• Title/Summary/Keyword: 2차 냉동시스템

Search Result 24, Processing Time 0.04 seconds

Performance Analysis of R404A Refrigeration System with Internal Heat Exchanger Using R744 as a Secondary Refrigerant (R744를 2차 냉매로 사용하는 내부열교환기 부착 R404A 냉동시스템의 성능 분석)

  • Oh, Hoo-Kyu;Son, Chang-Hyo;Yi, Wen-Bin;Jeon, Min-Ju
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.25 no.10
    • /
    • pp.548-554
    • /
    • 2013
  • A thermodynamic analysis of the R404A refrigeration system with an internal heat exchanger using R744 as a secondary refrigerant is presented in this paper to optimize the design for operating parameters of the system. The main results are summarized as follows: The COP increases with increasing subcooling and superheating degree of R404A, internal heat exchanger and compression efficiency of the R404A cycle and evaporating temperature of the R744 cycle and decreasing temperature difference of the cascade heat exchanger and condensing temperature of the R404A cycle. The mass flow ratio decreases with increasing evaporating temperature of the R744 cycle and internal heat exchanger efficiency of the R404A cycle and decreasing subcooling and superheating degree of the R744 cycle, temperature difference of the cascade heat exchanger and condensing temperature of the R404A cycle.

Performance analysis of R404A refrigeration system using R744 as secondary refrigerant (R744를 2차냉매로 사용하는 R404A용 냉동시스템의 성능 분석)

  • Oh, H.K.;Son, C.H.
    • Journal of Power System Engineering
    • /
    • v.16 no.2
    • /
    • pp.24-29
    • /
    • 2012
  • In this paper, an analysis on performance and exergy of R404A refrigeration system using R744 secondary refrigerant was performed numerically to optimize the design for the operating parameters. The operating parameters considered in this study include subcooling and superheating degree, internal heat exchanger and compression efficiency, evaporation and condensation temperature in the R404A refrigeration cycle and temperature difference of cascade heat exchanger. The main results are summarized as follows : The COP(coefficient of performance) of R404A refrigeration system increases with increasing evaporation temperature. The evaporation capacity of R744 as secondary refrigerant increases with the increase in evaporation pressure of R744 secondary refrigeration. And the enthalpy in the evaporator outlet of R744 increases with the increasing evaporation pressure of R744 secondary refrigeration. Therefore, it is important to analysis for the relationship between COP of R404A refrigeration system and refrigeration capacity of R744. As cascade evaporation temperature increase, the exergy loss of condenser and compressor using R404A is the largest among all components. Therefore, the exergy loss in the condenser and compressor using R404A must be decreased to enhance the COP of R404A refrigeration system with R744 secondary refrigerant.

Evaporator Superheat Control of a Multi-type Air-Conditioning/Refrigeration System (멸티형 공조/냉동시스템의 증발기 과열도 제어)

  • 김태섭;홍금식;손현철
    • Journal of Energy Engineering
    • /
    • v.10 no.3
    • /
    • pp.253-265
    • /
    • 2001
  • This paper investigates a PI control problem for the evaporator superheat, i.e., temperature difference between the two-phase region and the exit region of an evaporator, for multi-type air-conditioning/refrigeration system. Mathematical model describing the characteristics of compressor, condenser, evaporator, and electronic expansion valve are first derived. Then, two transfer function from the current input applied to an electronic expansion valve to the wall-temperatures of an evaporator tube at two-phase region and superheated region, respectively, are derived. The stability of the closed loop system with the PI controller designed it analyzed by using Nyquist stability criterion. Simulation results are provided.

  • PDF

2.5kW DC-DC Converter of the Anti-Start Refrigerator Compressor for Commercial Vehicle (상용차를 위한 무시동 냉동기 압축기용 2.5kW DC-DC 컨버터)

  • Han, Keun-Woo;Kim, Young-Chan;Kim, Seong-Gon;Jung, Young-Gook;Lim, Young-Cheol
    • Proceedings of the KIPE Conference
    • /
    • 2014.07a
    • /
    • pp.21-22
    • /
    • 2014
  • 대형 상용차량을 위한 냉난방장치는 이동 또는 정차 중에도 일정 온도를 유지 시켜야한다. 종전의 상용차량의 냉동시스템은 엔진과 연계하여 압축기를 구동하거나 엔진과 연계된 발전기의 전력을 이용하여 온도를 유지하였다. 이러한 방식은 제어가 용이하지 않고 효율성이 낮은 단점을 가지고 있다. 본 논문에서는 이러한 단점을 개선하고자 대형 상용차량이 정차중인 무시동 기간에도 일정 온도를 유지 할 수 있도록 직렬 L-C 공진을 이용한 2.5kW급 DC-DC 컨버터를 제안 하였다.

  • PDF

Simulation of Refrigeration System with MPCM slurry (마이크로캡슐 잠열재 적용 냉동기의 성능 시뮬레이션)

  • Cho, Jong-Min;Kim, Yong-Chan;Cheon, Deok-Woo;Yoon, Joon-Sang
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.1213-1218
    • /
    • 2006
  • In this study, a numerical model for a vapor compression refrigeration system using MPCM slurries as a secondary fluid through an evaporator was developed, and the system performance was compared with that using water Generally, the MPCM system showed higher performance than the water system. The COP of the MPCM system was higher by 16.6 to 18.6% than that of the water system at all conditions. The MPCM slurry yields better performance in the aspect of heat transfer and heat transportation comparing to the sensible heat transfer medium such as water.

  • PDF

크라이오 펌프 종합특성평가 시스템 기술개발

  • In, Sang-Ryeol;Jeong, Seung-Ho;Hwang, Pil-Seo
    • Proceedings of the Korean Vacuum Society Conference
    • /
    • 2011.08a
    • /
    • pp.93-93
    • /
    • 2011
  • 고진공 펌프 국산화의 일환으로 터보분자 펌프와 크라이오 펌프 개발이 진행 중이다. 크라이오 펌프 개발은 기계연구원, 우성진공(주), 국민대학교가 연합해서 수행하고 있다. 올해 9월말에 끝나는 1단계 마지막 3차 년도에는 두 고진공 펌프 모두 시제품을 완성하고 성능을 입증해야 한다. 이를 위해 고진공 펌프 개발과 별도로 진공 펌프 종합특성평가 시스템 개발도 표준과학연구원 주도로 진행되고 있는데 크라이오 펌프 평가 시스템은 원자력연구원이 담당하고 있다. 완성된 크라이오 펌프 성능평가 장치는 상온 기준 5${\times}$10-11 mbar의 기저압력을 보이고 있어서 초고진공 영역에서 크라이오 펌프 운전성능을 평가할 수 있는 준비를 마쳤다. 현재 크라이오 펌프 냉동기는 전반적으로 목표 설계치에 근접한 냉각성능을 나타내고 있는데 예를 들면 2차 냉각단 냉각능력이 10 K, 10 W로 대형 크라이오 펌프를 제작하기에도 충분하다. 활성탄 어레이도 여러 모델들을 자작하여 배기성능을 시험해 보았으므로, 최종적으로 3,600 L/s 급에 적합한 어레이를 만들고 이를 개발된 냉동기에 얹고 열차폐와 몸통을 씌워 펌프로서의 운전성능을 평가하는 일이 남아있다. 시제품은 상용품과 달리 기기가 차지하는 공간이 크고 부대설비가 복잡해서 운전성능 평가 장치에 부착해서 실험하기 어려울 수도 있으므로 기계연구원 현장에서 진공 게이지와 기체도입구만 부착한 마구리 플랜지를 펌프 흡기구 위에 달고 간이로 배기속도를 측정하는 것도 고려하고 있다. 이 경우는 표준용기를 사용할 때보다 배기속도가 과대평가되므로 이를 보정해 주는 방안을 마련해 놓아야 한다.

  • PDF

설비기술 - 평창올림픽 빙상장에 해양심층수 활용한 냉난방 시스템 적용

  • 대한설비건설협회
    • 월간 기계설비
    • /
    • s.258
    • /
    • pp.68-70
    • /
    • 2012
  • 평창올림픽 빙상장에 해양심층수를 이용한 냉난방시스템 가동 방안이 추진된다. 국토해양부는 태양광이 도달하지 않는 수심 200m 아래의 해양심층수가 연중 $2^{\circ}C$ 정도를 유지하는 점을 이용해 세계 최초로 올림픽 빙상장에 한국해양연구원의 '해수냉난방시스템' 및 '해수온도차 발전' 연구개발 사업 성과를 적용한다고 밝혔다. 이번 기술이 전기에어컨이나 흡수식 냉동기 등에 적용되면 기존 시스템에 비해 에너지는 60%, 비용은 82%, 이산화탄소 배출량은 64% 줄어들게 된다.

  • PDF