R32를 포함한 R22 대체 혼합냉매의 모세관 유동 특성 (Flow Characteristics of Refrigerant Mixtures with R32 in a Capillary Tube)

  • 장세동;노승탁
    • 설비공학논문집
    • /
    • 제8권2호
    • /
    • pp.177-186
    • /
    • 1996
  • The characteristics of the flow of pure HFC refrigerants(R32, R125, and R134a) and their mixtures through capillary tubes were investigated experimentally. Two capillary tubes with 1.2mm and 1.6mm inner diameter and 1.5m length were adopted as test sections. Mass flow rates and temperatures and pressures were measured for several condensing temperatures and degrees of subcooling at capillary tube inlet. The effects of the condensing temperature, inner diameter of capillary tube, and subcooling on the mass flow rate of refrigerants were discussed, and the mass flow rates of HFC refrigerants were compared with that of R22. The pressure and temperature distributions along the capillary tube compared with that of R22. The pressure and temperature distributions along the capillary tube show that there is a metastable equilibrium state in the flow through the tube. Underpressure for vaporization increases as refrigerant mass flux increases and inlet subcooling decreases. Empirical correlation was suggested to predict underpressure for vaporization of the HFC refrigerants.

  • PDF

평판 표면에서 HFC32/HFC152a 혼합냉매의 풀 비등 열전달계수 (Pool Boiling Heat Transfer Coefficient of HFC32/HFC152a on a Plain Surface)

  • 강동규;이요한;정동수
    • 설비공학논문집
    • /
    • 제25권9호
    • /
    • pp.484-492
    • /
    • 2013
  • Nucleate pool boiling heat transfer coefficients (HTCs) are measured with HFC32/HFC152a mixture at several compositions. All data are taken at the liquid pool temperature of $7^{\circ}C$, on a horizontal plain square surface of $9.53{\times}9.53$ mm, with heat fluxes of 10 $kW/m^2$ to 100 $kW/m^2$ with an interval of 10 $kW/m^2$, in the increasing order of heat flux. Test results show that the HTCs of these mixtures are up to 45% lower than those of the ideal HTCs calculated by a linear mixing rule with pure fluids' HTCs, due to the mass transfer resistance associated with non-azeotropic refrigerant mixtures. Pool boiling data show the deduction in HTCs with an increase in GTD of the mixture. The present mixture data agree well with five well known correlations, within 20% deviation.

고온용 밀폐형 왕복동 압축기에서 탄화수소계 혼합냉매 적용 (The application of hydrocarbon refrigerant mixtures in a hermetic reciprocating compressor for high back pressure conditions)

  • 김기문;박희용
    • 설비공학논문집
    • /
    • 제11권2호
    • /
    • pp.262-269
    • /
    • 1999
  • The application of hydrocarbon refrigerant mixtures in a hermetic reciprocating compressor for dehumidifier is investigated. The selected refrigerants are R12, R134a, HC-Blend (R290/R600a), CX(R152a/R600a) and OS-l2a. Both theoretical and experimental investigations have been performed for the selected refrigerants. The test results of hydrocarbon refrigerants have been compared to traditional refrigerant(R12) and R134a. The results show that hydrocarbon refrigerant mixtures(HC-Blend, CX and OS-l2a) are very good alternatives in the refrigeration system for R12 and R134a.

  • PDF

혼합매체를 사용하는 냉동기, 열펌프에서 2상열전달의 중요성

  • 노승탁
    • 기계저널
    • /
    • 제30권4호
    • /
    • pp.358-366
    • /
    • 1990
  • 이 글은 최근 대두되는 CFC 문제와 연관하여 혼합냉매를 사용함으로서 얻어지는 이점과 이들의 예를 알아보고 이에 수반하여 열교환기의 설계 및 제작에 있어서 필수적인 역할을 하는 혼합매 체에서의 2상유동열전달의 중요성과 체계적인 연구의 필요성을 강조하기 위하여 기술한 것이며 이 분야에 대한 새로운 지식을 전반적으로 집약하거나 자료를 광범위하게 수집한 것이 아니다.

  • PDF

공조기용 Finned Tube 열교환기 (Finned Tube Heat Exchanger for Air Conditioning System)

  • 김무환
    • 기계저널
    • /
    • 제35권9호
    • /
    • pp.776-793
    • /
    • 1995
  • 인간이 쾌적한 환경을 요구하는 수준과 함께 개발 및 개선되어 온 공조용 finned tube 열교환 기에 대한 연구는 앞으로도 환경과 소형화 및 정숙 운전의 요구에 부응하기 위하여 지속적인 연구 및 개선이 요구될 것이다. 또한, 생산기술이 발달함에 따라 이에 적합한 새로운 형태의 경 제적이고 효율적인 열교환기의 설계가 필요할 것이다. 특히 앞으로 중요성이 더욱 강조될 환경 오염, 재료의 재활용 등의 측면은 현재 우리가 개척해야 할 분야일 것이다. 한편으로는 국내의 짧은 열교환기 개발의 역사에 의하여 지금까지 사용되어 온 외국의 기술 및 특허 등의 무 제에 대하여 국내 고유의 기술을 보유할 수 있도록 더욱 노력을 하여야 할 것이다. 나아가 실제 열 교환기에서의 확장표면의 효과, 냉동유의 영향 그리고 혼합냉매의 열전달 특성 등을 고려할 수 있는 상관식을 개발함으로써 국내의 열교환기 설계기술이 외국에 비하여 우위를 점할 수 있도록 하는 노력이 계속되어야 할 것이다. 그리고 미래까지 이러한 기술적 우위를 지속하기 위해서는 혼합냉매의 상변화 열전달현상의 기본 메카니즘을 밝히는 등의 열교환기에서의 열유동특성에 대한 기초적인 연구와 새로운 형태의 열교환기 개발 및 전기장을 이용한 열전달 촉진 등의 신 기술을 이용한 열전달 연구 등에 대한 투자와 관심이 지속되어야 한다.

  • PDF

수평평활관내의 비공비 혼합냉매의 응축에 대한 예측모델 (A Prediction Model for Condensation of Zeotropic Refrigerant Mixtures Inside a Horizontal Smooth Tube)

  • 이상무;박병덕
    • 설비공학논문집
    • /
    • 제13권4호
    • /
    • pp.262-270
    • /
    • 2001
  • This paper deals with a prediction method for the condensation of ternary refrigerant mixture inside a horizontal smooth tube. Based on some reliable assumptions, the governing equations for the local heat and mass transfer characteristics are derived, and the prediction for the condensation of ternary zeotropic refrigerant mixtures composed of HFC32/HFC125/HFC134a, including R407C, is carried out. The local values of vapor quality, thermodynamic states at bulk vapor, vapor-liquid interface and bulk liquid, mass flux etc. are obtained for a constant wall temperature and a constant wall heat flux conditions, and the effects of the composition of HFC32/HFC125/HFC134a on heat transfer characteristics are examined. The prediction result is also compared with experimental data for condensation of ternary refrigerant mixtures. The predicted wall temperature distribution has a similar trend with experimental data but the predicted local heat transfer coefficients are 20-30% higher than the experimental data.

  • PDF

혼합냉매를 사용한 열펌프 시스템의 성능과 열전달 특성 (Performance and Heat Transfer Characteristics of Heat Pump System Using Refrigerant Mixtures)

  • 김동섭;신지영;노승탁
    • 설비공학논문집
    • /
    • 제4권4호
    • /
    • pp.360-369
    • /
    • 1992
  • A heat pump system is constructed to evaluate its performance and heat transfer characteristics with mixtures of R22/R142b as working fluids. The heat transfer in the evaporator and the overall performance are measured and analyzed in terms of the compositions and relevant variables. Possibility of capacity modulation by changing composition is observed without degradation of heat transfer coefficients and coefficient of performance. The cooling capacity is varied continuously within 200 percent based on minimum capacity at constant compressor speed. For similar cooling capacity, COP is improved by mixing two refrigerants and shows maximum value at 60% mass fraction of R22. Average heat transfer coefficients of mixtures decrease in comparison with pure refrigerants at similar cooling capacity and mass flow rate. However, the overall heat transfer coefficients decrease moderately. A cycle simulation is performed in order to manifest the advantages of using refrigerant mixtures, considering experimentally observed heat transfer characteristics.

  • PDF

프로판/이소부탄 혼합냉매를 적용한 가정용 소형 멀티 냉동시스템의 성능특성에 관한 연구 (Evaluation of the Performance Characteristics of Propane/isobutene Refrigerant Mixtures in a Small multi-refrigeration System)

  • 이무연;최석재;김상욱
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2004년도 춘계학술대회
    • /
    • pp.1945-1950
    • /
    • 2004
  • In this paper, The performance of Kim-Chi refrigerator with three evaporator and one compressor was investigated in employing 55% propane and 45% isobutane (R290/R600a) refrigerant mixture as an alternative refrigerant of R134a. The drop in test was performed by varying both refrigerant charge amount and capillary tube length in order to find both the performance and reliability of a small multi-refrigeration system. As a result, Both the power consumption and COP is increased by about 15% and 10%, respectively as compared to the baseline R134a system. In addition, the propane/isobutene refrigerant mixture system took advantage of the minimization of modification and redesigning of system components because of similar thermodynamic properties with R134a such as saturation pressure, temperature, normal boiling point(NBP) characteristics

  • PDF

HFC125+Propane 혼합냉매의 기-액 평형에 관한 실험적 연구 (An Experimental Study of Vapor-Liquid Equilibrium for HFC12S+Propane Refrigerant Mixtures)

  • 강준원;박영무;유재석;이종화
    • 설비공학논문집
    • /
    • 제15권7호
    • /
    • pp.563-571
    • /
    • 2003
  • The forty vapor-liquid equilibrium data of the binary system, HFC125+Propane, were measured between 273.15 and 313.15 K at 10 K interval and the composition range 0.2∼0.75, respectively. Experiments were performed in a circulation type apparatus in which the vapor phase was forced through the liquid phase. The composition at equilibrium were mea-sured by gas chromatography, and its response was calibrated using gravimetrically prepared mixtures. Vapor-liquid equilibrium data were calculated by using CSD equation of state and compared with the experimental data.