• 제목/요약/키워드: 협역수위제어

검색결과 2건 처리시간 0.017초

원자력발전소 증기발생기 수위제어를 위한 퍼지제어기법의 현장 제어기계에의 적용 (Implementation of Fuzzy Control Algorithm For Nuclear Power Plant Steam Generator Level Control At Field Controller)

  • 박기용;허우성;성풍현
    • 대한기계학회논문집
    • /
    • 제19권1호
    • /
    • pp.111-121
    • /
    • 1995
  • A fuzzy control algorithm of bell-type membership functions and 9 rules is constructed for narrow range level control of steam generators in nuclear power plants. It is implemented at a field digital distributed controller, a Westinghouse-made controller called Westinghouse Distributed Processing Family(WDPF). Performance for level control of the developed fuzzy controller is compared with that of conventional controller, both at the field controller. For these comparisons, both the fuzzy control algorithm and the conventional PI control algorithm were carefully tuned. Also the sampling time for optimal performance was investigated. The results show that the fuzzy control algorithm is not only better in performance than the conventional algorithm but also much easier to be tuned by operators in the field.

DCS-GRAPHIC 설계로 인한 원자력발전소 터빈운전원의 운전능력 향상

  • 박종범;양승권
    • 한국원자력학회:학술대회논문집
    • /
    • 한국원자력학회 1997년도 추계학술발표회논문집(1)
    • /
    • pp.401-406
    • /
    • 1997
  • 발전소 기동 및 저출력 운전시 원자력발전소(PWR) 터빈운전원(T/O)들은 증기발생기 수위제어를 위해 배전반(MCR)에 증기발생기 수위제어 관련 경험이 있는 운전원 3명 이상이 좁은 보드앞에서 각자 S/G A, B, C의 주요 파라미터들을 감시하며 수동운전하게 된다. 이렇게 운전원들이 많은 위험부담을 안고 수동운전하는 이유는 증기발생기 수위제어는 증기발생기 내부의 광역수위 측정범위가 약 14.2(m)이고, 주요 제어변수를 측정하는 협역수위는 약 3.2(m)로 매우 적어서 물의 Swell, Shrink 현상과 급수온도의 영향으로 제어하기 매우 어렵기 때문이다. 그러나 DCS(Distributed Control System)내의 한 부분인 공정감시제어를 위한 MMI(Man Machine Interface) Software를 사용하면 한사람이 증기발생기 수위제어 전 계통의 감시 및 제어가 가능하게 된다. 또한 과거나 현재의 변화 추이 및 문제점 분석은 물론, 계통의 결함 발생시 경보가 발생하여 경보발생 화면을 선택할 경우 어느 부분에서 결함이 발생했는지를 보여준다. 만약 이 화면을 운전원이 아닌 현장 Engineer가 보았을 경우는 결함부분의 확인 및 결함카드 보수가 가능하여 운전원들의 작업부담 감소와 이로 인한 다른 계통 점검 시간을 충분히 확보할 수 있다.

  • PDF