Investigation and Estimation of Transformer Load Factor for Rationalization of Transformer's Efficiency (변압기 효율 적정화를 위한 변압기 부하율 조사 및 추정)

  • Kim, Chong-Min;Kim, Young-Seog;Gil, Hyoung-Jun;Shong, Kil-Mok
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.30 no.1
    • /
    • pp.96-101
    • /
    • 2016
  • In this paper, We investigate the number of 795 transformer in the private electrical facilities and analyze the annual load factor. The results show that the annual load factor of transformer is 20.16% in manufacturing industry, education services(school) is 9.59%, retail and wholesale services is 19.68%, resort and leisure industry is 10.93%, office building is 13.10%, and apartment houses is 14.69%. Education services, resort and leisure industry are being operated with a very low annual load factor. The relatively small capacity of less than 500kVA transformer also been analyzed that is being operated with a low load factor. Therefore, In order to minimize the power loss of the transformer, it is advisable to complement the Transformer Efficiency Management system to be designed the efficiency is good transformer when the load is low. Analysis results will be used as the basis for the provision of transformer efficiency management system and be used High-efficiency transformers promotion system.

Load current and Temperature measurement system for Measuring the Degradation of Power cable (전력케이블의 열화측정을 위한 부하전류 및 온도측정 시스템)

  • Park, Yong-Kyu;Cho, Young-Seek;Lee, Kwan-Woo;Um, Kee-Hong;Park, Dae-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.2
    • /
    • pp.69-74
    • /
    • 2015
  • Recently, there has been a surge in interest in equipment diagnosis and monitoring technology from the perspective of providing quality electricity in terms of reliability and safety. In order to meet the electrical demands of consumers, reliability of power supply needs to be maintained. For this purpose, a monitoring system for power cable is very important. Since real-time measuring equipment has many advantages, it is highly applicable. By measuring the load current and the surface temperature of power cables, we have monitored and identified the deterioration phenomena of power cables in operation. Since direct measurement of the cable conductor temperature is not easy, we have measured the surface temperature instead, and converted that temperature to obtain the conductor temperature of the cables. In addition, we have designed a system to detect the deterioration processes of the power cables in operation.

Development of Heating and Cooling System with New Heat Exchange Cycle for High Efficiency and Peak Power Reduction Using Real time Constant Refrigerant Pressure Control (실시간 일정압력 제어기술을 적용한 냉난방장치의 피크부하 저감과 에너지 효율 향상을 위한 시스템 개발)

  • Choi, Sun-Young;Lee, Young-Kug;Choi, Myeong-Gwang;Choi, Tae-Won
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.11
    • /
    • pp.53-58
    • /
    • 2015
  • Systemic heating and cooling air conditioning systems are popular in various industrial fields and even home. Recently, the rate of supply of this kind of multi-heat pump has been increased under ESCO financing supporting system. Generally the heat pumping system has a structural simplicity and easy installation benefits. and has good running efficiency under normal designed condition. But under extreme climate condition (over $+30^{\circ}C$, under $-10^{\circ}C$), this system exposes abnormal power consumption. It causes high progressive electric power rates and resultant peak power capacity of power plant. In this paper, a novel system concept of buffering refrigerant accumulator and constant pressure control system to relieve peak power load is proposed and this system's utility is verified with an prototype experimental system.

A Study on the Application of the DVR in AC Electric Traction System (전기철도계통에 순간전압강하 보상장치 적용에 관한 연구)

  • 최준호;김태수;김재철;문승일;남해곤;정일엽;박성우
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.6
    • /
    • pp.95-104
    • /
    • 2003
  • The electric traction systems are quite differ from general power systems which is single-phase and heavy load. Therefore, there are inevitably power quality problems such as steady state or transient voltage drop, voltage imbalance and harmonic distortion. Among these problems, since steady-state volatge drop is the one of most important factor in electric power quality, many researches about on the compensation of volatge drop by using SVC(Static Var Compensator) and/or STACOM(Static Compensator) have been studied and proposed Also, it is expected that transient voltage drop(voltage sag) could affect the control and safety of high speed traction load. In this paper, voltage sag compensation of AT(Auto Transformer) feeding system are studied The detailed transient models of utility source, scott transformer, AT, and traction load are estabilished. The application of DVR(Dynamic Voltage Restorer) in electric traction system is proposed to compensate the voltage sag of traction network which is occured by the fault of utility source. It can be shown that application of the DVR in electric traction system is very useful to compensate the volatge sag from the result of related simulation works.

The 3-Phase Induction Motor Speed Control by the MRA-DSM controller (MRA-DSM 제어기를 이용한 3상 유도전동기의 속도 제어)

  • 원영진;한완옥;박진홍;이종규;이성백
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.9 no.1
    • /
    • pp.54-62
    • /
    • 1995
  • This paper is a study on a speed control of an induction motor used the MRA-DSM(Mode1 Reference Adaptive-Discrete Sliding Mode) controller. In this paper, when controls motor speed, DSM algorithm is proposed for having Robustness against disturbance and parameter variation. and it is also proposed MRA-DSM including the additional load model reference algorithm, which can be compensated the discontinuous control imputs at sliding mode and followed the model Preference independent of parameter variation of control subjects. The control system is composed of the parallel processing control system using the microprocessor for maximizing the performance of control systems and the real time processing. Also it simplifies the hardware composed of controlling the system by software and improves the reliability of the system. And while MRA-DSM control, faster response characteristics of 27.2 % is obtained than DSM control.

  • PDF

A Study on The MRA PWM Technique Using the Trapezoidal Waveform at Voltage Source Inverter(VSDI) (전압형 인버터(VSI)에서 사다리꼴파형을 이용한 MRA PWM 기법에 관한 연구)

  • 한완옥;원영진;이성백
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.7 no.2
    • /
    • pp.36-40
    • /
    • 1993
  • In order to improve complicated construction and complex control which are disadvantage of optimal PWM technique aimed at harmonic elimination method, this paper presented MRA(Model Reference Adaptive) PWM technique that gatmg signal of inverter is generated by comparing the reference signal with the induced feedback signal at the reference model of load. Design of controller is composed of microprocessor and analog circuit. MRA PWM technique used in the paper is able to compensate the degradation of voltage efficiency to be generated by the ratio of the output voltage to the DC supply voltage being low for using conventional sinusoidal PWM technique. When the trapezoidal signal is employed as the reference signal. the low order harmonics of line current can be reduced and the switching pattern is made by on-line computation using comparatively simple numerical analysis.

  • PDF

Optimum Operation of Power System Using Fuzzy Linear Programming (퍼지 선형계획법을 적용한 전력계통의 최적운용에 관한 연구)

  • 박성대;정재길;조양행
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.8 no.1
    • /
    • pp.37-45
    • /
    • 1994
  • A method of optimal active and reactive power control for economic operation in electrical power system is presented in this paper. The major features and techniques of this paper are as follows: 1) The method presented for obtaining the equivalent active power balance equation applying the sparse Jacobian matrix of power flow equation instead of using B constant as active power Balance equation considering transmission loss, and for determining directly optimal active power allocation without repeating calculations. 2) More reasonable and economic profit by minimizing total fuel cost of thermal power plants instead of using transmission loss as objective function of reactive Power control can be achieved. 3) Particularly in reactive power control, computing time can be considerably reduced by using Fuzzy Linear Programming instead of using conventional Linear Programming.

  • PDF

A Real-Time RPWM Inverter for Reduction of Switching Frequency Band Noise in the Induction Motor (유도전동기의 스위칭 주파수대 소음 저감을 위한 실시간 RPWM 인버터)

  • 나석환;최창률;양승학;김광헌;임영철;박종건
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.11 no.6
    • /
    • pp.64-73
    • /
    • 1997
  • RPWM(Random Pulse Width Modulation) techniques have been attracting an interest as an excellent reduction method of acoustic noise on the inverter drive system. Using randomly changed switching fre-quency of the inverter, the power spectrum of the electromagnetic acoustic noise can be spread out into the wide-band area. The wide band noise is much more comfortable and less annoying than the narrow-band one. This paper describes an implementationof the triangular carrier frequency modultde RPWM inverter drive system The poweer soedtrum of the noise emittde from the induction motro was measured in the anechoic chamber. The analysis of the sources for the acoustic noise and the effects of the noise reduction are confirmed by the ceasured dpectra of the noise. Real-time RPWM along with the speed control was achieved by high speed DSP(Digital Signal Processor ) TmS320C31, By changing the center frequency and the bandwidth of the carrier, theis real-time RPWM scheme can be used as an efficient switching frequency band acoustic noise reduction method for the inverter system with variant load conditions.

  • PDF

200[W] Half-Bridge LLC Series Resonant Converter for driving LED Lamp (LED 조명장치 구동용 200[W]급 하프브리지 LLC 직렬공진형 컨버터)

  • Han, Woo-Yong;Park, Hyo-Sik
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.11 no.11
    • /
    • pp.4483-4488
    • /
    • 2010
  • In comparison with some other light sources, LED has merits such as long lifetime, pollution free, and high energy efficiency. Lately, due to development of LED with high brightness and capacity, LED, which has been applied in display system only, has applied in the field of lighting system. Driving current of power LED has to be controlled below the designed value. In this paper, half-bridge LLC series resonant converter, which has the current limiting function, has been described. Half-bridge LLC series resonant converter allows in relatively wide input voltage and output load range when compared to the other resonant converter. Also, it is possible to reduce a magnetic component, because leakage inductance of transformer is used as a resonant inductance. It has been validated by designing and testing 200[W] half-bridge LLC converter of DC24[V] output voltage for LED lamp driver, which includes a current limiting function and power factor correction(PFC) function.

Short-term Power Load Forecasting using Time Pattern for u-City Application (u-City응용에서의 시간 패턴을 이용한 단기 전력 부하 예측)

  • Park, Seong-Seung;Shon, Ho-Sun;Lee, Dong-Gyu;Ji, Eun-Mi;Kim, Hi-Seok;Ryu, Keun-Ho
    • Journal of Korea Spatial Information System Society
    • /
    • v.11 no.2
    • /
    • pp.177-181
    • /
    • 2009
  • Developing u-Public facilities for application u-City is to combine both the state-of-the art of the construction and ubiquitous computing and must be flexibly comprised of the facilities for the basic service of the building such as air conditioning, heating, lighting and electric equipments to materialize a new format of spatial planning and the public facilities inside or outside. Accordingly, in this paper we suggested the time pattern system for predicting the most basic power system loads for the basic service. To application the tim e pattern we applied SOM algorithm and k-means method and then clustered the data each weekday and each time respectively. The performance evaluation results of suggestion system showed that the forecasting system better the ARIMA model than the exponential smoothing method. It has been assumed that the plan for power supply depending on demand and system operation could be performed efficiently by means of using such power load forecasting.

  • PDF