Performance of a room air conditioner using R410A according to the variation of outdoor temperature (실외온도 변화에 따른 R410A 적용 에어콘 시스템의 성능)

  • 김병순;이승홍
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.4
    • /
    • pp.537-541
    • /
    • 1999
  • The system performance of a room air conditioner using R410A was experimentally evaluated and compared with that of R22 system. The results indicated that the cooling EER(energy efficiency ratio) of R410A was 1% higher than that of R22 at the outdoor temperature of $35^{\circ}C$. As outdoor temperature increases above $35^{\circ}C$ ambient, EER of the R410A system decreased more substantially compared with R22 system. R410A showed higher compressor discharge temperature than that of R22 system at the outdoor temperature of higher than $50^{\circ}C$.