• Title/Summary/Keyword: 22.9kV Cable

Search Result 146, Processing Time 0.027 seconds

A Study of Over Voltage Ground Relay Operation Status at Opening of No-load Charged Cable (무부하 충전케이블 개방시 잔류전압에의한 과전압계전기 동작현상 연구)

  • Kim, Yeong-Han;Choi, Jong-Hyuck;Yoon, Ki-Seob
    • Proceedings of the KIEE Conference
    • /
    • 2000.07a
    • /
    • pp.185-187
    • /
    • 2000
  • Fault current is flowed into 154/23kV M. Tr when line-to-ground fault occurs in power system. NGR(Neutral Grounded Reactor) is set up in order to prevent M.Tr fault by limiting magnitude of fault currents. Here, disconnection of NGR causes voltage increase by L-C resonance and line-to-ground fault in an unearthed system results in voltage increase at healthy phases. So Over Voltage Ground Relay(OVGR) is used for tripping M.Tr. Also, buses at second phases of M.Trs are all connected with section circuit breakers closed for the purpose of parallel operation and load shedding. In case of speciality buses are comprised of power cable in part for GIS connection. When no-load charged cable or bus is open by a section CB, unbalanced voltage charged on the bus is induced. Also discrepant opening time for circuit breakers on different phases gives rise to unbalanced zero sequence voltage. It was observed that this zero sequence voltage detected in the 22.9kV P.T (Potential Transformer for bus) mal-operated 59GT and tripped M.Tr. The zero sequence voltage of which vanishing time is longer than relay operating time came out by EMTDC simulation. Also, it was shown that the voltage waves of actual test are similar to those of simulation. On the basis of above results, R-C circuit complement on the relay without any effect on a power system made operating time of the relay longer than vanishing time of distorted waves. Consequently, operating time of the relay was delayed and magnitude of distorted waves was decreased by increasing time constant of the relay.

  • PDF

Electromagnetic Force Calculation of Internet Winding Fault in A Distribution Power Transformer by using A Numerical Program (수치해석을 이용한 배전용 변압기 권선 고장시의 전자력 계산방법 연구)

  • Shin, Pan-Seok;Ha, Jung-Woo;Chung, Hee-Jun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.5
    • /
    • pp.60-67
    • /
    • 2007
  • In this paper, a simulation method of the internal winding fault is proposed to calculate winding current and electromagnetic force in a distribution power transformer by suing FEM program. The model of the transformer is a single phase, 60[Hz], 1[MVA], 22.9[kV]/220[V], cable-type winding. The short-circuit current and electromagnetic force are calculated by FEM(Finite Element Method) program(Flux2D) and the results we verified with theoretical formula and PSPICE program. The simulation results are fairly good agreement with the other verified methods within 5[%] error rate. The turn-to-turn short-circuit current is 500 times of the rated current and the electromagnetic force is about $20{\sim}200times$. The method presented in this study may serve as one of the useful tools in the electromagnetic force analysis of the transformer winding behavior under the short circuit condition for design of the structure.

Reduction of Radiated Emission of an Infrared Camera Using a Spread Spectrum Clock Generator (확산 스펙트럼 생성기를 이용한 적외선 카메라의 방사노이즈 저감에 관한 연구)

  • Choi, Bongjun;Lee, Yongchun;Yoon, Juhyun;Kim, Eunjun
    • The Journal of Korean Institute of Electromagnetic Engineering and Science
    • /
    • v.27 no.12
    • /
    • pp.1097-1104
    • /
    • 2016
  • The infrared camera is difficult to satisfy the RE-102 specification of Mil-Std-461. Especially, in the case of UAV electronics, shielded cable is not used, so it is difficult to meet the electromagnetic compatibility standard. In the RE-102 test of the IR camera for UAV, radiated noise exceeding 30 dBuV/m was observed in the range of 50 MHz to 200 MHz. As a result of pcb em scan, peak noise which caused by the harmonic frequency of the digital control signal clock was observed. Radiated noise was reduced by up to 22.9 dBuV/m by applying the spread spectrum clock generator(SSCG) with 3 % down spreading method to the camera control clock.

Partial Discharge Simulation and Analysis Based on Experiment in Underground Distribution Power Cables

  • Jung, Chae-Kyun;Kim, Jeong-Tae;Lee, Jong-Beom
    • Journal of Electrical Engineering and Technology
    • /
    • v.8 no.4
    • /
    • pp.832-839
    • /
    • 2013
  • This paper describes the simulation and experiment for partial discharge (PD) pulse propagation in 22.9kV CNCV power cables. To investigate the propagation characteristics of PD, experiments are carried out by injecting the PD pulse in 100m-long 60 $mm^2$ CNCV cable in the laboratory. The characteristics of PD are also simulated using EMTP to investigate and analyze PD in the same cable. By comparing the simulation and test results, parameter permittivity is recalculated by considering semiconducting screen in the process of simulation and analysis of PD. After it is proved that simulation results and test results are almost similar in the laboratory, extensive simulations are performed to analyse various PD characteristics such as propagation velocity, attenuation, etc. in 60 $mm^2$ and 325 $mm^2$ CNCV cables. Authors are confident that results obtained in this paper will be used as important technical materials to detect and investigate PD generated in transmission and distribution power cables.

Statistical Analysis of Breakdown Voltage using needle electrode inserted in XLPE (침전극하에서 XLPE의 절연파괴강도의 통계적평가)

  • Oh, Jae-Hyung;Jun, Eun-A;Park, Woon-Ho;Park, Soo-Gil;Park, Dae-Hee
    • Proceedings of the KIEE Conference
    • /
    • 1998.11c
    • /
    • pp.872-874
    • /
    • 1998
  • The needle electrode was inserted in virgin and 1.000 hr aged XLPE which is the insulation used for 22.9 kV underground distribution cable with the distance of 1, 1.5 and 2mm respectively. Breakdown voltage were measured for the virgin and 1.000 hr aged specimen and statistically evaluated through Weibull distribution. As the of electrode increase in virgin and 1.000 hr aged specimen. shape parameter and scale parameter showed increase coincidently. For shape parameter, the value of aged specimen showed the higher than that of virgin specimen.

  • PDF

Impurities of the Semiconductive Shield in the Power Distribution Cable (배전용 전력케이블의 반도전층에 함유되어 있는 불순물 분석)

  • Kim, S.J.;Song, I.K.;Kim, J.Y.;Han, J.H.;Suh, K.S.;Lee, C.R.;Lee, C.H.
    • Proceedings of the KIEE Conference
    • /
    • 1996.07c
    • /
    • pp.1794-1796
    • /
    • 1996
  • In order to evaluate the soundness of 10 year service-aged XLPE-insulated 22.9 kV underground distribution cables, semiconductive shields have been characterized. The edge of insulation near the insulation shield shows a drastic decrease of OIT. Impurities such as Ca, Mg, Fe, Cu were detected in both conductor and insulation shields. Their concentrations at the insulation shield are much higher than those at the strand shield. All these facts suggest that the edge of insulation near the insulation shield is degraded considerably, which might be attributed to the oxidation reaction of insulation by a large amount of impurities in the insulation shield.

  • PDF

Filter Test for Detecting Partial Discharge in XLPE Cable (XLPE 케이블의 PD 검출 필터 시험)

  • Kim, Dae-Yeol;Yun, Ju-Ho;Choi, Yong-Sung;Park, Dae-Hee;Lee, Kyung-Sup
    • Proceedings of the KIEE Conference
    • /
    • 2007.04b
    • /
    • pp.72-74
    • /
    • 2007
  • Due to a variable noises in the field underground lines, clear technology of noises is very important in the diagnosis technology of partial discharge. Therefore we progressed filter test to improve the measuring test of partial discharge in a field. We applied to field test after making W-LC filter for partial discharge measurement, and then designed experimental environment such as underground distribution lines of field. Measuring sensor for test was UHF sensor. And we analysed those using the Lemke Probe and oscilloscope (TDS-3054, Tektronix). Finally, we obtained excellent data of noise decrement in the joint box of 22.9[kV] distribution lines from above experiment.

  • PDF

Filter Test for Partial Discharge Detection of Underground Distribution Cables (지중배전케이블의 PD 검출용 필터 시험 연구)

  • Lee, Yong-Sung;Kim, Jung-Yoon;Lee, Kwan-Woo;Choi, Yong-Sung;Park, Dae-Hee
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.07a
    • /
    • pp.215-216
    • /
    • 2005
  • To decrease and remove of much noises that is detected in PD (partial discharge) measuring test. we forced on detection of those. We made W-LC filter for measuring PD. which adapted that to field test. We tested after design laboratory circumstances like field line. and then the phase change properties of detected signal in UHF sensor were measured by Lemke Probe and oscilloscope (TDS-3054. Tektronix). Eventually we checked decrement of noises from experimental result. Also from experimental result at the joint box of 22.9[kV] distribution line. we obtained reasonable data which enable noises to decrease. Hereafter those results will be adapted at ultra-high voltage for trouble prevention and on-line cable watch. diagnosis of those.

  • PDF

Analysis of PD Pulse Polarity Measured in Power Cable (전력케이블에서 측정된 부분방전 펄스극성 분석)

  • Lee, Ki-Joung;Lee, Yong-Sung;Park, Noh-Joon;Park, Dea-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.1617-1618
    • /
    • 2011
  • 케이블의 고장 검출과 예방진단을 위하여 방전펄스의 극성을 분석하고 시간차를 구하여 방전원의 방향 및 위치를 추정할 수 있다. 본 논문에서는 현장에서 적용되는 22.9[kV] 배전전력케이블을 모의실험실에 구성하였다 모의결함 가공 후에 부분방전 발생전압까지 가압 후 신호측정 및 분석을 하였으며 두개의 동일한 센서를 사용하여 하나는 단말기 접지 쪽에 고정취부 하였고 나머지 하나는 중간 접속부 안팎을 각각 측정하였다. 또한 케이블 간격별로 측정을 하였으며 측정된 방전펄스의 파두 극성을 분석하여 부분방전펄스의 방향 분석을 하였다. 측정에 적용된 센서는 HFCT센서를 적용 하였으며 측정펄스 분석은 오실로스코프를 이용하여 확인 하였다.

  • PDF

Characteristics of Radiated Electromagntic Wave Caused by Progress of Partial Discharge in Power XLPE(Crosslinkable Polyethylene) Dielectric (전력용 XLPE 절연체의 부분방전진전에 따른 방사전자파 특성)

  • Lee, H.C.;Park, K.S.;Yoon, D.H.;Lee, S.H.;Kim, J.H.;Kim, K.Ch.;Lee, K.S.
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.304-307
    • /
    • 2004
  • This paper simulated partial discharge caused by 22.9[kV] power cable using XLPE(Peroxide Crosslinkable Polyethylene) insulation having the outside damage. As one of the insulation diagnostic method a radiated electromagnetic waves were measured by an UHF method using a BiconiLog antenna(EMCO-3142) and a spectrum analyzer used to measure EMI, EMC. From results of this study, It was confirmed that discharge progress were possible to be estimated by the proposed method.

  • PDF