Characteristics of loci on Line-to-Earth Voltage according to Earth Fault in Earthing System for Ships (선박의 접지 시스템에서 지락 고장에 따른 대지 전압 변동 특성)

  • Kim, Jong-Phil;Ryu, Ki-Tak;Lee, Yun-Hyung
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.22 no.2
    • /
    • pp.487-495
    • /
    • 2021
  • The voltages mainly used in ships are 450 [V], 6.6 [kV], and 11 [kV], and an earthed system is applied to ensure the stability of the power distribution system. In general, low-voltage ships using 450 [V] apply an unearthed system, while high-voltage ships using 6.6 [kV] or 11 [kV] use a high-resistance earthed system. When an earth fault occurs in a ship's power distribution system, the voltage of the healthy phase increases to the line-to-line voltage or higher, which causes an excessive impact on the insulation of the cable. Thus, analyzing this behavior is very important. In this paper, we investigate the characteristics of the line-to-earth voltage variation according to earth faults and a recognition procedure of a faulty phase using the symmetrical coordinate method for a high-resistance earthed system and unearthed system. A mathematical model of the line-to-earth voltage was derived through the symmetric coordinate method, and the ship voltage for simulations was selected as 6.6 [kV] and 450 [V]. A MATLAB simulation proved that this method can determine the highest increase of the line-to-earth voltage, which leads by 120° on the faulty phase, and it accurately judges the faulty phase in both earthed systems.