• 제목/요약/키워드: 캐스캐이드 냉동시스템

검색결과 3건 처리시간 0.013초

캐스캐이드 냉동시스템에서 냉매로서의 프로판-에탄 냉매의 성능 분석 (The Characteristic of Propane(R290)-Ethane(R170) as Refrigerant in the Cascade Refrigeration System)

  • 김필환;이병호;정효민;정한식;김철수
    • 동력기계공학회지
    • /
    • 제11권4호
    • /
    • pp.50-55
    • /
    • 2007
  • Nowadays, demands on super low temperature condition for industrial and commercial uses are thriving. Considering of its wide application in the present and the future, study of the super-low temperature refrigeration system should be actively carried out. This study is aimed to investigate refrigeration capacity and coefficient of performance(COP) of the cascade refrigeration system, as well as to get the system which can reach evaporator temperature of $-70^{\circ}C$. For this purpose, R290 and R170 are charged in high stage and low stage respectively. Finally the characteristics of system using R290 and R170 will be proposed. Additionally, In this experiment, the flow rate of air flowing through the LS evaporator and the compressor inlet pressure were varied to investigate the refrigeration capacity and coefficient of performance characteristics.

  • PDF

에탄을 사용한 2원 냉동 시스템의 성능 평가 (Study of Ethane Performance at Two-Stage Cascade Vapor Compression System)

  • 루비 라하디얀;김연근;정한식;정효민
    • 동력기계공학회지
    • /
    • 제10권2호
    • /
    • pp.75-82
    • /
    • 2006
  • 세계적인 환경 보호 정책에 따라 할로겐화탄소 냉매를 대체할 환경 친화적인 초저온 냉매의 개발과 연구가 활발히 진행되고 있다. 일반적으로 캐스캐이드 2원 냉동 시스템에서 아직까지 할로겐화탄소 냉매가 널리 사용되고 있다. 탄화수소 화합물의 한 종류인 에탄은 낮은 지구 온난화 지수와 낮은 오존층 파괴지수를 가진 친 환경적인 자연 냉매이다. 본 연구는 지구 온난화 지수가 높은 R-23 냉매와 비교하여 캐스캐이드 2원 냉동 시스템에서 에탄의 성능 시험을 목적으로 수행 하였다. 1원측에는 R-22를 사용하였으며, 증발 온도에 따른 성능은 R-23 보다 에탄(R-170)이 더 높게 나타났다.

  • PDF