열전달 촉진관에서 HFC32/HFC152a 혼합냉매의 외부 응축열전달계수 (External Condensation Heat Transfer Coefficients of HFC32/HFC152a Mixtures on Enhanced Tubes)

  • 이요한;강동규;김현주;이호생;정동수
    • 설비공학논문집
    • /
    • 제26권7호
    • /
    • pp.315-321
    • /
    • 2014
  • In this study, external condensation heat transfer coefficients (HTCs) of two non-azeotropic refrigerant mixtures of HFC32/HFC152a at various compositions were measured on both 26 fpi low-fin and Turbo-C enhanced tubes, of 19.0 mm outside diameter. All data were taken at the vapor temperature of $39^{\circ}C$, with a wall subcooling of 3~8 K. Test results showed that the HTCs of the tested mixtures on the enhanced tubes were much lower than the ideal values calculated by mass fraction weighting of the pure component HTCs. Also, the reduction of HTCs due to the diffusion vapor film was much larger than that of a plain tube. Unlike HTCs of pure fluids, HTCs of the mixtures measured on enhanced tubes increased, as the wall subcooling increased, which was due to the sudden break-up of the vapor diffusion film with an increase in wall subcooling. Finally, the heat transfer enhancement ratios for mixtures were found to be much lower, than those of pure fluids.

수평증발관내 R22/R114 혼합냉매의 열전달 특성에 관한 연구 (A Study for Evaporation Heat Transfer Characteristic of R22/Rl14 Refrigerant Mixtures in a Horizontal Tube)

  • 윤치한;이종인;하옥남
    • 설비공학논문집
    • /
    • 제12권5호
    • /
    • pp.502-510
    • /
    • 2000
  • Evaporation heat transfer characteristics were studied in a horizontal tube using R22/R114 non-azotropic refrigerant mixture. the heat transfer coefficient was high in the upper part for pure refrigerants, and heat transfer coefficient was low in the lower part for refrigerant mixtures. In the low quality region where nucleate boiling was dominant, the average heat transfer coefficient was low. In the region where forced convection was dominant, heat transfer coefficient was high. Results show that the heat transfer coefficient for pure refrigerants obtained by experiments were lower than those of Yoshida et al. but agreed well with Jung et al., and Chen et al. data. But the heat transfer coefficients for refrigerant mixtures were lower about 20% than those predicted by the equation for pure refrigerant.

  • PDF

프로판과 R227ea 혼합냉매의 기상-액상 평형 실험 (An Experimental Study on the Vapor-Liquid Equilibria of Propane and R227ea Mixtures)

  • 강대경;김주혁;김민수;김영일
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2003년도 추계학술대회
    • /
    • pp.245-249
    • /
    • 2003
  • Vapor-liquid equilibrium data were obtained for system of propane + R227ea (Heptafluoropropane) over the temperature range from 253.15 K to 323.15 K at 10 K intervals. Experiments were performed in a circulation type apparatus by injecting vapor through liquid pool using a magnetic pump. This system forms azeotrope in the temperature range of this study. The experimental results were correlated with the Peng-Robinson (PR) equation of state and Redlich-Kwong-Soave (RKS) equation of state using the van der Walls one-fluid mixing rule and were compared with each other.

  • PDF

수열원 히트펌프 용 HFC32/HFC152a 혼합냉매의 성능평가 (Performance of HFC32/HFC152a Mixture for Water-source Heat Pumps)

  • 강동규;김욱진;정동수
    • 설비공학논문집
    • /
    • 제24권5호
    • /
    • pp.391-400
    • /
    • 2012
  • In this study, performance of HFC32/HFC152a mixture is measured in the composition range of 20 to 50% R32 with an interval of 10% for the comparison with the conventional HCFC22 in water-source heat pumps. Tests are carried out under the same capacity in a heat pump bench tester equipped with a variable speed compressor at the evaporation and condensation temperatures of 7/$45^{\circ}C$ and -7/$41^{\circ}C$ for summer and winter conditions, respectively. Test results show that the compressor power of the HFC32/HFC152a mixture is 13.7% lower than that of HCFC22 while the coefficient of performance(COP) the HFC32/HFC152a mixture is 15.8% higher than that of HCFC22. Hence, from the view point of energy efficiency, the HFC32/HFC152a mixture is excellent as compared to HCFC22. Compressor discharge temperatures of HFC32/HFC152a mixture are increased up to $15.4^{\circ}C$ as compared to that of HCFC22. The amount of charge for HFC32/HFC152 mixture decrease up to 27% as compared to that of HCFC22. Overall, HFC32/ HFC152a mixture is an excellent long term candidate to replace HCFC22 in water-source heat pumps.

R170/R290 혼합냉매 적용 히트펌프 성능 평가 (Performance of Heat Pumps Charged with R170/R290 Mixture)

  • 박기정;이철희;정동수
    • 설비공학논문집
    • /
    • 제20권9호
    • /
    • pp.590-598
    • /
    • 2008
  • In this study, performance of R170/R290 mixtures is measured on a heat pump bench tester in an attempt to substitute R22. The bench tester is equipped with a commercial hermetic rotary compressor providing a nominal capacity of 3.5kW. All tests are conducted under the summer cooling and winter heating conditions of $7/45^{\circ}C$ and $-7/41^{\circ}C$ in the evaporator and condenser respectively. During the tests, the composition of R170 is varied from 0 to 10% with an interval of 2%. Test results show that the coefficient of performance (COP) and capacity of R290 are up to 15.4% higher and 7.5% lower than those of R22 for both conditions respectively. For R170/R290 mixture, the COP decreases and the capacity increases with an increase in the amount of R170. The mixture of 4%R170/96%R290 shows the similar capacity and COP as those of R22. For the mixture, the compressor discharge temperature is $16{\sim}30^{\circ}C$ lower than that of R22. There is no problem with mineral oil since the mixture is mainly composed of hydrocarbons. The amount of charge is reduced up to 58% as compared to R22. Overall, R170/R290 mixture is a good long term 'drop-in' candidate to replace R22 in residential air-conditioners and heat pumps.

수평관에서 프로판, 이소부탄, BFC134a를 포함한 혼합냉매의 풀비등 열전달계수 (Pool Boiling Heat Transfer Coefficients of Mixtures Containing Propane, Isobutane and HFC134a on a Plain Tube)

  • 박기정;백인철;정동수
    • 설비공학논문집
    • /
    • 제18권12호
    • /
    • pp.955-963
    • /
    • 2006
  • Nucleate pool boiling heat transfer coefficients (HTCs) were measured with one nonazeotropic mixture of Propane/Isobutane and two azeotropic mixtures of HFC134a/Isobutane and Propane/HFC134a. All data were taken at the liquid pool temperature of $7^{\circ}C$ on a horizontal plain tube with heat fluxes of $10kW/m^2\;to\;80kW/m^2$ with an interval of $10kW/m^2$ in the decreasing order of heat flux. The measurements were made through electrical heating by a cartridge heater. The nonazeotropic mixture of Propane/Isobutane showed a reduction of HTCs as much as 41% from the ideal values. The azeotropic mixtures of HFC134a/Isobutane and Propane/HFC134a showed a reduction of HTCs as much as 44% from the ideal values at compositions other than azeotropic compositions. At azeotropic compositions, however, the HTCs were even higher than the ideal values due to the increase in the vapor pressure. For all mixtures, the reduction in heat transfer was greater with a larger gliding temperature difference. Stephan and $K{\ddot{o}}rner's$ and Jung et al's correlations predicted the HTCs of mixtures with a mean deviation of 11%. The largest mean deviation occurred at the azeotropic compositions of HFC134a/Isobutane and Propane/HFC134a.

HFC32/HFC125 혼합냉매의 히트펌프 성능 평가 (Performance of HFC32/HFC125 Mixtures for Heat Pumps)

  • 김욱진;강동규;이요한;정동수
    • 설비공학논문집
    • /
    • 제23권12호
    • /
    • pp.791-798
    • /
    • 2011
  • In this study, performance of R410A(50%R32/50%R125) and HFC32/HFC125 mixture is measured to examine the effect of composition shift of R410A used for various air-conditioners and heat pumps. The composition of HFC32/HFC125 mixture varies from the reference composition of R410A ${\pm}10%$ with 5% interval. Tests carried out in a heat pump bench tester at the evaporation and condensation temperatures of $7/45^{\circ}C$ and $-7/41^{\circ}C$ for summer and winter conditions, respectively. Test results show that both the coefficient of performance (COP) and compressor power of the HFC32/HFC125 mixture have the maximum difference of 2.0% as compared to those of R410A. Compressor discharge temperatures of HFC32/HFC125 mixture are increased up to $6.7^{\circ}C$ as compared to that of R410A. The amount of charge for HFC32/HFC125 mixture vary within 5.6% as compared to that of R410A. Overall, performance of R410A is not appreciably affected by the composition shift of ${\pm}10%$ of R32 under both air-conditioning and heat pumping conditions.

세관을 사용한 응축기에서 R-22의 대체냉매인 R-410A의 응축 열전달 특성 (Condensation Heat Transfer Characteristics of R-410A as an Alternative R-22 in the Condenser with Small Diameter Tubes)

  • 손창효
    • 청정기술
    • /
    • 제13권2호
    • /
    • pp.151-158
    • /
    • 2007
  • 프레온계 냉매의 지구온난화와 오존층파괴 문제로 인해 대체냉매로서 R-410A가 주목을 받고 있다. 이러한 대체냉매를 세관에 적용시킬 경우 효율을 향상시킬 뿐만 아니라 지구환경에 미치는 영향을 감소시키고, 대기를 청정하게 만드는 기술 및 방안으로 각광 받고 있다. 따라서 본 연구에서는 R-22의 대체냉매로 각광받고 있는 R-410A의 세관응축기 내에서의 응축열전달 특성에 대해 실험적으로 고찰하고자 하였다. 실험장치는 유동양식, 열전달, 압력강하 특성을 파악할 수 있도록 제작되었고, 주요 구성품은 냉매펌프, 증발기, 응축기(시험부), 사이트 글라스(가시화부), 압력탭, 측정장치 등이다. 시험부의 내관은 내경 3.36 mm와 5.35 mm인 수평평활 동관이다. 실험변수들의 범위로서 질량유속 $200{\sim}500\;kg/m^2s$이고, 열유속은 $1.0{\sim}2.4\;kW$이다. R-410A의 응축열전달 계수가 R-22에 비해 최대 5% 정도 높은 것을 알 수 있었다. 세관 내 R-410A와 R-22의 유동양식은 환상류 영역이 지배적으로 나타남을 관찰하였고, 건도가 0.2 이하인 영역에서는 성층류가 나타남을 확인할 수 있었다. 내경 3.36 mm의 압력강하가 내경 5.35 mm에 비해 $30{\sim}50%$정도 높았다. 종래의 응축 열전달 상관식과 실험데이터를 비교한 결과, Fujii의 상관식과 최대 40%이내에서 일치하였다.

  • PDF