• Title/Summary/Keyword: 전자팽창밸브 제어알고리즘

Search Result 5, Processing Time 0.019 seconds

Control of Compressors and Electronic Expansion Valve considering the Safe Operation of a Tandem-type Air-conditioning system (텐덤형 냉방시스템의 안전운전을 고려한 압축기와 전자팽창밸브 제어)

  • Han, Do-Young;Kim, Jae-Hyun
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.675-680
    • /
    • 2006
  • Capacities of a tandem-type air-conditioner may be modulated by turning on and off of multiple compressors, and adjusting the position of a electronic expansion valve. In this study, control algorithms for compressors and a electronic expansion valve were developed by using fuzzy logics. The pressure control algorithm was also developed for the safe operation of compressors. There algorithms were implemented in a test lab and proved to be effective for the control of indoor air temperature and superheat temperature,

  • PDF

Control of Compressor and Electronic Expansion Valve for a Tandom-type Air-conditioner (텐덤형 냉방시스템의 압축기와 전자팽창밸브 제어)

  • Jung, Nam-Chul;Han, Do-Young
    • Proceedings of the SAREK Conference
    • /
    • 2005.11a
    • /
    • pp.469-473
    • /
    • 2005
  • Capacities of a tandom-type air-conditioner may be modulated by turning on/off multiple compressors and adjusting positions of a electronic expansion valve. In this study. control algorithms for compressors and a electronic expansion valve were developed by using fuzzy’ logics. There algorithms were implemented in a test lab and proved to be effective for the control of indoor air temperature and superheat temperature.

  • PDF

The EEV Control of the Multi-type Air-conditioning System by using a Fuzzy Logic Superheat Temperature Setpoint Reset Algorithm (퍼지로직 과열도 재설정 알고리즘을 사용한 멀티형 냉방시스템의 전자팽창밸브 제어)

  • 한도영;이상원
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.5
    • /
    • pp.382-388
    • /
    • 2003
  • Refrigerant flow rates of the multi-type air-conditioning system can be regulated by electronic expansion valves (EEV). The performance of the multi-type air-conditioning system may be improved by lowering the superheat at the compressor suction side. In this study, a superheat temperature setpoint reset algorithm was developed by using fuzzy logics, and a PI algorithm was applied to control the superheat temperature near setpoints. Experimental results showed energy savings and stable operations at a multi-type air-conditioning system. Therefore, the developed setpoint reset algorithm may be effectively used for the EEV superheat temperature control of the multi-type air-conditioning system.

Fuzzy Control Algorithms for the Compressor and the Electronic Expansion Valve of a Multi-type Air-conditioning System using Multiple Input Variables (다입력변수를 사용한 멀티형 공조시스템 압축기와 전자팽창밸브의 퍼지 제어 알고리즘)

  • Han, Do-Young;Park, Kwan-Jun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.2
    • /
    • pp.163-171
    • /
    • 2006
  • In order to control multi-zone temperatures, a multi-type air-conditioning system may be used. In this study, control algorithms for the compressor and the electronic expansion valve of a multi-type air-conditioning system were developed by using fuzzy logics. The compressor control algorithm was composed of a compressor pressure setpoint algorithm, a compressor pressure setpoint reset algorithm, and a compressor frequency setpoint algorithm. The electronic expansion valve control algorithm was composed of an indoor temperature control algorithm, and a superheat control algorithm. These algorithms were applied to a multi-type air-conditioning system. Test showed good results for the control of a multi-type air-conditioning system.

EEV Superheat Control of a Multi-type Heat Pump by Using Dither Signal (멀티형 히트펌프 전자팽창밸브의 디더 신호를 적용한 과열도 제어)

  • 한도영;표수환
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.11
    • /
    • pp.948-953
    • /
    • 2002
  • The electronic expansion valve (EEV) may be used to control the refrigerant flow rate for the multi-type heat pump. Stepping motor driven EEV may precisely control the refrigerant flow rate to meet each internal load requirement. To control the EEV, PI algorithm may be used. But the hysteresis of EEV deteriorates the performance of superheat control. To reduce the performance degradation, the PI algorithm along with the dither signal may be used. The dither signal, with about 10 times higher frequency than the system crossover frequency and about 10 times larger magnitude than the deadband of hysteresis, was selected for the superheat control of EEV. Experimental results showed the improvement of EEV control by adding the dither signal to the PI algorithm.