• 제목/요약/키워드: 액체 제습식 냉방 시스템

검색결과 2건 처리시간 0.017초

액체 제습식 냉방 시스템의 최적 설계 (Optimization Design of Liquid Desiccant Cooling System)

  • 전동순;이상재;김선창;김영률;이창준
    • 설비공학논문집
    • /
    • 제22권7호
    • /
    • pp.419-428
    • /
    • 2010
  • This paper presents the optimization process of liquid desiccant cooling system using LiCl aqueous solution as a working fluid. Operating conditions(mass flow rate, conditioner outlet concentration, difference concentration) and design factors for heat exchangers(difference temperature of the district heating water, leaving temperature difference of the conditioner, leaving temperature difference of the regenerator, air temperature difference of the conditioner, air temperature difference of the regenerator) were optimized by response surface method. As a result, we obtained the 7.297 kW of cooling capacity and 0.788 of COP at optimized condition. Effect of difference temperature of hot water on system performances was also examined. As difference temperature of the district heating water increases, the cooling capacity increases and COP decreases.

냉각식 시스템과 비교한 복합식 제습냉방시스템의 냉각 열량증가에 관한 실험적 연구 (Study on the Energy Efficiency Improvement of Hybrid Dehumidification Air Conditioning System Compared with Refrigeration System)

  • 이수동;박문수;정진은;최영석
    • 설비공학논문집
    • /
    • 제16권10호
    • /
    • pp.952-959
    • /
    • 2004
  • The hybrid liquid desiccant air conditioning system has been in use for many years, primarily in industrial process applications requiring dehumidification and humidity control. In this study, the hybrid dehumidifier has been designed to study the dehumidification characteristic of the aqueous triethylene glycol (TEG) solution. The experimental results show energy efficient characteristics of hybrid liquid desiccant air conditioning system compared with the refrigeration system in terms of energy use, the difference of pressure loss between hybrid liquid desiccant air conditioning system and refrigeration system. Data obtained are useful for design guidance and performance analysis of the hybrid air conditioning system.