• Title/Summary/Keyword: 혼합냉매

Search Result 156, Processing Time 0.031 seconds

Simulation of the Mixed Propane Refrigeration Cycle Using a Commercial Chemical Process Simulator (상용성 화학공정모사기를 활용한 혼합냉매 이용 냉동사이클의 전산모사)

  • Cho, Jung-Ho;Kim, Young-Woo
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.10 no.11
    • /
    • pp.3253-3259
    • /
    • 2009
  • In this study, a computer simulation has been performed for the refrigeration cycle using mixed refrigerants in order to decrease the process stream temperature to $-20^{\circ}C$. Refrigerant supply temperature was assumed to be $-30^{\circ}C$ considering the temperature difference as $10^{\circ}C$ with process stream. Peng-Robinson equation of state model was selected for the computer simulation. A new alpha function proposed by Twu et al was used for an accurate prediction of pure component vapor pressure experimental data. One fluid mixing rules were used for the estimation of mixture vapor-liquid equilibria calculations. A commercial process simulator, PRO/II with PROVISION was utilized for the simulation of the overall refrigeration process. In order to minimize the compressor power consumption, we have optimized the two-stage compression system by varying the first stage compressor outlet pressure. Finally, we could obtain the minimum total power 755.7kW at the first stage compressor outlet pressure, 6 bar.

A study on the room heating by solar assisted heat pump using the alternatives (대체냉매적용 태양열 열펌프시스템에 의한 난방성능분석(1))

  • 선경호;정현채
    • Proceedings of the Korea Society for Energy Engineering kosee Conference
    • /
    • 1995.05a
    • /
    • pp.94-99
    • /
    • 1995
  • 본 연구는 태양열 열펌프시스템에 의한 약 6평 규모의 실내의 난방방법으로서 간접 난방인 온수순환난방과 직접난방인 복사난방의 성능을 분석하였다. 태양열 열펌프의 최대의 열적성능을 나타낼 수 있도록 알루미늄 롤 본드형 태양열 집열기의 면적을 조절하였으며 집열효과를 극대화하기 위하여 온도감응 자동팽창밸브의 용량을 변화시켰다. 본 실험에서 적용된 태양열 열펌프 난방은 서울지방 봄 가을철의 외기온도에서 실내온도가 18~2$0^{\circ}C$로 유지되도록 설계제작되었다. 태양열 열펌프시스템에 적용된 작용유체는 온수순환 난방에는 R-12냉매. 그 대체냉매는 R-134a 및 혼합냉매, 복사난방에는 R-22냉매이었다.

  • PDF

A Study on Heat Transfer Characteristics in Flow Boiling of Pure Refrigerants and Their Mixtures in Horizontal Tube (수평 전열관내 유동비등하는 순수냉매와 혼합냉매의 열전달 특성에 관한 연구)

  • 임태우;한규일
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.2
    • /
    • pp.144-151
    • /
    • 2003
  • An experimental study was carried out in a uniformly heated horizontal tube to examine heat transfer characteristics of pure refrigerants, R134a and R123, and their mixtures during flow boiling. The flow pattern was also observed through tubular sight glasses with an internal diameter of 10 mm located at the inlet and outlet of the test section. Tests were run at a pressure of 0.6 MPa and in the heat flux ranges of 5~100 kW/$m^2$, vapor Quality 0~100 percent and mass velocity of 150-600 kg/$m^2$s. The observed flow patterns were compared to the flow pattern map of Kattan et al., which predicted well the present data over the entire range of mass velocity employed in this study. Heat transfer coefficients of the mixture were less than the interpolated values between pure fluids both in the low quality region where the nucleate boiling is dominant and in the high quality region where the convective evaporation is dominant.

Frictional Pressure Drop of a Capillary Tube Flow of Pure HFC Refrigerants and Their Mixtures (HFC 순수냉매 및 혼합냉매의 모세관내에서 마찰에 의한 압력강하)

  • Chang, S.D.;Ro, S.T.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.7 no.4
    • /
    • pp.589-599
    • /
    • 1995
  • The frictional pressure drop of a capillary tube flow is experimentally investigated for pure refrigerants such as R32, R125, and R134a and refrigerant mixtures such as R32/R134a(30/70 by mass percent), R32/R125(60/40), R125/R134a(30/70), and R32/R125/R134a(23/25/52). The binary interaction parameters for the calculation of viscosities of refrigerant mixtures are found based upon the data in the open literature. Several homogeneous flow models predicting the viscosity of two-phase region are compared to select the best model. Cicchitti's equation is known to be the most adequate for the prediction of the viscosity for refrigerant mixtures, which is used in the analysis of adiabatic capillary flows. A model for the prediction of the frictional pressure drop of single and two-phase flow is developed for refrigerant mixtures in this study. This model may be used to design and analyze the performance of a capillary tube in the refrigerating system.

  • PDF

Prediction on Performance of Cascade Refrigeration System using Alternative Freon and Natural Refrigerants (대체 프레온 및 자연 냉매를 이용하는 이원 냉동시스템의 성능 예측)

  • Kim, Jong-Ryeol;Roh, Geon-Sang
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.13 no.4
    • /
    • pp.1427-1433
    • /
    • 2012
  • In this paper, cycle performance analysis of cascade refrigeration system using alternative FREON refrigerants and natural refrigerants are presented to offer the basic design data for the operating parameters of the system. The operating parameters considered in this study include subcooled and superheated degree, and condensing and evaporating temperature, temperature difference of cascade heat exchanger in cascade refrigeration system. The COP of cascade refrigeration system increases with the increasing subcooled degree, but there is no significant changes with the increasing superheated degree. The COP of cascade refrigeration system depends on evaporating and condensing temperatures of cascade heat exchanger. Therefore, subcooled degree, evaporating and condensing temperature of cascade heat exchanger using alternative FREON refrigerants and natural refrigerants have an effect on the COP of this system. In this paper, COP of cascade refrigeration system using (R23 / R290), (R23 / R600), (R23 / R600a), (R23 / R717), (R744 / R404A) are higher 20 ~ 36 % than (R23 / R22), using R23 for low temperature system and R22 for high temperature system.

Condensation Heat Transfer Coefficients of Binary Refrigerant Mixtures on Enhanced Tubes (열전달 촉진관에서 2원 혼합냉매의 외부 응축열전달계수)

  • 김경기;서강태;채순남;정동수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.2
    • /
    • pp.161-167
    • /
    • 2002
  • In this study, external condensation heat transfer coefficients (HTCs) of two non-azeotropic refrigerant mixtures of HFC32/HFC134a and HF0134a/HCF0123 at various compositions were measured on both low fin and Turbo-C enhanced tubes of 19.0 mm outside diameter All data were taken at the vapor temperature of 39$^{\circ}C$ with a wall subcooling of 3- 8 K. Test results showed that HTCs of the tested mixtures on the enhanced tubes were much lower than the ideal values calculated by the mass fraction weighting of the pure compo- nents'HTCs. Also the reduction of HTCs due to the diffusion vapor film was much larger than that of a plain tube. Unlike HTCs of pure fluids, HTCs of the mixtures measured on enhanced tubes increased as the wall subcooling increased, which was due to the sudden break up of the vapor diffusion film with an increase in wall subcooling. Finally, heat transfer enhancement ratios for mixtures were found to be much lower than those of pure fluids.

Pool Boiling Heat Transfer Correlation for Mixture Refrigerants (혼합냉매의 풀비등 열전달 상관식)

  • 고영환;김종곤;박진석;정동수;김영일
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.2
    • /
    • pp.122-133
    • /
    • 2001
  • Pool boiling heat transfer coefficients(HTCs) of HFC32/HFC134a, HFC125/HFC134a, HFC32/HFC125 and HFC32/HFC125/HFC134a were measured on a horizontal smooth tube. The experimental apparatus was specially designed to simulate the real heat transfer tube with the use of the secondary fluid of water. Data were taken in the order of decreasing heat flux starting at 80kW/$m^2\; and\; ending\; at\; 5kW/m^2$ in the pool temperature at $7^{\circ}C$. Test results showed that HTCs of these mixtures were 11~38% lower than those of ideal HTCs calculated by a linear mixing rule with pure fluids、 HTCs. Experimental data were compared with Stephan & Korner, Thome, Schlunder, Thome & Shakir、s correlations only to find that those correlations were not satisfactory for all fluids. Hence, a new correlation based on the present data was proposed which could be applied even to the ternary mixture. The correlation predicts the degradation of HTCs of mixtures well, showing a mean deviation of less than 15% for all the mixture data.

  • PDF

Performance analysis of 20 kW OTEC power cycle using various working fluids (다양한 작동유체를 이용한 20 kW급 해양온도차 발전 사이클 성능 분석)

  • Yoon, Jung In;Ye, Byung Hyo;Heo, Jung Ho;Kim, Hyun Ju;Lee, Ho Saeng;Son, Chang Hyo
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.37 no.8
    • /
    • pp.836-842
    • /
    • 2013
  • In this paper, the 20 kW Ocean Thermal Energy Conversion(OTEC) is newly proposed in order to select the refrigerant that makes the cycle performance be optimized and the performance of 20 kW OTEC applying 15 pure refrigerants and 16 mixed refrigerants is analyzed. The efficiency of system, the mass flow of working fluids and TPP, which is new concepts, are analyzed. In view of cycle efficiency, R32/R152a (87:13) is the highest efficiency among the refrigerants. At the mass flow of working fluid to make the 20 kW electricity, R717 is shown as the lowest value. And in view of TPP in this study, R32/R134a 70:30 is the most optimized refrigerant. The analysis can confirm that the refrigerant is different along with the part of the system, so it is necessary to select the optimized refrigerant for 20 kW OTEC.

Condensation Heat Transfer for Pure HFC Refrigerants and a Ternary Refrigerant Mixture Inside a Horizontal Tube (HFC 순수냉매 및 3성분 혼합냉매의 수평관내 응축열전달)

  • Oh, Jong-Taek;Hihara, Eiji
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.24 no.2
    • /
    • pp.233-240
    • /
    • 2000
  • An experimental study of condensation heat transfer was performed for pure refrigerants HFC32, HFCI25, and HFC134a, and a ternary refrigerant mixture of HFC32/125/134a (23/25/52wt%). The heat transfer coefficients were measured inside a horizontal smooth tube 5.8 mm I.D. and 8.0 m long. The refrigerant temperature at inlet was 40 $^{\circ}C$, and the mass flux was varied from 150 to 400 $kg/m^2s$. As for the pure refrigerants, the heat transfer coefficient of HFC32/125/l34a decreased as the quality decreased. In addition, the heat transfer coefficient of HFC32/l25/134a was about 20 % lower than HFC 134a at a low mass flux but showed no reduction at a high mass flux. The heat transfer coefficient of ternary refrigerant mixtures was 30% lower on the average than that of the pure refrigerant.