• 제목/요약/키워드: 정풍량댐퍼

검색결과 4건 처리시간 0.015초

원형 CAV 댐퍼의 개발에 관한 연구 (A Study on the Development of a Circular CAV Damper)

  • 권영필
    • 설비공학논문집
    • /
    • 제25권11호
    • /
    • pp.612-616
    • /
    • 2013
  • A circular CAV damper has been developed, based on the investigation of the pressure loss, and the flow-resisting moment by the damper blade. When a torsional spring is attached to the damper axle, and the setting angle is adjusted to around $82^{\circ}$, the volume rate across the damper is almost independent of the static pressure. Such a CAV characteristic appears at an opening angle between $40^{\circ}$ and $60^{\circ}$, where the normalized moment decreases linearly with the angle. In addition, by adjusting the setting angle, the volume rate can be controlled to within 10% error, regardless of the pressure loss.

정풍량방식 덕트에서 이중압력측정방법을 이용한 취출구 풍량조정 (Balancing air flow at terminal in CAV duct system with DPM method)

  • 이대우;박명식;박영우
    • 설비공학논문집
    • /
    • 제10권1호
    • /
    • pp.66-78
    • /
    • 1998
  • Adequate ventilation with the proper amount of air to the right place is important factor to achieve a good Indoor air climate. Thus it is of prime importance that the ventilation system is working properly. This requires reliable pressure loss calculation to balance the air flow through duct systems. So a computer program for balancing CAV duct system is developed In this study. The results of CAV duct system is compared with the "Balans" code developed by Larsen from Norway. To obtain the pressure drop characteristics of damper at duct terminal, some experiments are performed using DPM(Dual Pressure Measurement) system. To adjust the resistance of damper, present study suggests that some special diffusers should be designed and damper producers should give the data of air flow vs. pressure drop to the customs when they manufacture the damper. One of the results concludes that the working time can be reduced from several minutes to several seconds per damper in the present experimental site, if the DPM system and the air volume adjusting process are used.

  • PDF

공동주택의 세대별 균등 배기량을 확보 하는 제어방법에 관한 연구 (Control Method to Ensure Uniform Exhaust Function by Household of Apartment House)

  • 권용일
    • 설비공학논문집
    • /
    • 제29권12호
    • /
    • pp.628-637
    • /
    • 2017
  • This study was conducted to present an effective control method for the common duct system to uniformly discharge volume flow rate exhausted from the kitchen and bathroom of each household in an apartment regardless of the position of household. Since the common duct system is installed vertically and the ventilator is installed in the terminal, the static pressure of each household decreases when vertical height increases. Therefore, the volume flow rate exhausted from each household is different. In order to improve such a phenomenon, a constant air volume damper shall be installed in a branch duct coupled with a common vertical duct system. The selected ventilator should also be able to handle the maximum volume flow rate considering diversity factor. Therefore, a uniform volume flow rate must be exhausted from all households where the hood is operated. This paper mainly focuses on suggestion of an optimum exhaust control method by comparing exhaust performance of each household according to the presence or absence of a constant air volume damper.

실물실험에 의한 순환공기 바이패스 공조시스템의 성능분석 (The Performance Analysis of a Return Air Bypass Air Conditioning System by a Simulator Experiment)

  • 신현준;김보철;김정엽
    • 에너지공학
    • /
    • 제11권2호
    • /
    • pp.130-135
    • /
    • 2002
  • 바이패스 공조시스템은 냉각코일과 가열코일의 공기통과여부에 따라 크게 외기바이패스, 혼합공기 바이패스와 순환공기 바이패스 공조시스템으로 구분할 수 있다. 이 중에서 순환공기 바이패스 공조시스템은 다른 두 방식과 달리 공조되지 않은 외기가 시스템 내부로 직접 유입되지 않으므로 실내온습도 조절면에서 가장 효율적인 시스템이다. 먼저, 수치계산을 통하여 부하변동에 따른 순환공기 바이패스 공조시스템과 단일덕트 정풍량공조시스템의 실내온습도 구현능력을 비교, 평가하였다. 또한 제안 시스템의 성능분석을 위해 실물실험동을 건립하여 그 실험결과를 수치계산결과와 비교하였다. 실험을 통하여 실현열비가 0.7(현열부하만 변동)인 경우, 실내 최대현열부하에 대한 부분부하시의 실내 현열부하의 비(DSL; Design Sensible Load)가 70% 이내에서는 수치계산, simulator 실험 모두 실내상대습도는 ASHRAE STANDARD 62-1999에서 지정하는 60% 이하로 유지됨을 알 수 있었다. 결론적으로, 바이패스 공조시스템은 실내의 온습도를 정해진 범위의 부하변동내에서는 바이패스 댐퍼의 조작만으로 쾌적한 상태로 유지시킬 수 있으며, 환기회수가 많은 장손의 경우, 순환공기 바이패스에 의해 양질의 실내공기질(IAQ; Indoor Air qualify)을 확보할 수 있다.