• 제목/요약/키워드: 유하액막

검색결과 24건 처리시간 0.03초

LiBr 수용액의 수평관 유하액막 증발에 있어서의 열전달계수 특성 (The characteristics of heat transfer coefficient for falling-film evaporation on a horizontal tube with aqueous LiBr solution)

  • 지용해;김동관김무환
    • 대한기계학회논문집B
    • /
    • 제21권2호
    • /
    • pp.294-302
    • /
    • 1997
  • Falling-film evaporation experiments for aqueous solution of lithium bromide (LiBr) were performed on a horizontal smooth 19.05-mm-dia copper tube. Average heat transfer coefficients were obtained with varied film Reynolds numbers, system pressures, LiBr concentrations and degrees of wall superheat. Heat transfer coefficients increase with increasing system pressure and decreasing concentration. For degrees of wall superheat, the heat transfer coefficient did not't show the distinct trend. For this experimental ranges, heat transfer coefficients showed maximum values at an optimal film Reynolds number. The results of this work were compared with pool boiling data reported previously, and it was shown that the heat transfer performance is superior to the pool boiling.

LiBr 수용액을 이용한 수평관 유하액막 증발의 촉진관 전열향상 특성 (Heat Transfer Enhancement Characteristics for Falling-Film Evaporation on Horizontal Enhanced Tubes with Aqueous LiBr Solution)

  • 김동관;김무환
    • 대한기계학회논문집B
    • /
    • 제22권9호
    • /
    • pp.1267-1276
    • /
    • 1998
  • Falling-film evaporation experiments with aqueous lithium bromide (LiBr) solution were performed to investigate the heat transfer characteristics of enhanced copper tubes. Enhanced tubes (a knurled tube, a spirally grooved tube, and a tube coated with $20{\mu}m$ aluminum particles) and a bare tube were selected as test specimens. Averaged evaporation fluxes of water were obtained from horizontal tubes with various film Reynolds numbers, system pressures, LiBr concentrations and degrees of wall superheat. The enhanced performance of steam generation was compared between tubes with varying parameters. The knurled tube geometry showed the most excellent performance among the tubes tested. The specified enhanced tubes were more useful for generating steam on a low grade heat source such as waste heat.

암모니아-물 흡수식 시스템에서 유하액막식 발생기의 해석 (Analysis of Falling-film Generator in Ammonia-water Absorption System)

  • 김병주;손병후;구기갑
    • 설비공학논문집
    • /
    • 제13권5호
    • /
    • pp.422-430
    • /
    • 2001
  • In the present study, an evaporative generation process of ammonia-water solution film on the vertical plate was analysed. For the utilization of waste heat, hot water of low temperature was used as the heat source. The continuity, momentum, energy and diffusion equations for the solution film and vapor mixture were formulated in integral forms and solved numerically. Counter-current solution-vapor flow resulted in the refrigerant vapor of the higher ammonia concentration than that of co-current flow. Eve the rectification of refrigerant vapor was observed near the inlet of solution film in counter-current flow. For the optimum operation of generator using hot water, numerical experiments, based on the heat exchange and generation efficiencies. revealed the inter-relationships among the Reynolds number of the solution film and hot water, and the length of generator. Enhancement of heat and mass transport in the solution film was found to be very effective for the improvement of generation performance, especially at high solution flow rate.

  • PDF

코일형 흡수기에서 증기 유동 방향이 유하액막 열전달에 미치는 영향 (제1부: 물을 이용한 실험) (Effect of Vapor Flow Direction on Falling Film Heat Transfer in a Coiled Tube Absorber (Part 1: Experiments with Pure Water))

  • 박경진;권경민;정시영;김병주
    • 설비공학논문집
    • /
    • 제13권8호
    • /
    • pp.720-729
    • /
    • 2001
  • The effect of vapor flow direction on falling film heat transfer was experimentally investigated by using water. Parallel flow (both water and vapor downwards) showed higher heat exchange performance than counterflow(downward water and upward vapor). The difference became significant as the vapor flow rate was increased. It is supposed that the uprising vapor disturbs the solution film flow and heat transfer is reduced by uneven distribution or detachment of water film.

  • PDF

흡수성능에 미치는 수직 액막 파동의 영향에 관한 연구 (Effect of Wavy Flow of Vertical Falling Film on the Absorption Performance)

  • 김정국;조금남
    • 설비공학논문집
    • /
    • 제16권2호
    • /
    • pp.194-201
    • /
    • 2004
  • In the present study, the improvement of absorption characteristics on combined heat and mass transfer process in a falling film of a vertical absorber by change of geometric parameters were studied experimentally and analytically. The energy and diffusion equations are solved simultaneously to give the temperature and concentration variations at the liquid solution-refrigerant vapor interface and at the wall. Absorption behaviors of heat and mass transfer were analyzed through falling film of the LiBr aqueous solution contacted by refrigerant vapor in the absorber. Effects of film Reynolds number, geometric parameters by insert device (spring) and flow pattern on heat and mass transfer performances have been also investigated. Especially, effects of the flow pattern by geometric parameters have been considered to observe the total heat and mass transfer rates through falling film along the absorber. As a numerical and experimental result, maximum absorption rate was shown at the wave-flow by insert device (spring). The error ranges between experiment and analysis were from 5.8 to 12% at Re$_{f}$ > 100.0.

채널내 공기유동이 있는 유하액막의 열전달특성에 관한 실험적 연구 (An Experimental study on heat transfer of a falling liquid film in air channel flow)

  • 오동은;강병하;김석현
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2007년도 춘계학술대회B
    • /
    • pp.2291-2296
    • /
    • 2007
  • Thermal transport from vertical heated surface to falling liquid film in a channel has been investigated experimentally. Air-flow is introduced into channel to make a counter flow against falling liquid film. This problem is of particular interest in the design of direct contact heat exchange system, such as cooling tower, evaporative cooling system, absorption cooling system, and distillation system. The effects of channel width and air flow rate on the heat transfer to falling liquid film are studied in detail. The results obtained indicate that heat transfer rate is gradually decreased with an increase in the channel width without air flow as well as with air flow in a channel. It is also found that heat transfer rate of air-flow is increased while heat transfer rate of falling liquid film is decreased with an increase in the air flow rate at a given channel width. However, total heat transfer rate form the heated surface is increased as the air flow rate is increased.

  • PDF

리튬브로마이드 수용액 유하액막의 흡수과정에 대한 근사 해법 : 증기 유동의 영향 (Approximate solutions on the absorption process of an aqueous LiBr falling film : effects of vapor flow)

  • 김병주;이찬우
    • 설비공학논문집
    • /
    • 제9권2호
    • /
    • pp.144-152
    • /
    • 1997
  • Film absorption involves simultaneous heat and mass transfer in the vapor-liquid system. In the present work, the absorption process of water vapor by an aqueous soluton of LiBr flowing inside of the vertical tube was investigated. The continuity, momentum, energy and diffusion equations for the solution film and vapor were formulated in integral forms and solved numerically. The model could predict the film thickness, the pressure gradient, and the heat and mass transfer rate. Particularly the effects of vapor flow conditions on the absorption process were investigated in terms of the vapor Reynolds number. As the vapor Reynolds number increased, the shear stress at the vapor-solution interface also increased. Consequently solution film became thinner at higher vapor flowrate under the co-currentflow condition. Thinner film was capable of higher heat transfer to the wall and leaded to higher absorption rate of the water vapor into the solution film.

  • PDF

수직원관 외부 유하액막 열전달에 주변 기체유동이 미치는 영향 (The Effect of Surrounding Gas Flow on the Heat Transfer of the Falling Film Flowing Down the Outside of a Vertical Tube)

  • 권경민;정시영;김병주
    • 설비공학논문집
    • /
    • 제14권12호
    • /
    • pp.996-1003
    • /
    • 2002
  • Heat transfer characteristics were investigated for the falling film flowing down the outside of an electrically heated vertical tube. Water was used for the falling film, and its Reynolds number was varied in the range of 70~500. Because water is heated and evaporated as it flows down, both sensible and latent heat transfer should be considered. The effect of the surrounding air movement was investigated by changing the direction of the air injection; without air injection, parallel-flow, and counter-flow. For all cases, sensible teat transfer rate was almost linearly increased with the increasing film flow rate. It was found that the film heat transfer coefficient was hardly influenced by the parallel air flow. However, the counter-flow of air reduced the heat transfer coefficient, which might be caused by the uneven distribution or flooding of the film. At high heat flux, a sudden change of the film heat transfer coefficient was detected as the film flow rate reached the transition value. It is supposed that this phenomenon was caused by the change in the film flow pattern.

수평단관 상의 유하액막 열전달 (Falling Film Heat Transfer on a Horizontal Single Tube)

  • 김동관;김무환
    • 설비공학논문집
    • /
    • 제12권7호
    • /
    • pp.642-648
    • /
    • 2000
  • Falling film heat transfer analyses with aqueous lithium bromide solution were peformed to investigate the transfer characteristics of the copper tubes. Finned(knurled) tube and a smooth tube were selected as test specimens. Averaged generation fluxes of water and the heat transfer performances(heat flux, heat transfer coefficient) were obtained. The results of this work were compared with the data reported previously. As the film flow rate of the solution increased, the generation fluxes of water decreased for both tubes. The reason is estimated by the fact that the heat transfer resistance with the film thickness increased as the film flow rate increased. The effect of the enlarged surface area at the knurled tube was supposed to be dominant at a small flow rate. The generation fluxes of water increased with the increasing degree of tube wall superheat. Nucleate boiling is supposed to occur at a wall superheat of 20 K for a smooth tube, and at 10 K for a knurled tube. The heat transfer performance of the falling film was superior to pool boiling at a low wall superheat below 10 K for both tubes tested. The knurled tube geometry showed good performance than the smooth tube, and the increased performance was mainly came from the effect of the increased heating surface area.

  • PDF