• Title/Summary/Keyword: 충진층식 세정집진기

Search Result 1, Processing Time 0.015 seconds

An Experiment on the Particle Collection Characteristics in a Packed Wet Scrubber (충진층식 세정집진기의 집진특성 실험)

  • 유경훈;노희환;최은수;김종균
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.4
    • /
    • pp.305-311
    • /
    • 2003
  • DOP aerosol particles with geometric mean diameter of 0.5-3.0 ${\mu}{\textrm}{m}$, geometric standard deviation of 1.1-1.3 and total number concentration of 1,500-8,000 Particles/㎤ were used to determine collection efficiencies of a packed wet scrubber with respect to particle size. The tested operating variables included air velocity and water injection rate. It was shown from the experimental results that the collection efficiencies increased with increasing water injection rate and decreasing air velocity. Meanwhile, as for the particle size variation, all of the collection efficiency curves increased rapidly between 0.57-1.41${\mu}{\textrm}{m}$ for the range of water injection rate above 30 L/min. It was also seen that the collection efficiency of a packed wet scrubber is mainly governed by the mechanism of inertial impaction.