• Title/Summary/Keyword: 응축기오염

Search Result 12, Processing Time 0.035 seconds

CFD Analysis to Suppress Condensate Water Generated in Gas Sampling System of HANARO (하나로 기체시료채취계통에서 생성된 응축수 억제를 위한 CFD 해석)

  • Cho, SungHwan;Lee, JongHyeon;Kim, DaeYoung
    • Journal of Nuclear Fuel Cycle and Waste Technology(JNFCWT)
    • /
    • v.18 no.2_spc
    • /
    • pp.327-336
    • /
    • 2020
  • The high-flux advanced neutron application reactor (HANARO) is a research reactor with thermal power of 30 MW applied in various research and development using neutrons generated from uranium fission chain reaction. A degasifier tank is installed in the ancillary facility of HANARO. This facility generates gas pollutants produced owing to internal environmental factors. The degasifier tank is designed to maintain the gas contaminants below acceptable levels and is monitored using an analyzer in the gas sampling panel. If condensate water is generated and flows into the analyzer of the gas sampling panel, corrosion occurs inside the analyzer's measurement chamber, which causes failure. Condensate water is generated because of the temperature difference between the degasifier tank and analyzer when the gas flows into the analyzer. A heating system is installed between the degasifier tank and gas sampling panel to suppress condensate water generation and effectively remove the condensate water inside the system. In this study, we investigated the efficiency of the heating system. In addition, the variations in the pipe temperature and the amount of average condensate water were modeled using a wall condensation model based on the changes in the fluid inlet temperature, outside air temperature, and heating cable-setting temperature.

The Fault Detection of an Air-Conditioning System by Using a Residual Input RBF Neural Network (잔차입력 RBF 신경망을 사용한 냉방기 고장검출 알고리즘)

  • Han, Do-Young;Ryoo, Byoung-Jin
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.8
    • /
    • pp.780-788
    • /
    • 2005
  • Two different types of algorithms were developed and applied to detect the partial faults of a multi-type air conditioning system. Partial faults include the compressor valve leakage, the refrigerant pipe partial blockage, the condenser fouling, and the evaporator fouling. The first algorithm was developed by using mathematical models and parity relations, and the second algorithm was developed by using mathematical models and a RBF neural network. Test results showed that the second algorithm was better than the first algorithm in detecting various partial faults of the system. Therefore, the algorithm developed by using mathematical models and a RBF neural network may be used for the detection of partial faults of an air-conditioning system.

Fault Diagnosis Algorithm of an Air-conditioning System by using a Neural No-fault Model and a Dual Fuzzy Logic (신경망무고장모델과 이중퍼지로직을 사용한 냉방기 고장진단 알고리즘)

  • Han Do-Young;Jung Nam-Chul
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.10
    • /
    • pp.791-799
    • /
    • 2006
  • The fault diagnosis technologies may be applied in order to decrease the energy consumption and the maintenance cost of an air-conditioning system. In this paper, a fault diagnosis algorithm was developed by using a neural no-fault model and a dual fuzzy logic. Five different faults, such as the compressor valve leakage, the liquid line blockage, the condenser fouling, the evaporator fouling, and the refrigerant leakage of an air-conditioning system, were considered. The fault diagnosis algorithm was tested by using a fault simulation facility. Test results showed that the algorithm developed for this study was effective to detect and diagnose various faults. Therefore, this algorithm may be practically used for the fault diagnosis of an air-conditioning system.

IRWST 배관내의 열수력적 현상 모델링

  • 김상녕;김융석;고종현
    • Proceedings of the Korean Nuclear Society Conference
    • /
    • 1998.05a
    • /
    • pp.596-602
    • /
    • 1998
  • 한국의 차세대 원자로 (Korean Next Generation Reactor; KNGR)에 처음 적용되는 격납건물내에 설치된 재장전수조 (In-Containment Refueling Water Storage Tank; IRWST)는 기존 재장전수조의 기능외에 주입모드에서 재순환 모드를 전환생략, 일차계통으로 방출된 고온, 고압 냉각수의 응축 및 냉각 격납용기 방사능 오염방지, 원자로 동공층수 등 여러 가지 추가 기능을 가진 한층 진보된 설계개념이다. 발전소 천이사고 시 발생하는 Pipe Clearing, 응축진동 현상(Condensation Oscillations), Chugging 등의 열수력 현상들이 방출증기의 유동 및 가속도와 관련해 항력과 응력, 압력진동 등을 일으켜 IRWST 구조물에 영향을 미칠 수 있기 때문에 IRWST를 처음으로 시도하는 우리 나라로서는 이와 관련된 제반현상에 대한 심도 깊은 연구가 요구된다. 따라서 본 연구에서는 원자력 발전소 과도로 인한 가압기 안전밸브(Pressurizer Safety Valve) 또는 안전감압밸브(Safety Depressurization Valve) 작동시 IRWST로 방출되는 유체로 야기되는 하중 예측 모델을 기존의 BWR의 응축수조(suppression Pool)에서 일어나는 각종 현상을 토대로 이론적으로 체계적으로 유도하여 이를 비교, 분석하였다.

  • PDF

반도체 및 Optic Industries 클린룸 배기가스의 오염제어 및 청정화기술

  • 황유성
    • Air Cleaning Technology
    • /
    • v.17 no.4 s.67
    • /
    • pp.39-57
    • /
    • 2004
  • 첨단산업으로 불리는 반도체, LCD, PDP, 유기EL(OLED) 등의 생산 공정은 고도의 청정상태를 요구하며, 때문에 이들의 생산공정 중 대부분이 클린룸 내에서 이루어진다. 클린룸 내에서의 주요공정은 크게 박막형성(Layering), 노광(Photo Lithography), 식각(Etching) 등 3가지 공정으로 나눌 수 있으며, 반도체 제조공정의 경우 특별히 도핑(Doping) 공정이 추가된다. 오염물질을 함유하는 클린룸 배기는 일반적으로 산, 알칼리, Toxic(PFCs, Flammable), VOC 등으로 분류하며, 각각의 배기는 각 배기특성에 맞는 오염제어 장치를 통해, 정화된 후, 대기로 방출된다. 산, 알칼리 배기는 일반적으로 최종 단계에서 중앙집중식 습식스크러버에 의해 흡수, 중화 처리되며, VOC의 경우 농축기(Concentrator) & 축열식 열 산화장치(RTO) 설비에 의해 연소 처리된다. 하지만 CVD공정으로부터의 배기가 주를 이루는 Toxic배기의 경우, 다량의 PFCs(과불소화합물) 가스를 함유하고 있는 이유로, 대부분 클린룸 내부에 P.O.U(Point of use) 처리장치가 설치되며, P.O.U에 의해 1차 처리된 후 최종적으로 중앙집중식 습식스크러버를 거쳐 대기로 방출된다. 알칼리배기의 주성분으로는 암모니아($NH_3$), HMDS (Hexa Methyl DiSilazane), TMAH (Tetra Methyl Ammonium Hydroxide), LGL, CD 등이며 흡수액에 황산(Sulfuric Acid)용액을 공급, 중화처리하고 있다. 탄소성분을 먹이로 하는 미생물의 번식에 의한 막힘 문제를 제외하고는 큰 문제가 없다. 하지만 Toxic배기 및 산배기의 경우 처리효율이, 가스흡수 이론에 의한 계산결과와 비교할 때, 매우 저조하게 나타나는 효율부족 현상을 겪고 있으며, 이는 잔여 PFCs 가스성분 및 반응에어로졸, 응축에어로졸 등의 영향으로 추정하고 있다. 최근 Toxic 배기의 경우, P.O.U 설비를 Burn & Wet type으로 변경하여, 배기 중 PFCs 및 반응에 에어로졸($SiO_2$)의 농도를 원천적으로 감소시키는 노력이 진행 중이다. 산배기의 경우, 산결로 현상에 의한, 응축에어로졸이 문제가 되고 있으나 내식열교환기(Anti-Corrosive Heat Exchanger), 하전액적스크러버 시스템(Charged Droplets Scrubber System), Wet ESP(Wet Electrostatic Procipitator) 등의 도입을 통해 문제해결을 위한 노력을 경주하고 있다.

  • PDF

Partial Fault Detection of Air-conditioning System by Neural Network Algorithm using Data Preprocessing Method (데이터 전처리기법을 적용한 신경망 알고리즘의 냉방기 부분고장 검출)

  • 한도영;이한홍;윤태훈
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.7
    • /
    • pp.560-566
    • /
    • 2002
  • The fault detection and diagnosis technology may be applied in order to decrease the energy consumption and the maintenance cost of the air-conditioning system. In this study, two different types of faults in the air-conditioning system, such as the condenser fouling and the evaporator fan slowdown, were considered. The neural network algorithm combined with data preprocessor was developed and applied to detect the faults of the real system. Test results show that this method is very effective to detect the faults in the air-conditioning system. Therefore, this developed method can be used for the development of the air-conditioner fault detection system.

The Partial Fault Detection of an hir-Conditioning System by the Neural Network Algorithm using Normalized Input Data (정규화 입력을 사용한 신경망 알고리즘에 의한 냉동기의 부분 고장 검출)

  • 한도영;황정욱
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.3
    • /
    • pp.159-165
    • /
    • 2003
  • The fault detection and diagnosis technology may be applied in order to decrease the energy consumption and the maintenance cost of the air-conditioning system. To detect partial faults of the air-conditioning system, a neural network algorithm may be used. In this study, the neural network algorithm using normalized input data by the standard deviation was applied. And the [7$\times$10$\times$10$\times$1] neural network structure was selected. Test results showed that the neural network algorithm using normalized input data was very effective to detect the condenser fouling and the evaporator fan fault of an air-conditioning system.

Characteristics of the Air Heat Exchanger for the Improvement of the Heat Pump COP (열펌프 성능향상을 위한 공기 열교환기 특성)

  • 노정근;송현갑;박용규
    • Proceedings of the Korean Society for Agricultural Machinery Conference
    • /
    • 2002.02a
    • /
    • pp.151-157
    • /
    • 2002
  • 화석에너지에 대한 경제적 부담과 환경오염문제를 줄이기 위하여 열펌프의 성능계수향상을 위하여 냉온 공기열교환기(HEEVA)를 고안하였고, 이 열교환기의 열특성과 성능계수향상에 미치는 영향을 분석하기 위하여 냉.난방 실험을 수행하였다. HEEVA에 의한 찬 공기와 더운 공기의 온도변화, 전열량 및 냉온 공기열교환기 효율, 총열전달계수등을 측정분석하였고, 냉난방시 외기온에 따른 열펌프의 성능계수, 소비전력, 응축기.증발기 출구 공기토출 온도 변화를 측정 분석함으로서 다음과 같은 결과를 얻을 수 있었다. 1. 외기온이 -4~11$^{\circ}C$로 변할 때 열펌프의 난방과정에서 HEEVA 찬공기 입출구 온도차는 4.5$^{\circ}C$에서 9.$0^{\circ}C$로 증가하였으며, HEEVA에 의한 영향으로 2~6$^{\circ}C$상승된 공기가 증발기 입구로 유입되어 냉매증발을 촉진하였다. 2. 실온이 4~22$^{\circ}C$일 때 HEEVA 더운공기 입출구 온도차는 3$^{\circ}C$에서 7$^{\circ}C$로 증가하였으며, 응축기에 유입되는 공기온도를 3~8$^{\circ}C$낮게 함으로서 압축기 소모전력을 감소시켜 COP 상승 효과를 나타냈다. 3. 외기온과 실온변화에 따라 풍량 346m$^3$/hr의 찬 공기가 받은 열량과 풍량 747m$^3$/hr의 더운 공기가 준 열량간의 차는 50~150kcal/hr로 나타났으며, 더운 공기가 준열량과 찬 공기가 받은 열량의 비가 83~98% 이었으므로 HEEVA의 열 교환율은 91% 을 보였다. 4. 총합열전달계수는 이론값이 실험 값보다 1~3W/m$^2$K 크게 나타났으며, 이 결과는 두 값 사이에 10% 내.외의 편차로서 Nusselt수를 구하기 위한 Petukhov상관식의 자체오차 15%에 비해 크지 않은 오차범주에 속하며, 이론상의 총합열전달계수 유도식의 타당성을 입증한 것이라 하겠다. 5. HEEVA를 작동함으로서 난방시 COP가 HEEVA를 작동하지 않았을 경우보다 0.3~0.5 향상된 것으로 나타났다. 이것은 HEEVA가 겨울철 난방에 효율을 높일수 있는 것으로 판단된다.

  • PDF

Simultaneous Removal of SOx and NOx in Flue Gas of Oxy-fuel Combustion by Direct Contact Condenser (직접접촉식 응축기를 통한 가압순산소 연소 배가스 내 SOx, NOx 동시저감 연구)

  • Choi, Solbi;Mock, Chinsung;Yang, Won;Ryu, Changkook;Choi, Seuk-Cheon
    • Clean Technology
    • /
    • v.25 no.3
    • /
    • pp.245-255
    • /
    • 2019
  • Pressurized oxy-fuel combustion is a promising technology for $CO_2$ capture with a benefit of improving power plant efficiency compared with atmospheric oxy-fuel combustion. Prior to $CO_2$ compression in this process, a flue gas condenser (FGC) is used to remove $H_2O$ while recovering the latent heat. At the same time, the FGC has a potential for high-efficiency removal of $SO_x$ and $NO_x$ by exploiting their good solubility in water. In this study, experiments were carried out in a lab-scale, direct contact FGC under different pressures varying between 1 and 20 bar to evaluate the removal efficiency of $SO_2$ and $NO_x$ for individual gases and their mixture. In the tests for individual gases, 20% and 76% of $NO_x$ was removed at 1 bar and 10 bar, respectively. Even higher removal efficiencies were achieved for $SO_2$, and also these were maintained for longer as the pressure increased. In the tests for $SO_2$ and $NO_x$ mixture, the removal efficiency of $NO_x$ increased from 13% at 1 bar to 56% at 20 bar because of higher solubility at elevated pressures. $SO_2$ in the mixture was initially dissolved almost completely and then increased by 1,219 ppm at 1 bar and by 165 ppm at 20 bar. Overall, the removal efficiency of $SO_2$ and $NO_x$ was increased at elevated pressures, but it was lower in the mixture compared with individual gases at identical conditions because of a lower pH and associated chemical reactions in water.

Development of Volatile Organic Compound Pretreatment Device for Removing Exhaust Gas from Display Manufacturing Process (Display 제조공정 배출가스 처리를 위한 휘발성 유기화합물 전처리 장치 개발)

  • Moon, Gi-Hak;Kim, Jae-Yong
    • Applied Chemistry for Engineering
    • /
    • v.30 no.5
    • /
    • pp.523-529
    • /
    • 2019
  • In this study, we investigated the pretreatment technologies of volatile organic compounds (VOCs) which is a problem as the semiconductor and display industry develops recently. The conventional concentrator used in the direct combustion system, is easily contaminated by the exhaust gas in the manufacturing process of the display, resulting in the low treatment efficiency of generated VOCs. Physical/Chemical analyses of the exhaust gas showed high boiling point and viscosity in addition to a large amount of molecular weight alcohols and oil components. In this study, we tried to treat degrading materials by using the heat exchanger in a pretreatment facility and some materials degrading the concentrator were condensed more than 90%. In addition, it was also confirmed that an auxiliary device of the grease filter could remove the redispersion polymer oil from the heat exchanger.