• Title/Summary/Keyword: 2단압축 냉동장치

Search Result 4, Processing Time 0.02 seconds

An Experimental Study on Performance Characteristics of Two-Stage Compression Refrigeration Systems (2단압축 냉동장치의 성능특성에 관한 실험적 연구)

  • 김재돌;오후규;김성규;권옥배
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.18 no.2
    • /
    • pp.25-32
    • /
    • 1994
  • The characteristics of the R-22 two-stage compression refrigeration systems were investigated. The apparatus consisted of 0.5HP and 1HP hermetic reciprocating compressors for the high and low stage sides respectively, a condenser, an evaporator, a heat exchanger, four expansion valves, and two intercoolers. The experiments covered a range of refrigerant flow rates from 24 to 84kg/h, and the inlet temperature of cooling water in the condenser and heat source water in the evaporator ranged from 20 to 30$^.\circ}C$The results Showed that the refrigerant flow rate had greater effect on the refrigerating capacities, the compression efficiency and the coefficient of performance of two-stage compression systems than the inlet temperature of heat source water. And all these values were decreased with increasing inlet temperatures of the cooling water. The pressure drops in the evaporator of two-stage compression systems were decreased in proportion to the increase in the inlet temperature of the heat source and cooling water, but it was increased by the refrigerant flow rate.

  • PDF

Performance Analysis of 2-Stage Compression and 1-Stage Expansion Refrigeration System using Alternative Natural Refrigerants (암모니아 대체 자연냉매를 이용하는 2단압축 1단팽창 냉동시스템의 성능예측)

  • Roh, Geon-Sang
    • Journal of the Korean Institute of Gas
    • /
    • v.16 no.3
    • /
    • pp.42-47
    • /
    • 2012
  • In this paper, alternative natural refrigerant R290(Propane), R600(Butane), R717(Ammonia), R1270(Propylene) for freon refrigerant R22 were used working fluids for 2-stage compression and 1-stage expansion refrigeration system. The operating parameters considered in this study included evaporation temperature, condensation temperature, subcooling degree, superheating degree, mass flow rate ratio of inter-cooler. The main results were summarized as follows : The COP of 2-stage compression and 1-stage expansion refrigeration system increases with the increasing subcooling degree and mass flow rate ration of inter-cooler, but decreases with the increasing evaporating temperature, condensing temperature and superheating degree. Therefore, subcooling degree, mass flow rate ratio of inter-cooler of 2-stage compression and 1-stage expansion refrigeration system using natural refrigerants have an effect on COP of this system. The COP of natural refrigerants was higher than the COP of freon R22 in this study, so points to be considered are the security, the attached facilities for natural refrigerants than COP.

Development of an Automatic Refrigerant Charging Device for Refrigeration Applications (냉동기용 자동 냉매 충전장치 개발)

  • 김성수;윤희정;홍희기;강용태
    • Journal of Energy Engineering
    • /
    • v.12 no.4
    • /
    • pp.253-258
    • /
    • 2003
  • Manual type manifold gauge has been used for charging the refrigerant in the refrigeration systems. In this case, the refrigerant is released to the ambient during the hose-switching period. :he objectives of this study are to develop a novel automatic refrigerant charging system, and to quantify the effect of the automatic systems on the reduction of the non-condensable gas and the contamination of the compressor oil. The automatic charging system makes the pressure test, vacuum test, and refrigerant charging work very simple and easy because the charging hose does not have to be switched many times. It is found that the amount of water in the SiO$_2$and the compressor oil reduces to l/4 times of that for the manual type manifold gauge and the refrigerant is not released to the ambient at all when the automatic charging system is adopted.

Performance Analysis of a Seawater Ice Machine Applied Two-stage vapor compression refrigeration system for Various Refrigerants (2단 증기 압축식 냉동시스템을 적용한 해상용 제빙장치의 냉매에 따른 성능 분석)

  • Yoon, Jeong-In;Son, Chang-Hyo;Heo, Seong-Kwan;Jeon, Min-Joo;Jeon, Tae-Young
    • Journal of Power System Engineering
    • /
    • v.20 no.2
    • /
    • pp.85-90
    • /
    • 2016
  • Coefficient of performance (COP) for two-stage compression system is investigated in this paper to develop seawater ice machine. The system performance is analyzed with respect to degrees of superheating and subcooling, condensing and evaporating temperatures, compression and mechanical efficiencies and mass flow ratio in an inter-cooler. The main results are summarized as follows : The COP of the system grows when the mass flow ratio, subcooling degree and evaporating temperature edge up. Contrariwise, the system performance descends in case that superheating degree and condensing temperature increase. The most effective factor for the COP is the mass flow rate ratio. Each refrigerant has different limitation for a value of the mass flow ratio in the inter-cooler because of difference in material property.