• Title/Summary/Keyword: 캐비테이션 서지

Search Result 1, Processing Time 0.015 seconds

Experimental Study on Cavitation Instability of a Solution Pump Inducer in an Absorption Chiller-Heater (흡수식 냉온수기내 용액펌프 Inducer의 Cavitation 불안정성에 대한 실험적 연구)

  • Seo, Min;Lee, Kyung-Hoon;Kang, Shin-Hyung
    • Proceedings of the KSME Conference
    • /
    • 2008.11b
    • /
    • pp.2434-2439
    • /
    • 2008
  • This paper was studied on the cavitation instability of a Solution Pump Inducer in an absorption chiller-heater. Inlet pressure of LiBr and rotational speed at nominal mode are 2,800 Pa and 3,500 rpm respectively. Due to the marginal operation of available NPSH, the cavitation performance of the inducer is critical for the stable operation without the deterioration of head performance. In the study, cavitation performance and its mode of instability was investigated experimentally. Water was used as the working fluid and the test inducer was scaled up as 1.75 times for detail measurements and flow visualization. Inlet pressure was controlled by a vacuum pump. This research focused on types of cavitation instability and phenomena to investigate the possibility of harmful damage due to cavitation instability. Casing wall pressure and instantaneous inlet pressure was measured to observe the unsteady flow characteristics. Through the visualization and spectrum analysis of pressure, the occurrence region and intensity of asymmetric cavitation and cavitation surge are analyzed in the test inducer.

  • PDF