• Title/Summary/Keyword: 외기냉방

Search Result 61, Processing Time 0.023 seconds

Effects of Control Methods of Outdoor Air Cooling System on Energy Consumption in Building (외기냉방 시스템의 제어방법이 에너지 소비량에 미치는 영향에 관한 연구)

  • Hwang, Jin-Won;Ahn, Byung-Cheon
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.6
    • /
    • pp.4253-4259
    • /
    • 2015
  • In this study, the effects of various control methods of outdoor air cooling control system on control characteristics and energy consumption in building are researched by simulation. The system analysis modelling is done by using TRNSYS program package, and the control performances with existing outdoor air cooling methods are compared with the control ones without outdoor air cooling. As a result, appropriate operating temperature conditions of outdoor air cooling system according to outdoor temperature changes are required, and the outdoor air/return air dry bulb temperature comparison control method among the control methods shows best responses in energy savings.

A study on design for free cooling system using dry cooler (드라이쿨러를 적용한 외기냉수냉방 시스템 설계에 관한 연구)

  • Yoon, Jung-In;Baek, Seung-Moon;Heo, Jeong-Ho;Kim, Young-Min;Son, Chang-Hyo
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.38 no.9
    • /
    • pp.1027-1031
    • /
    • 2014
  • Free cooling system is used to reduce energy consumption of cooling system. Free cooling system is consisted of cooling group and dry-cooler in which heat exchange of chilled water and out air is conducted. Although this system has an excellent energy saving effect in place having cooling load regularly, data or material of design for free cooling system is lacked. In this study, characteristics analysis of free cooling system is conducted through software HYSYS with changing some facts. The main result is following as : Dry-cooler capacity is influenced by out air temperature, required chilled water temperature and LMTD(Logarithmic Mean Temperature Difference) of heat exchanger. As out air temperature is more low, dry-cooler capacity become increased. in addition, as required chilled water temperature is more high and LMTD is more low, the out air temperature range is widened for using dry-cooler. If out air temperature is below $0^{\circ}C$, antifreeze need to be used because freeze and burst can be occurred. In case of South Korea, antifreeze of 34% of ethylene glycol concentration is proper. When compressor load of R22, R134a and R407C is compared, considering environmental regulation and energy consumption, R134a is best working fluid.

Reduction of Cooling Load using Outdoor Air Cooling (외기냉방을 이용한 냉방부하 절감 연구)

  • Kim, Min-Yang;Kim, Young-Il;Chung, Kwang-Seop
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.7 no.1
    • /
    • pp.51-58
    • /
    • 2011
  • Due to enhanced sealing and insulation of buildings, extensive use of glasses for building envelopes and increased use of heat generating office equipments, energy consumption of modem buildings for cooling is steadily increasing. With outdoor air cooling(ODAC) system, cooling load can be reduced by exchanging indoor air with the cold outdoor air during spring and fall seasons. If ODAC is operated based only on temperature, total cooling load may virtually increase if the outdoor humidity is high. To overcome this problem, ODAC should be controlled based on enthalpy. In this work energy saving characteristics of enthalpy controlled ODAC is studied using dynamic simulation. The result shows that cooling load can be reduced by 27% by adopting ODAC.

Energy Performance of Air-side Economizer System for Data Center Considering Supply Temperature and Design Airflow Rate of CRAH(Computer Room Air Handler) (외기냉방시스템이 적용된 데이터센터 CRAH의 급기온도와 설계 풍량에 따른 에너지성능 분석)

  • Kim, Ji-Hye;Aum, Tae-Yun;Jeong, Cha-Su
    • Journal of the Architectural Institute of Korea Structure & Construction
    • /
    • v.35 no.11
    • /
    • pp.181-188
    • /
    • 2019
  • The purpose of this study is to evaluate the cooling energy saving effects of CRAH supply air temperature(SAT) and design flow rate changes when applying air-side economizer in the data center. MLC(Mechanical Load Component), which is cooling performance indicator of data center, was used to assess the effectiveness of cooling energy savings. It was computed with energy simulation (DesignBuilder) to evaluate the cooling energy performance of 8 different alternatives in a data center. The MLC was 0.31~0.32 regardless of CRAH supply temperature without air-side economizer, and 0.15 to 0.19 value with air-side economizer. That is, cooling energy can be reduced by approximately 40~55% when applying economizer. As the CRAH SAT and design flow rate changed, the MLC values were 0.16 to 0.18 and 0.15 to 0.19, respectively.

Characteristic Analysis of Hybrid Desiccant Cooling System for District Heating in Residential Environment (지역난방에 연계된 하이브리드 제습냉방시스템의 주거환경에서의 성능 분석)

  • Ahn, Joon;Kim, Jaeyool;Kang, Byung Ha
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.38 no.7
    • /
    • pp.571-579
    • /
    • 2014
  • A series of field tests on hybrid desiccant cooling systems were conducted in July-August, 2013. The temperature and humidity of the supply and return air, power, and heat consumption were monitored and transferred in real time through the Internet. The performance parameters of the cooling system, namely, cooling capacity and COP (coefficient of performance), were evaluated from the measured data and their variations under outdoor conditions was analyzed. It was found that with increase in the outdoor temperature, the total energy decreases and cooling capacity increases whereas the latter decreases with increase in the outdoor humidity. The COP was also found to increase with the increase in outdoor temperature.

Performance Analysis of Hybrid Desiccant Chiller Based on Field Test (실증 실험을 통한 하이브리드 제습냉방 시스템의 성능 분석)

  • Ahn, Joon;Yun, Changho;Kang, Byung Ha
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.37 no.7
    • /
    • pp.621-627
    • /
    • 2013
  • Field tests of hybrid desiccant cooling systems were conducted from July to August 2011. Data were monitored and transferred in real time over the Internet. The monitored variableswere analyzed to determine the performance characteristics under outdoor conditions. A series of system simulations has been conducted for outdoor conditions of the field tests. The results agree well with the experimental data in general. The system performance has been shown to deteriorate for wetter conditions, as predicted by the simulation.

A Study on Building Energy Saving using Outdoor Air Cooling by Load Prediction (부하예측 외기냉방에 의한 건물에너지 절약에 관한 연구)

  • Kim, Tae-Ho;Yoo, Seong-Yeon;Kim, Myung-Ho
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.29 no.2
    • /
    • pp.43-50
    • /
    • 2017
  • The purpose of this study is to develop a control algorithm for outdoor air cooling based on the prediction of cooling load, and to evaluate the building energy saving using outdoor air cooling. Outdoor air conditions such as temperature, humidity, and solar insolation are predicted using forecasted information provided by the meteorological agency, and the building cooling load is predicted from the obtained outdoor air conditions and building characteristics. The air flow rate induced by outdoor air is determined by considering the predicted cooling loads. To evaluate the energy saving, the benchmark building is modeled and simulated using the TRNSYS program. Energy saving by outdoor air cooling using load prediction is found to be around 10% of the total cooling coil load in all locations of Korea. As the allowable minimum indoor temperature is decreased, the total energy saving is increased and approaches close to that of the conventional enthalpy control.

Viability of HVAC System for Energy Conservation in High Density Internal-load Dominated Buildings (고밀도 내부부하 중심 건물의 에너지 절약적 공조방식에 대한 연구)

  • Cho, Jin-Kyun;Jeong, Cha-Su;Kim, Byung-Seon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.22 no.8
    • /
    • pp.530-537
    • /
    • 2010
  • With the advancement of technology, the density of IT equipment, heat load and power consumption continue to increase in high density internal-load dominated buildings as datacenters. To improve the HVAC system's energy performance and efficiency, there is a need to find methods of using outside air. Through cooling tower control that is based on outside wet-bulb temperature, the water-side economizer made it possible to achieve a maximum energy performance improvement of about 16.6% over the basic chilled water system, whereas the air-side economizer, through control based on outdoor air enthalpy, made it possible to achieve about 42.4% improvement.

An Analysis of Heating and Cooling Energy and Effect on Outdoor Air Cooling according to Building Type of Apartment Complex (공동주택 단지의 주동형식에 따른 냉난방 에너지 및 외기냉방 효과 분석)

  • Roh, Ji-Woong
    • Journal of the Korean Solar Energy Society
    • /
    • v.34 no.4
    • /
    • pp.31-38
    • /
    • 2014
  • This study makes three apartment building complex an object of analyzing representative building types and energy consumption rate of house holds, and effect of outdoor air cooling. Recently created apatrment complex is composed of very various types of building, plan, and orientation etc. But, it is difficult to remark conclusively that these various types of buildings are designed energy-effectively. Because architects are hard to find useful energy design guideline for decision making. By the preceding study, the present condition and problem about this subject is grasped, apartment building types were examined and representative types were extracted. In this study, energy simulation was conducted, and the effect to outdoor air cooling was analyzed about representative types of the subject apartment complex. It is expected that this analysed results will be basic data for the more integrated study. Research consequence can be summarized as follow: 1) Besides solar gain, household layout of building, orientation, and plan etc. effects compositively on energy consumption rate. 2) The effect of ourdoor air cooling in building of tower type can be improved by arranging households appropriately.