• Title/Summary/Keyword: 환기 유닛

Search Result 30, Processing Time 0.031 seconds

폐열회수 환기유닛의 인증제도 및 성능시험방법

  • 한화택;김경환
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.33 no.1
    • /
    • pp.28-34
    • /
    • 2004
  • 본고에서는 한국설비기술협회에서 추진 중인 패열화수 환기유닛(Heat Recovery Ventilator)에 대한 품질인증제도의 추진배경 및 핵심적인 몇가지 인증표시항목에 대한 성능시험 방법에 관하여 소개한다.

  • PDF

Uncertainty Analysis of Test Method for Heat Recovery Ventilators (폐열회수 환기유닛의 인증시험 방법에 대한 오차분석)

  • Han, H.;Choo, Youn-Bok
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.423-428
    • /
    • 2006
  • Twenty nine HRV models have been tested for last two years since the attestation system has been started by KARSE. It is the objective of the present study to analyze the performance test results. Uncertainty analysis has been conducted to find the effects of measured variables on the uncertainties of test results. The uncertainty of enthalpy is found to be affected by the uncertainty of wet bulb temperature significantly, but not by that of dry bulb temperature for the present range of parameters. The uncertainty of effective enthalpy efficiency is calculated to be 6%P for the cooling condition, and 3%P for the heating condition approximately. In order to reduce the uncertainty of the test results, the uncertainty of wet bulb temperature should be minimized and the indoor/outdoor test conditions should be modified so as to increase the enthalpy difference.

  • PDF

Evaluation of Thermal Comfort and Ventilation Performance in the Lecture Room with Ventilation System and Two Different Air-conditioning Systems: System Air-conditioner or Fan Coil Unit (환기시스템 설치 강의실에서 시스템에어컨과 팬코일유닛의 열쾌적성 및 환기성능 평가)

  • Han Chang-Woo;Noh Kwang-Chul;Oh Myung-Do
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.11
    • /
    • pp.1079-1087
    • /
    • 2005
  • In this paper, thermal comfort and ventilation performance characteristics in the lecture room with the ventilation system and two different air-conditioning systems, system air-conditioner or fan coil unit, were evaluated by experimental and numerical methods. We compared the measured data with the computational results of the predicted mean vote and carbon dioxide concentration. Additionally the ventilation effectiveness was calculated numerically. From a viewpoint of the uniformity of PMVs in the lecture room, the thermal distribution performance of the system air-conditioner was more effective than the fan coil unit. Carbon dioxide concentration and ventilation effectiveness were barely affected by the type of the air-conditioning system.

Experimental Study on Heat Transfer and Pressure Drop of Heat Exchangers for Cooling Fan Coil Unit (냉방용 팬코일 유닛 열교환기의 열전달 및 압력강하 특성 실험연구)

  • Kwon, Young-Chul;Ko, Kuk-Won;Kwon, Jeong-Tae
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.9 no.3
    • /
    • pp.599-604
    • /
    • 2008
  • An experimental study has been performed to investigate the air-side capacity and pressure drop of the fin-tube heat exchanger for a fan coil unit under a cooling condition. The experimental data of five kinds of slit fin-tube heat exchangers were measured using an air-enthalpy calorimeter and a constant temperature water bath. Cooling capacities at the air and water rating flow rates were larger at the lower inlet water temperature. With increasing the water flow rate, the cooling capacity increased at the constant rate. Under the lower inlet water temperature, since the condensate was generated more on the fin-tube surface, the air-side pressure drop of the heat exchanger was larger.

Heat Exchangers for Refrigeration and Air Conditioning Equipment (냉동공조용 열교환기)

  • 오후규
    • Journal of the KSME
    • /
    • v.35 no.9
    • /
    • pp.816-828
    • /
    • 1995
  • 냉동공조용 열교환기의 종류, 특징, 기술개발 동향, 전망 등에 대해 요약한 결과를 정리하면 다 음과 같다. (1) 암모니아 냉매가 다시 각광을 받음에 따라 응축기의 형식도 크게 변하고 있다. 이러한 변화로 핀 튜브를 사용한 횡형, 금속용착형 플레이트 식, 플레이트 핀 식의 응축기들이 암모니아 용으로 적용되기 시작하고 있다. (2) 암모니아 냉동장치는 현재에도 많이 적용되고 있으나 대부분 중앙 집중식 천정증발기나 강관 제 유닛 쿨러를 사용하고 있다. 그러나 최근 기술의 발전과 더불어 알루미늄 관 알루미늄 핀 증발기가 개발됨에 따라 암모니아 냉매도 프레온 냉매와 마찬가지로 건식, 분산식으로 적용되게 되었으며 이 분야의 기술개발이 요청된다. (3) 열교환기의 연구 방향은 에너지 절약, 공간 절약에 기여하면서도 성능향상을 이룩할 수 있는 기술개발, 그리고 소음이 적은 기기 제조 기술이 요망된다. 또한, 착상에 대한 기술적 대책, 근 본적 대책에 대한 대비가 요망되며, 기존 냉매에 대한 대체 냉매용 최적 열교환기에 대한 적극적 연구가 요망된다. (4) 제한된 에너지 자원, 지구환경, 열악한 우리나라의 에너지 사정 등을 고려할 때 냉동공조용 열교환기의 성능 향상에 대한 국가와 일반 소비자들의 기대는 더욱 증가하리라 예상된다. 이들 요구를 만족시키기 위해서는 냉동공조용 열교환기의 성능 향상, 열교환기의 제작에 필요한 자 원의 절약, 생산성 향상, 설치장소와 관련한 효율적인 공간활용, 열교환기 자체 소음의 최소화 등의 방면에 착실한 연구 개발이 있어야 할 것이다.

  • PDF