd superconducting winding. In this paper, we designed conceptually the structure of the superconducting windings of a single phase 33 MVA transformer. The electrical characteristics of the HTS transformer such as % impedance and AC loss vary with the arrangement of the windings and gaps between windings. We analyzed the effects of the winding parameters, evaluated the cost of each design, and proposed a suitable HTS transformer model for future power distribution system.

  • PDF

Analysis of the Ferroresonance Characteristics in 3 Phase Transformer Considering Lateral Length of the Primary Cable (1차측 케이블의 측면길이를 고려한 3상 변압기의 철공진 해석)

  • Cho, K.S.;Kim, K.S.;Kim, H.C.;Shin, J.R.
    • Proceedings of the KIEE Conference
    • /
    • 1997.07c
    • /
    • pp.825-828
    • /
    • 1997
  • The ferroresonance characteristics in 3 phase transformer is analysed in this paper using EMTP simulations under the consideration of lateral length of the primary cable. The ferroresonant overvoltage or undervoltage may occur in cable-fed 3 phase transformer when single phase switching is made in relatively remote point from the transformer, and this phenomena is closely related to the lateral length of the cable. This paper shows the voltage characteristics concerned with the transformer ferroresonance and the proper lateral length of the cable for reducing the voltage in 3 phase installation, through some case studies.

  • PDF

Problem Analysis by Iron Core Structure of the Transformer on Asymmetric three Phase lines and Prevention Measures (비대칭 3상 선로에서 변압기의 철심구조별 문제점 분석 및 방지대책)

  • Shin, Dong-Yeol;Yun, Dong-Hyun;Cha, Han-Ju
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.10
    • /
    • pp.1536-1541
    • /
    • 2012
  • The study analyzed problems by iron core structure of the three phased transformer on asymmetric three phase lines, which included line disconnections, ground faults, COS OFF, and unbalanced loads on the power distribution system. In particular, by analyzing PT combustion cases within the MOF, the study was able to analyze the combustion cause of the core-type transformer and its effect on the system, conduct simulations and practice demonstrations on the characteristics for each iron core structure of the three phase transformer using PSCAD/EMTDC, and suggest measures to prevent the combustion of the core-type transformer.

Characteristics of a 10kVA three phase superconducting power transformer (3상 10kVA 고온초전도 변압기의 특성)

  • Lee, S.W.;Lee, H.J.;Cha, G.S.;Lee, J.K.;Ryu, K.W.;Hahn, S.Y.
    • Proceedings of the KIEE Conference
    • /
    • 2001.10a
    • /
    • pp.24-26
    • /
    • 2001
  • The high temperature super-conductor transformer gains interests from the industries. This paper described construction and test results of a 10kVA HTS transformer. Three phase transformer with double pancake windings were constructed. BSCCO-2223 wire, silicon sheet steel core and FRP cryostats were used in that transformer After the test of basic properties of the 3 phase HTS transformer using no load test, short ciucuit test and full load test, continuous operation of 100 hours with pure resistive load has been carried out. Test proved over-load capability and reliability of the HTS transformer.

  • PDF

Design of an HTS Transformer with OLTC (OLTC를 고려한 고온 초전도 변압기의 설계)

  • Choi, J.H.;Lee, S.W.;Park, M.J.;Joo, H.G.;Han, J.H.;Hahn, S.Y.;Choi, K.D.
    • Progress in Superconductivity and Cryogenics
    • /
    • v.9 no.1
    • /
    • pp.67-71
    • /
    • 2007
  • HTS transformers which have been developed until now had only fundamental structures. Among the auxiliary functions of conventional transformers, voltage regulating is the most important one. For the voltage regulation, conventional transformers are equipped with on load tap changers (OLTCS). In this paper, we describe the possibility of the HTS transformer with OLTC. For the case study, we designed a single phase 33 MVA HTS transformer with OLTC. It is one of three individual HTS transformers which composes a 3 phase, 100 MVA transformer. It is expected to substitute for a 3 phase, 60 MVA conventional transformer in Korea. The parameters of an HTS transformer are varied due to the gap length between primary and secondary windings. The length was decided for the transformer to have the impedance of 12 %. Its size was limited to the one of the conventional transformer. The characteristics of the HTS transformer were analyzed in both case of having OLTC and not.

A Three-Winding Transformer Protective Relaying Algorithm Based on the Induced Voltages (유기 전압비를 이용한 3권선 변압기 보호계전 알고리즘)

  • 강용철;이병은
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.3
    • /
    • pp.173-178
    • /
    • 2003
  • This paper proposes a three-winding transformer protective relaying algorithm based on the ratio of the induced voltages (RIV). The RIV of the two windings is the same as the turn ratio for all operating conditions except an internal fault. For a single phase and a three-phase transformer containing the wye-connected windings, the induced voltages of the windings are estimated. For a three-phase transformer containing the delta-connected windings, the induced voltage differences are estimated using the line currents, because the winding currents are practically unavailable. The algorithm can identify the faulted phase and winding if a fault occurs on one phase of a winding. The test results clearly show that the algorithm successfully discriminates internal winding faults from magnetic inrush. The algorithm not only does not require hysteresis data but also can reduce the operating time of a relay.

A Technique for a Short-Circuit Current Calculation to The Single-Phase Transformer in the Three-Phase Systems (3상계통에서 단상변압기에 대한 단락전류계산 기법)

  • Park, Jae-Hwae;Jin, Tae-Seok
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.57 no.2
    • /
    • pp.170-175
    • /
    • 2008
  • This paper describes the exact short-circuit current calculation technique for the single-phase transformer which is installed in the three-phase systems and shorted in the secondary side. Not only the results for a short-circuit current calculation in the existing literatures are wrong, but also little literature deals with the short-circuit current for a single-phase transformer. So, this paper presents a theoretical study and calculation method for a single-phase short current. The validity of the presented method is investigated through Simulation using "Power Tools" and "PSim" program.